4 Commiss
ioni
ng t
h
e in
st
ru
me
nt
12
Process value offset
process value offset in °C, °F or digit (no unit)
-99.9 ...
0.0
... 99.9
Lead compensation resistance
This value is used for compensating the resistance of the probe lead for re-
sistance sensors and is dependent on the lead length.
For best temperature measurement results, the resistance value of the
probe lead has to be entered here.
0.0 ...
0.0
... 99.9 in
Ω
Unit
for the indicated process value
°C
,
°
F or
no (= no unit)
Parameter
Meaning
Value range
from...
factory-set
...to
A
If the total resistance at the measurement input (sensor resi
selected value for OF.r) exceeds 320
Ω
with Pt100 or 3200
Ω
with
Pt1000/KTY2x-6, a measurement error will occur !
A
For settings in °F, the process value will be converted correspond-
ingly. All other setting, such as for SP, will retain their values.