joule ACAPELLA Operation And Maintenance Home Owner Manual Download Page 9

9

SOLAR SYSTEMS

manual and maintenance

What happens when you go on holidays

When you go on holidays or leave your house for more than a couple of days then you are 

not using any hot water out of your hot water cylinder. This means that the solar system 

heats your cylinder on day 1 and then on day 2 it has no water left to heat because the 

cylinder was heated the previous day and no water has been taken out of the hot water 

cylinder. To change any options including setting up the controller for going on holidays 

you must first enter the service menu of the controller. To do this, follow these steps.

   

1.  Tap button 1 until you reach the TIME screen

2.  Press and hold button 1 until the screen moves. 

 

(3 seconds to move).

3.  Tap button 1 until you reach the desired screen. 

The three buttons of the BS/4 controller

DeltaSol

®

 

BS/4

© RESOL_12089_deltasol_bs4_v2.monen.ind

d

23 |

CMN:
Collector minimum temp. 
Adjustment range: 
10 ... 90 °C [50 ... 190 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
10 °C [50 °F]

Collector minimum limitation option
OCN:  
Collector minimum limitation 
Adjustment range: OFF / ON 
Factory setting: OFF

If the collector minimum limitation option is activated, 
the pump (R1) is only switched on if the adjustable 
collector minimum temperature is exceeded. The minimum 
temperature prevents the pump from being switched on too 
often at low collector temperatures. A fixed hysteresis of 
5 K [10 °Ra] is set for this function
If the collector minimum limitation is active,   (flashing) is 
shown on the display.

Antifreeze option
OCF: 
Antifreeze function 
Adjustment range: OFF / ON 
Factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the store when the temperature falls below 
the adjusted antifreeze temperature. This will protect the 
fluid against freezing or coagulating. If the adjusted antifreeze 
temperature is exceeded by 1 K [2 °Ra], the loading circuit 
will be deactivated.
When the antifreeze function is activated,   is shown on 
the display. If the antifreeze function is active, 

 

and 

 

(flashing) are shown on the display.

Note: 
Since this function uses the limited heat quantity 
of the store, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.
The antifreeze function will be suppressed if the 
store temperature falls below 5 °C [40 °F] in 
order to protect the store from frost damage.

CFR:
Antifreeze temperature 
Adjustment range: 
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
4.0 °C [40.0 °F]

Store cooling function

When the store cooling function is activated, the controller 
aims to cool down the store during the night in order to 
prepare it for solar loading on the following day.
If the adjusted maximum store temperature S MX is 
exceeded and the collector temperature falls below the 
store temperature, the system will be reactivated in order 
to cool down the store. Cooling will continue until the store 
temperature has fallen below the adjusted maximum store 
temperature S MX again. A fixed hysteresis of 2 K [4 °Ra] 
is set for this function.
Reference threshold temperature differences for the store 
cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period of 
time, the additional holiday cooling option OHOL can be 
activated in order to extend the store cooling function. The 
adjustable temperature THOL then replaces the maximum 
store temperature S MX as a switch-off temperature for the 
store cooling function.
When the holiday cooling function is activated

,

 

 and   

(flashing) are shown on the display. 
While the holiday cooling function is active, 

,

 

 and   

(flashing) are shown on the display.

OSTC:
Store cooling option 

 

Adjustment range: OFF / ON 
Factory setting: OFF

THOL:
Holiday cooling temperature 
Adjustment range: 
20 ... 80 °C [70 ... 175 °F]
in steps of 1 K [1 °Ra]
Factory setting: 
40 °C [110 °F]

OHOL:
Holiday cooling option 
Adjustment range: OFF / ON 
Factory setting: OFF

Note: 
If OSTC or OCF is active, the collector minimum 
function will be overridden. In that case, the 
collector temperature may fall below CMN.

When the store cooling function is activated, the 

controller aims to cool down the store during the 

night in order to prepare it for solar loading on the 

following day.

If the adjusted maximum store temperature S MX 

is exceeded and the collector temperature falls 

below the store temperature, the system will be re-

activated in order to cool down the store. Cooling 

will continue until the store temperature has fallen 

below the adjusted maximum sture temperature S 

MX again. A fixed hysteresis of 2K [4 °Ra]  is set for 

this function.

Reference treshold temperature differences for the 

store cooling function are DT O and DT F.

If no DHW consumption is expected for a longer 

period of time, the additional holiday cooling option 

OHOL can be activated in order to extend the store 

cooling function. The adjustable temperature THOL 

then replaces the maximum store temperature 

MX as a switch-off temperature for the store cool-

ing function.

