4 Commissioning the instrument
14
Input
Sensor connected in 2-wire circuit
Measurement input group 1 on Type: 701540/X11-XX
Pt100:
Pt1000:
KTY2X-6:
or
Measurement input group 2 on Type: 701540/X21-XX
Fe-Con J :
Fe-Con L:
NiCr-Ni K:
or
Measurement input group 3 on Type: 701540/X31-XX
0(4)... 20 mA:
/
Measurement input group 4 on Type: 701540/X41-XX
0 ... 10 V:
/
Start value
for indication range with measurement input voltage or current
Example: input signal 4 — 20mA is to be represented in the display from
-10 to 50. Set S.cL= -10 and S.cH=50.
-999 ...
0
... +999
End value
for indication range with measurement input voltage or current
-999 ...
100
... +999
Signal
for measurement input current: 0 = 0 to 20mA
1 = 4 to 20mA
0, 1
Process value offset
PV offset in °C, °F or digit (no unit)
-99.9 ...
0.0
... 99.9
Parameter Meaning
Value range
from...
factory-set
...to