3 Electrical connection
20
3.4
Functional test
The
voltage supply
and the
connection to the system bus
must be tested on completion of the elec-
trical connection.
Voltage supply
Connection to system bus
The "Bus In" input must be connected to the "Bus Out" output of an upstream router module or to the
"LAN2" socket of the central processing unit 705003.
Startup
The check described above completes the process of installation and electrical connection. For the start-
up, the router module is integrated into the system through the definition of the hardware arrangement
in the setup program. The router module itself does not need to be configured (see operating manual of
the central processing unit).
LEDs at the RJ45 sockets
The LEDs indicate the status of the connection between the router module and the remote side.
NOTE!
The LED "S" (Status) indicates the system status and, if necessary, module-specific errors (depending
on the module). In normal operation it lights green (Run – Operational). For further information, refer to
the operating manual of the relevant module or central processing unit.
Signal
Meaning
LED "P" (Power, green)
is lit
The router module is supplied with voltage.
LED "P" (Power, green)
is not lit
The router module is not supplied with voltage or
there is a problem with the electrical function of the
LED.
Remedy:
•
Check voltage supply at the "+24V" and "GND"
terminals of the router module.
•
Check power supply unit and connection be-
tween the power supply unit and the router
module.
If the "P" (Power) LED does not light up despite a
voltage supply being present, the entire router
module must be replaced.
Green
Orange
Meaning
Recommended action
Off
Off
No connection
Check cabling and topology
On
Off
Connection with 10 Mbit/s
On
On
Connection with 100 Mbit/s
Flickering
Off
Connection with 10 Mbit/s and data
transfer
Flickering
On
Connection with 100 Mbit/s and data
transfer
Summary of Contents for 705043
Page 2: ......
Page 3: ...70504300T94Z000K000 DE 00742713 Routermodul 1 Port 705043 Montageanleitung ...
Page 4: ...Weitere Informationen und Downloads qr 705043 de jumo info ...
Page 6: ...Inhalt ...
Page 14: ...2 Montage 12 Mindestabstände 201 50 5 50 5 30 70 130 ...
Page 18: ...2 Montage 16 2 3 Abmessungen 22 5 101 17 6 17 1 23 9 ...
Page 26: ...4 Anhang 24 ...
Page 27: ......
Page 29: ...70504300T94Z000K000 EN 00742713 Router module 1 port 705043 Installation Instructions ...
Page 30: ...Further information and downloads qr 705043 en jumo info ...
Page 32: ...Contents ...
Page 40: ...2 Mounting 12 Minimum distances 201 50 5 50 5 30 70 130 ...
Page 44: ...2 Mounting 16 2 3 Dimensions 22 5 101 17 6 17 1 23 9 ...
Page 52: ...4 Annex 24 ...
Page 53: ......
Page 55: ...70504300T94Z000K000 FR 00742713 Module routeur 1 port 705043 Notice de montage ...
Page 56: ...Informations complémentaires et téléchargements qr 705043 fr jumo info ...
Page 58: ...Sommaire ...
Page 66: ...2 Montage 12 Ecarts minimaux 201 50 5 50 5 30 70 130 ...
Page 70: ...2 Montage 16 2 3 Dimensions 22 5 101 17 6 17 1 23 9 ...
Page 78: ...4 Annexe 24 ...
Page 79: ......
Page 81: ......
Page 82: ......