5 Functions
20
db
for double-setpoint controller
HYS.1
Differential 1 (controller output 1)
Differential 2 (controller output 2)
for controllers with
Pb.1
=0 or
Pb.2
=0
HYS.2
Y:0
Working point (basic load)
Output if process value=setpoint
Y:1
Output limiting
y:1
- maximum output
y:2
- minimum output
Y:2
Symbol
Notes
H
For controllers without controller structure (
Pb.1
=0 or
Pb.2
=0), it is necessary
that
y:1
=100% and
y:2
=-100%.
b70.2040en.bk Seite 20 Mittwoch, 19. November 2008 10:15 10