background image

+

+

-

-

+

-

HART

mA

+

-

+

-

4...20 mA

+

-

V

7

6

8

5

+

-

112 mm

106.5 mm

6.1 mm

107 mm

112 mm

3xxx Housing

 

115 mm

+

-

+

-

2

3

1

4

 

 V1.00/EN/00698632 - 70710100T90Z001K000 

15

Connections

Input wiring

Output wiring

Supply wiring

*JUMO dTRANS 
T08 01 - only 
internal CJC

JUMO dTRANS T08 01, JUMO dTRANS T08 02 and JUMO dTRANS T08 33:  No galvanic isolation 
JUMO dTRANS T08 31 and JUMO dTRANS T08 37: 

2 port isolation (reinforced) 

JUMO dTRANS T08 11, JUMO dTRANS T08 12 and JUMO dTRANS T08 13:  3 port isolation (reinforced)

External CJC  

(2- or 3-wire Pt100)

-

-

-

3

2

Y* JUMO dTRANS T08 01

1,2 & 3,4

1,2 & 3

2 & 3

-

-

N JUMO dTRANS T08 02

-

-

-

3

2

Y

JUMO dTRANS T08 11

1,2 & 3,4

1,2 & 3

2 & 3

-

-

N JUMO dTRANS T08 12

1,2 & 3,4

1,2 & 3

2 & 3

3

2

Y

JUMO dTRANS T08 13

1,2 & 3,4

1,2 & 3

2 & 3

3

2

Y

JUMO dTRANS T08 31

1,2 & 3,4

1,2 & 3

2 & 3

-

-

N JUMO dTRANS T08 33

1,2 & 3,4

1,2 & 3

2 & 3

3

2

Y

JUMO dTRANS T08 37

+

-

Type

CJC

JUMO dTRANS 
T08 01

N

5

6

5

6

-

-

7

8

N

JUMO dTRANS 
T08 02

N

5

6

5

6

-

-

7

8

N

JUMO dTRANS 
T08 11

N

5

6

5

6

-

-

7

8

Y

JUMO dTRANS 
T08 12

N

5

6

5

6

-

-

7

8

Y

JUMO dTRANS 
T08 13

Y

5

6

-

-

-

-

7

8

Y

JUMO dTRANS 
T08 31

N

-

-

-

-

5

6

-

-

N

JUMO dTRANS 
T08 33

N

-

-

-

-

5

6

-

-

N

JUMO dTRANS 
T08 37

Y

-

-

-

-

5

6

-

-

N

JUMO dTRANS  
T/S08 PCU

N

-

-

-

-

-

-

7

8

Y

24 VDC

Power  

rail

+ V

supply

CJC

Summary of Contents for dTRANS T08 01

Page 1: ...Zone 2 ZONE 2 JUMO dTRANS T08 XX Temperature transmitter series 6 mm 707101 707102 707111 707112 707113 707131 707133 707137 Operating Manual 70710100T90Z001K000 V1 00 EN 00698632 ...

Page 2: ...ctions 3 UL installation 4 IECEx ATEX installation in Zone 2 4 Flexible supply 6 Mounting and demounting of JUMO dTRANS T S08 7 Installation on DIN rail power rail 8 Supply of power rail 8 Marking 8 Side label 9 Applications 10 Technical characteristics 10 Mounting installation 10 Order codes 11 Accessories 11 Accessories for power rail devices 11 Technical data 11 Connections 15 Front led indicat...

Page 3: ...static charging hazard To avoid the risk of explosion due to electrostatic charging of the enclosure do not handle the units unless the area is known to be safe or appropriate safety measures are taken to avoid electrostatic discharge Symbol identification Triangle with an exclamation mark Read the manual before installation and commissioning of the device in order to avoid incidents that could le...

Page 4: ... unit for the device JUMO dTRANS T S08 must be mounted on a DIN rail according to EN 60715 UL installation Use 60 75 C copper conducters only Wire size AWG 26 12 UL file number E201387 The device is an Open Type Listed Process Control Equipment To prevent injury resulting from accessability to live parts the equipment must be installed in an enclosure The power supply unit must comply with NEC Cla...

Page 5: ... profile TN 00697614 supplied by Power connector unit for dTRANS T S08 XX TN 00697612 is allowed To prevent ignition of the explosive atmospheres disconnect power before servicing and do not separate connectors when energised and an explosive gas mixture is present Do not mount or remove devices from the power rail when an explosive gas mixture is present Cleaning When disconnected the device may ...

Page 6: ...ct 24 VDC to any one JUMO dTRANS T S08 device with power rail connector which will then energize other units on the rail Protective fuse 2 5 A DIN rail solution device daisy chain The JUMO dTRANS T08 01 T08 02 T08 11 T08 12 and T08 13 can be supplied with 24 VDC 30 via direct wiring and a loop between the devices Power rail solution 2 The JUMO dTRANS T S08 PCU power connector unit allows easy conn...

Page 7: ...N rail power rail Click the device onto the rail Picture 2 Demounting from DIN rail power rail First remember to demount the connectors with hazardous voltages Detach the device from the DIN rail by lifting the bottom lock Picture 3 Wire size AWG 26 12 0 13 x 2 5 mm2 stranded wire Screw terminal torque 0 5 Nm ...

Page 8: ...connectors on a standard DIN rail the head of the screws holding the 7 5 mm DIN rail shall be no more than 3 5 mm high in order to avoid short circuit between the power rail connectors on the device and the screws Supply of power rail It is possible to supply the power rail via the supply terminals The terminals can pass a current of max 400 mA Marking The front cover of the JUMO dTRANS T S08 devi...

Page 9: ...V1 00 EN 00698632 70710100T90Z001K000 9 Side label ...

Page 10: ... protects the control system from transients and noise The loop powered devices have high 2 port galvanic separation to eliminate ground loops The devices can be mounted in the Safe area or in Zone 2 Division 2 areas Approved for marine applications Technical characteristics High conversion accuracy better than 0 05 of span A visible green LED indicates operational status and status of the input s...

Page 11: ...egree 2 overvoltage category II Mechanical specifications Dimensions HxWxD 113 x 6 1 x 115 mm Weight approx 70 g DIN rail type DIN EN 60715 35 mm Wire size 0 13 2 5 mm2 AWG 26 12 stranded wire Screw terminal torque 0 5 Nm Vibration IEC 60068 2 6 2 25 Hz 1 6 mm 25 100 Hz 4 g Input Output LED Supply Isolated HART TC Pt100 Current Volt age J K Int CJC Ext CJC 2 3 4 wire Active Passive JUMO dTRANS T08...

Page 12: ...r is the maximum power needed at power supply terminals or rail connector Max power dissipation is the maximum power dissipated at nominal operating values Isolation voltage test 2 5 kVAC Isolation voltage working 300 VAC reinforced 250 VAC Zone 2 Div 2 Double isolation Input output 1 output 2 supply Signal dynamics input 23 bit Signal dynamics output 18 bit Signal noise ratio Min 60 dB Incorrect ...

Page 13: ...84 1 Min measuring range span 50 C Sensor cable resistance 5 kΩ per wire Cold junction compensation CJC accuracy Accuracy external Pt100 Better than 0 15 C Accuracy internal CJC Better than 2 5 C Open Thermocouple detection Yes selectable via DIP switch Internal CJC error detection Yes External CJC error detection Yes selectable via DIP switch Device Input Basic accuracy General accuracy Temperatu...

Page 14: ...S T08 01 0 4 20 mA 0 3 8 20 5 mA 0 3 5 23 mA 600 Ω JUMO dTRANS T08 02 0 4 20 mA 0 3 8 20 5 mA 0 3 5 23 mA 600 Ω JUMO dTRANS T08 11 0 4 20 mA 0 3 8 20 5 mA 0 3 5 23 mA 600 Ω JUMO dTRANS T08 12 0 4 20 mA 0 3 8 20 5 mA 0 3 5 23 mA 600 Ω JUMO dTRANS T08 13 4 20 mA 0 3 8 20 5 mA 0 3 5 23 mA 600 Ω JUMO dTRANS T08 31 4 20 mA 3 8 20 5 mA 3 5 23 mA Vsupply 5 5 0 023 Ω JUMO dTRANS T08 33 4 20 mA 3 8 20 5 mA...

Page 15: ...einforced External CJC 2 or 3 wire Pt100 3 2 Y JUMO dTRANS T08 01 1 2 3 4 1 2 3 2 3 N JUMO dTRANS T08 02 3 2 Y JUMO dTRANS T08 11 1 2 3 4 1 2 3 2 3 N JUMO dTRANS T08 12 1 2 3 4 1 2 3 2 3 3 2 Y JUMO dTRANS T08 13 1 2 3 4 1 2 3 2 3 3 2 Y JUMO dTRANS T08 31 1 2 3 4 1 2 3 2 3 N JUMO dTRANS T08 33 1 2 3 4 1 2 3 2 3 3 2 Y JUMO dTRANS T08 37 Type CJC JUMO dTRANS T08 01 N 5 6 5 6 7 8 N JUMO dTRANS T08 02 ...

Page 16: ...cate the operation status see the table below Condition LED Output Action required No supply device error OFF De energized Connect supply replace device Power up or restart 1 Flash 0 5 s OFF 0 5 s ON De energized Device OK Flashing 13 Hz 15 ms ON Energized Incorrect DIP switch setting Flashing 1 Hz 500 ms ON De energized Correct setting and re power device Sensor error indication Flashing 1 Hz 15 ...

Page 17: ...MO dTRANS T08 13 and JUMO dTRANS T08 37 Pt100 TC J K HART JUMO dTRANS T08 33 Pt100 JUMO dTRANS T08 02 JUMO dTRANS T08 12 JUMO dTRANS T08 31 JUMO dTRANS T08 33 JUMO dTRANS T08 01 JUMO dTRANS T08 11 JUMO dTRANS T08 13 JUMO dTRANS T08 37 Sensor type Pt100 3 wire TC K int CJC Pt100 3 wire Output range 4 20 mA 4 20 mA 4 20 mA Error detection Short circuit detection Broken circuit detection Short circui...

Page 18: ...ge 100 1200 C correct DIP switch setting Valid TC K range 180 1372 C correct DIP switch setting JUMO dTRANS T08 02 JUMO dTRANS T08 12 and JUMO dTRANS T08 33 only Pt100 input available Valid Pt100 range 200 850 C correct DIP switch setting Start temp must be lower than End temp correct DIP switch setting Power must be cycled after DIP switch positions are changed ...

Page 19: ... address 36035 Fulda Germany Phone 49 661 6003 0 Fax 49 661 6003 607 Email mail jumo net Internet www jumo net JUMO House Temple Bank Riverway Harlow Essex CM20 2DY UK Phone 44 1279 63 55 33 Fax 44 1279 62 50 29 Email sales jumo co uk Internet www jumo co uk 6733 Myers Road East Syracuse NY 13057 USA Phone 1 315 437 5866 Fax 1 315 437 5860 Email info us jumo net Internet www jumousa com ...

Reviews: