Judo PROFI JPF 2 1/2 DN65 Installation And Operating Instructions Manual Download Page 3

JUDO PROFI

3

Example for installation

If installing into a vertical line, the coarse
particles, deposited in the grit trap can’t be
flushed out as optimally as when installed
horizontally.

Tension-free installation has to be 
observed!

Example for installation

The installation of the Backwash Protective
Filter is effectuated up to a water pressure
of 150 psi (1000 kPa), and concerning 2½"
(DN  65) up to 232 psi (1600 kPa) behind the
water meter, and the backflow preventer
before a possibly mounted  pressure  reducer
(see fig. 3).

In the event of water pressure above
150 psi (1000 kPa)
, the pressure reduction
valve should be fitted in front of the Back-
wash Protective Filter (see fig. 3). If the
operating pressure is above 150 psi
(1000 kPa), this may result in defects during
operation.  

For the backwashing water a wastewater
connection (for example a floor drainage) in
accordance with DIN 1986 must be in place.
If a wastewater connection directly under
the filter is not possible, the rinse water can
be led by means of a line to be mounted on

Fig. 2: Application

> 100 mm
(4 Inch)

> 200 mm
(8 Inch)

> 40 mm
(1.5 Inch)

The installation of a pressure
reduction valve is recommended for
water pressures between 73 psi
(500 kPa) and 150 psi (1000 kPa)
.

Fig. 3: Pressure reducer upstream of the unit. 
Example: JPF 2½" (DN  65)

1

1 = Pressure reducer

Summary of Contents for PROFI JPF 2 1/2 DN65

Page 1: ...uctions and safety information before installing and putting the unit into service These Instructions must always be issued to the owner user Installation and Operating Instructions JUDO PROFI 2 DN65...

Page 2: ...t can be installed into all drinking water pipes usual in the trade in each flow direc tion To ensure easy operation and maintenance the indicated minimum distances have to be observed The installatio...

Page 3: ...bove 150 psi 1000 kPa the pressure reduction valve should be fitted in front of the Back wash Protective Filter see fig 3 If the operating pressure is above 150 psi 1000 kPa this may result in defects...

Page 4: ...Doing this it is prevented that the sieve cloth is damaged by a too strong pres suring of the suction tube At the same time the rinse water consumption is reduced With a flush valve opened to one hun...

Page 5: ...stallation length B unit width C Height above pipe centre D Height below pipe centre F Connection dimension waste water Model Pipe connection Order No JPF 2 DN65 2 8010138 JPF 3 DN80 3 8010117 JPF 4 D...

Page 6: ...m Designation Recommended average replacement interval for wearing parts Piece s 2 Order No Piece s 3 4 Order No 1 Lid of handwheel 1 1607152 1 1607152 2 Countersunk screw M5x12 1 1607454 1 1607454 3...

Page 7: ...120135 16 Suction Pipe complete 1 2607135 1 2010029 17 Filter Screen MW 0 10 mm 0 004 inch 1 2010380 1 2010376 18 O ring 1 1607110 2 1607110 19 Flush pipe JPF 3 1 2010039 19 Flush pipe JPF 4 1 2010044...

Page 8: ...g All rights are reserved for modifications as a result of technical progress or further developments Claims with regard to models or products are excluded 1701746 2009 08 Installed by JUDO Water Trea...

Reviews: