7 Mounting
26
7.3.3
Terminal assignment and use of a selection switch
HINWEIS!
Galvanic isolation of relay outputs DO2 and DO3
Mixed switching of mains voltage AC 230 V and SELV or PELV voltage is not admissible due to the basic
insulation between the relays!
(1)
Terminal strip
I out Current output AO1 (4 to 20 mA)
L+
V+ (positive power supply)
L-
0 V (ground for the power supply)
PE
Functional ground, wired at the plant (
see "Terminal strip 1: Connecting
the grounding cable ", page 27)
P+
Positive transistor output DO1
P-
Negative transistor output DO1
(2)
Terminal strip
PE
Shielding on the supply cable and output cables of AO1 and DO1
(3)
Terminal strip
PE
Functional ground for the cable for the DI1 digital input
-
Negative signal for the digital input DI1
+
Positive signal for the digital input DI1
(4)
Terminal strip
Connection for the relay output DO2
(5)
Terminal strip
Connection for the relay output DO3
(6)
Terminal strip
4-pin ribbon cable for connecting the sensor
(A)
Switch
see "Use of the sink selection switch (right) or source selection switch
(B)
Switch
see "Use of the selection switch to lock or unlock the CONFIRM key ", page 27