JUDO PROFI
3
Example for installation
Tension-free installation has to be
observed!
Example for installation
The installation of the Backwash Protective
Filter is effectuated up to a water pressure
of 150 psi (1000 kPa), and concerning 2½"
(DN 65) up to 232 psi (1600 kPa) behind the
water meter, and the backflow preventer
before a possibly mounted pressure reducer
(see fig. 3).
In the event of water pressure above
150 psi (1000 kPa), the pressure reduction
valve should be fitted in front of the Back-
wash Protective Filter (see fig. 3). If the
operating pressure is above 150 psi
(1000 kPa), this may result in defects during
operation.
Fig. 2: Application
> 100 mm
(4 Inch)
> 200 mm
(8 Inch)
> 40 mm
(1.5 Inch)
The installation of a pressure
reduction valve is recommended for
water pressures between 73 psi
(500 kPa) and 150 psi (1000 kPa).
Fig. 3: Pressure reducer upstream of the unit.
Example: JPF 2½" (DN 65)
1
1 = Pressure reducer