16
JUDO SPEEDY-LongLife
Faults
5.5
Stoppages
ATTENTION
(see chapter “Safety information and
dangers due to non-compliance”)
If a filter has to be removed from the flange
or unscrewed, the chapter “Intended use”
has imperatively to be observed!
–
Protect the flange surfaces from
damage! Damaged flange surfaces
cannot close tight any longer. As a
result, escaping water can damage the
building and installations.
–
Ensure that no dirt can get into the filter!
Upon re-commissioning this dirt can get
into contact with the drinking water and
be discharged into the drinking water.
The health of people consuming polluted
water is at risk.
–
Store the filter in frost-free conditions!
The water contained in the hollows of the
filter can freeze due to frost and thus the
filter can be mechanically damaged to a
degree that it will become loose at
operating pressure or that it can burst.
Leaking water can cause major material
damages to the building. In addition,
people near the filter can be injured by
blistering filter parts.
–
When re-commissioning the filter, same
course of action as applied to the new
filter.
6.
Faults
The opening of the units and the replacement of the water pressure charged parts may
only be effected by authorized personal in order the ensure the unit security and its
tightness.
Help with faults:
Fault
Cause
Remedy
Backwashing water
continues running!
Ceramic flushing valve not
fully closed.
Repeat the backwashing and
then turn the handwheel until
it locks into place!
Dirt in the ceramic flushing
valve.
Water flow rate falls!
Screen is blocked.
Carry out backwashing.
Leaks in the backwash
protective filter!
Inform the fitter or nearest
customer service centre.
(The filter cover must be
replaced immediately.)
Filter cover becomes turbid!
Filter has been exposed
to high temperatures or
solvents.
Hairline cracks on the filter
hood!