Attention
High relevant devices and so on won’t be supplied further on. If it’s still
necessary to supply them by the UPS, there has to be installed an external
bypass to feed the loads during a failure or servicing of the UPS further on.
Attention!
To protect the batteries the UPS-system switches-off at the moment the adjusted
battery cut-off voltage is reached.
Thereby the system is completely released. In case of mains returning the UPS-
system returns automatically into the normal operation state.
8.2
Reset of the alarm messages for 115V – Series
The alarm messages can’t be reset without switching off the UPS-system completely.
-
Switch off the complete load at the consumer distribution pole of the UPS.
-
Switch off the UPS-systems
POWERMASTER M
1000
through removing the input mains of the
device. Than you have to press down the push button
OFF
in front of the display for 2 seconds. After a
delay of 5 seconds the UPS-system will switch-off completely.
-
In case of no success please contact our service-department.
8.3
Acoustical alarms (deactivated) and troubleshooting for 115V - Series
The symbol
LINE
at the display is out and the symbols
INV
and
BACKUP
are lightening.
-
Failure of the mains (input mains of the UPS-system)
Measure:
Check the line from the terminals to the UPS-system and control the mains fuses of
the domestic installation
-
The symbol
INV
is out, the symbol
BYPASS
is on and the load indication is flashing:
The UPS is overloaded.
Measure:
Decrease the loading of the UPS-system by switching-off separate consumers.