Backwash Protective Filter

JUDO PROFI DN65 - DN100

Abbreviated Designation:

JPF DN65 - DN100

Design Types

Technical Data

The following applies for all the models of
the device:

Pressure loss when clean (after back-
washing): 0.2 bar at the water flow rate
(nominal flow rate) given in the table.

Maximum ambient temperature and wa-
ter temperature: 30°C (86°F).

The water to be filtered must conform
to the European Drinking Water Re-
gulations!

Threaded connection to DIN 2999.

Flange connection according to DIN 2633

Nominal Pressure JPF DN65: PN 16
Nominal Pressure JPF DN80, 100: PN 10
Operating
Pressure: 1,5 – 10 bar

The nominal pressure denotes the pressure
class, according to which the filter must fulfil
the requirements to DIN 19628 and DIN EN
13443-1. The maximum operating pressure
is lower, in order to ensure the optimum
function of the filter.

Installed dimensions

A = Installation length
B = unit width
C = Height above pipe centre
D = Height below pipe centre
F = Connection dimension waste water

Model

Pipe connec-

tion

Order No.

JPF DN65

DN65

8107014

JPF DN80

DN80

8010033

JPF DN100

DN100

8010034

Water flow rate

Model

Water flow rate for a pres-
sure loss of 0.2 bar with 

clean sieve insert

1)

JPF DN65

27 m³/h

JPF DN80

50 m³/h

JPF DN100

70 m³/h

1)

Data concerning the water flow rate are

valid for drinking water. The maximum water
flow rate for more polluted water is lower, de-
pending on the mesh size If so, a larger di-
mension has to be chosen.

Fig. 4: Installed dimensions e.g.: JPF DN80

Model

A

B

C

D

F

JPF DN65

240

185

332

159

¾"

JPF DN80

320

232

402

166

¾"

JPF DN100 320

232

412

176

¾"

All dimensions in [mm] (see Fig. 4)

Summary of Contents for PROFI JPF DN65

Page 1: ...and putting the unit into service These must always be issued to the owner user Prolongated guarantee period if a maintenance contract has been concluded Installation and Operating Instructions JUDO...

Page 2: ...n It can be installed into all drinking water pipes usual in the trade in each flow direc tion To ensure easy operation and maintenance the indicated minimum distances have to be observed The installa...

Page 3: ...t a water pressure of more than 10 bar a pressure reducer has to be mounted before the filter see Fig 3 At an operating pres sure higher than 10 bar malfunctions can occur For the backwashing water a...

Page 4: ...lve Doing this it is prevented that the sieve cloth is damaged by a too strong pressuring of the suction tube At the same time the rinse wa ter consumption is reduced With a flush valve opened to one...

Page 5: ...fulfil the requirements to DIN 19628 and DIN EN 13443 1 The maximum operating pressure is lower in order to ensure the optimum function of the filter Installed dimensions A Installation length B unit...

Page 6: ...placement interval for wearing parts Piece s DN65 Order No VE1 Piece Piece s DN80 DN100 Order No VE1 Piece 1 Lid of handwheel 1 1607152 7 1 1607152 7 2 Countersunk screw M5x12 1 1607454 1 1 1607454 1...

Page 7: ...thpiece Nozzle 2 1607104 10 4 1120135 11 16 Suction Pipe complete 1 2607135 122 1 2010029 320 17 Filter Screen MW 0 10 mm silver plated 1 2607136 180 1 2010028 350 18 O ring 1 1607110 2 2 1607110 2 19...

Page 8: ...5 6 92 0 Fax 49 0 71 95 6 92 188 e mail info judo eu www judo eu JUDO Wasseraufbereitung GmbH Niederlassung sterreich Zur Schleuse 5 A 2000 Stockerau Tel 43 0 22 66 6 40 78 Fax 43 0 22 66 6 40 79 e ma...

Reviews: