4 Commissi
oning the instr
u
ment
11
Response to over/underrange
0: relay de-energized
1: relay energized
0
, 1
Input
Sensor connected in 2-wire circuit
Measurement input group 1 on Type: 701050/X1X-1-XX
Pt100:
Pt1000:
KTY2X-6:
or
Measurement input group 2 on Type: 701050/X2X-1-XX
Fe-Con J:
Fe-Con L:
NiCr-Ni K:
or
Measurement input group 3 on Type: 701050/X3X-1-XX
0(4)... 20 mA:
/
Measurement input group 4 on Type: 701050/X4X-1-XX
0 ... 10 V:
/
Start value
for indication range with measurement input voltage or current.
Example: input signal (e.g. 4 — 20mA) is to be represented on the display
from -10 to 50. Setting: S.cL= -10 and S.cH=50.
-999 ...
0
... +999
End value
for indication range with measurement input voltage or current
-999 ...
100
... +999
Signal
for measurement input current: 0 = 0 — 20mA
1 = 4 — 20mA
0
, 1
Parameter
Meaning
Value range
from...
factory-set
...to