JUDO PROFI
5
Type
Type
Backwash Protective Filter
JUDO PROFI 2½" (DN65) - 4" (DN100)
Abbreviated Designation:
JPF 2½" (DN65) - 4" (DN100)
Design Types
Technical Data
The following applies for all the models of
the device:
–
–
Maximum ambient temperature and
water temperature: 30 °C (86 °F).
–
The water to be filtered must possess
quality of drinking water!
–
Threaded connection to DIN 2999.
–
Flange connection according to DIN 2633.
Installed dimensions
A = Installation length
B = unit width
C = Height above pipe centre
D = Height below pipe centre
F = Connection dimension waste water
Model
Pipe
connection
Order
No.
JPF 2½" (DN65)
2½"
8010138
JPF 3" (DN80)
3"
8010117
JPF 4" (DN100)
4"
8010139
Nominal Pressure
Model
Operating
Pressure
Nominal
Pressure
JPF 2½"
(DN65)
22 - 150 psi
(150 - 1000 kPa)
PN 16
JPF 3" (DN80),
4" (DN100)
22 - 150 psi
(150 - 1000 kPa)
PN 10
Water flow rate
Model
Water flow rate for a pres-
sure loss of 3 psi (20 kPa)
with clean sieve insert
1)
JPF 2½" (DN65)
119 gpm (27.0 m³/h)
JPF 3" (DN80)
220 gpm (50.0 m³/h)
JPF 4" (DN100)
308 gpm (70.0 m³/h)
1)
Data concerning the water flow rate are
Fig. 4: Installed dimensions e.g.: JPF 3" (DN80)
All dimensions in inch (mm) (see fig. 4)
Model
A
B
C
D
F
JPF 2½"
(DN65)
9.4
(240)
7.3
(185)
13.1
(332)
6.3
(159)
¾"
JPF 3"
(DN80)
12.5
(320)
9.1
(232)
15.8
(402)
6.5
(166)
¾"
JPF 4"
(DN100)
12.5
(320)
9.1
(232)
16.2
(412)
6.9
(176)
¾"