When the holiday cooling function is activated, 

DeltaSol

®

 

BS/4

© RESOL_12089_deltasol_bs4_v2.monen.ind

d

23 |

CMN:
Collector minimum temp. 
Adjustment range: 
10 ... 90 °C [50 ... 190 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
10 °C [50 °F]

Collector minimum limitation option
OCN:  
Collector minimum limitation 
Adjustment range: OFF / ON 
Factory setting: OFF

If the collector minimum limitation option is activated, 
the pump (R1) is only switched on if the adjustable 
collector minimum temperature is exceeded. The minimum 
temperature prevents the pump from being switched on too 
often at low collector temperatures. A fixed hysteresis of 
5 K [10 °Ra] is set for this function
If the collector minimum limitation is active,   (flashing) is 
shown on the display.

Antifreeze option
OCF: 
Antifreeze function 
Adjustment range: OFF / ON 
Factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the store when the temperature falls below 
the adjusted antifreeze temperature. This will protect the 
fluid against freezing or coagulating. If the adjusted antifreeze 
temperature is exceeded by 1 K [2 °Ra], the loading circuit 
will be deactivated.
When the antifreeze function is activated,   is shown on 
the display. If the antifreeze function is active, 

 

and 

 

(flashing) are shown on the display.

Note: 
Since this function uses the limited heat quantity 
of the store, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.
The antifreeze function will be suppressed if the 
store temperature falls below 5 °C [40 °F] in 
order to protect the store from frost damage.

CFR:
Antifreeze temperature 
Adjustment range: 
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
4.0 °C [40.0 °F]

Store cooling function

When the store cooling function is activated, the controller 
aims to cool down the store during the night in order to 
prepare it for solar loading on the following day.
If the adjusted maximum store temperature S MX is 
exceeded and the collector temperature falls below the 
store temperature, the system will be reactivated in order 
to cool down the store. Cooling will continue until the store 
temperature has fallen below the adjusted maximum store 
temperature S MX again. A fixed hysteresis of 2 K [4 °Ra] 
is set for this function.
Reference threshold temperature differences for the store 
cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period of 
time, the additional holiday cooling option OHOL can be 
activated in order to extend the store cooling function. The 
adjustable temperature THOL then replaces the maximum 
store temperature S MX as a switch-off temperature for the 
store cooling function.
When the holiday cooling function is activated

,

 

 and   

(flashing) are shown on the display. 
While the holiday cooling function is active, 

,

 

 and   

(flashing) are shown on the display.

OSTC:
Store cooling option 

 

Adjustment range: OFF / ON 
Factory setting: OFF

THOL:
Holiday cooling temperature 
Adjustment range: 
20 ... 80 °C [70 ... 175 °F]
in steps of 1 K [1 °Ra]
Factory setting: 
40 °C [110 °F]

OHOL:
Holiday cooling option 
Adjustment range: OFF / ON 
Factory setting: OFF

Note: 
If OSTC or OCF is active, the collector minimum 
function will be overridden. In that case, the 
collector temperature may fall below CMN.

 

and

DeltaSol

®

 

BS/4

© RESOL_12089_deltasol_bs4_v2.monen.ind

d

23 |

CMN:
Collector minimum temp. 
Adjustment range: 
10 ... 90 °C [50 ... 190 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
10 °C [50 °F]

Collector minimum limitation option
OCN:  
Collector minimum limitation 
Adjustment range: OFF / ON 
Factory setting: OFF

If the collector minimum limitation option is activated, 
the pump (R1) is only switched on if the adjustable 
collector minimum temperature is exceeded. The minimum 
temperature prevents the pump from being switched on too 
often at low collector temperatures. A fixed hysteresis of 
5 K [10 °Ra] is set for this function
If the collector minimum limitation is active,   (flashing) is 
shown on the display.

Antifreeze option
OCF: 
Antifreeze function 
Adjustment range: OFF / ON 
Factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the store when the temperature falls below 
the adjusted antifreeze temperature. This will protect the 
fluid against freezing or coagulating. If the adjusted antifreeze 
temperature is exceeded by 1 K [2 °Ra], the loading circuit 
will be deactivated.
When the antifreeze function is activated,   is shown on 
the display. If the antifreeze function is active, 

 

and 

 

(flashing) are shown on the display.

Note: 
Since this function uses the limited heat quantity 
of the store, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.
The antifreeze function will be suppressed if the 
store temperature falls below 5 °C [40 °F] in 
order to protect the store from frost damage.

CFR:
Antifreeze temperature 
Adjustment range: 
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
4.0 °C [40.0 °F]

Store cooling function

When the store cooling function is activated, the controller 
aims to cool down the store during the night in order to 
prepare it for solar loading on the following day.
If the adjusted maximum store temperature S MX is 
exceeded and the collector temperature falls below the 
store temperature, the system will be reactivated in order 
to cool down the store. Cooling will continue until the store 
temperature has fallen below the adjusted maximum store 
temperature S MX again. A fixed hysteresis of 2 K [4 °Ra] 
is set for this function.
Reference threshold temperature differences for the store 
cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period of 
time, the additional holiday cooling option OHOL can be 
activated in order to extend the store cooling function. The 
adjustable temperature THOL then replaces the maximum 
store temperature S MX as a switch-off temperature for the 
store cooling function.
When the holiday cooling function is activated

,

 

 and   

(flashing) are shown on the display. 
While the holiday cooling function is active, 

,

 

 and   

(flashing) are shown on the display.

OSTC:
Store cooling option 

 

Adjustment range: OFF / ON 
Factory setting: OFF

THOL:
Holiday cooling temperature 
Adjustment range: 
20 ... 80 °C [70 ... 175 °F]
in steps of 1 K [1 °Ra]
Factory setting: 
40 °C [110 °F]

OHOL:
Holiday cooling option 
Adjustment range: OFF / ON 
Factory setting: OFF

Note: 
If OSTC or OCF is active, the collector minimum 
function will be overridden. In that case, the 
collector temperature may fall below CMN.

 (flashing) are shown on the display.

While the holiday cooling function is active, 

DeltaSol

®

 

BS/4

© RESOL_12089_deltasol_bs4_v2.monen.ind

d

23 |

CMN:
Collector minimum temp. 
Adjustment range: 
10 ... 90 °C [50 ... 190 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
10 °C [50 °F]

Collector minimum limitation option
OCN:  
Collector minimum limitation 
Adjustment range: OFF / ON 
Factory setting: OFF

If the collector minimum limitation option is activated, 
the pump (R1) is only switched on if the adjustable 
collector minimum temperature is exceeded. The minimum 
temperature prevents the pump from being switched on too 
often at low collector temperatures. A fixed hysteresis of 
5 K [10 °Ra] is set for this function
If the collector minimum limitation is active,   (flashing) is 
shown on the display.

Antifreeze option
OCF: 
Antifreeze function 
Adjustment range: OFF / ON 
Factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the store when the temperature falls below 
the adjusted antifreeze temperature. This will protect the 
fluid against freezing or coagulating. If the adjusted antifreeze 
temperature is exceeded by 1 K [2 °Ra], the loading circuit 
will be deactivated.
When the antifreeze function is activated,   is shown on 
the display. If the antifreeze function is active, 

 

and 

 

(flashing) are shown on the display.

Note: 
Since this function uses the limited heat quantity 
of the store, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.
The antifreeze function will be suppressed if the 
store temperature falls below 5 °C [40 °F] in 
order to protect the store from frost damage.

CFR:
Antifreeze temperature 
Adjustment range: 
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
4.0 °C [40.0 °F]

Store cooling function

When the store cooling function is activated, the controller 
aims to cool down the store during the night in order to 
prepare it for solar loading on the following day.
If the adjusted maximum store temperature S MX is 
exceeded and the collector temperature falls below the 
store temperature, the system will be reactivated in order 
to cool down the store. Cooling will continue until the store 
temperature has fallen below the adjusted maximum store 
temperature S MX again. A fixed hysteresis of 2 K [4 °Ra] 
is set for this function.
Reference threshold temperature differences for the store 
cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period of 
time, the additional holiday cooling option OHOL can be 
activated in order to extend the store cooling function. The 
adjustable temperature THOL then replaces the maximum 
store temperature S MX as a switch-off temperature for the 
store cooling function.
When the holiday cooling function is activated

,

 

 and   

(flashing) are shown on the display. 
While the holiday cooling function is active, 

,

 

 and   

(flashing) are shown on the display.

OSTC:
Store cooling option 

 

Adjustment range: OFF / ON 
Factory setting: OFF

THOL:
Holiday cooling temperature 
Adjustment range: 
20 ... 80 °C [70 ... 175 °F]
in steps of 1 K [1 °Ra]
Factory setting: 
40 °C [110 °F]

OHOL:
Holiday cooling option 
Adjustment range: OFF / ON 
Factory setting: OFF

Note: 
If OSTC or OCF is active, the collector minimum 
function will be overridden. In that case, the 
collector temperature may fall below CMN.

DeltaSol

®

 

BS/4

© RESOL_12089_deltasol_bs4_v2.monen.ind

d

23 |

CMN:
Collector minimum temp. 
Adjustment range: 
10 ... 90 °C [50 ... 190 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
10 °C [50 °F]

Collector minimum limitation option
OCN:  
Collector minimum limitation 
Adjustment range: OFF / ON 
Factory setting: OFF

If the collector minimum limitation option is activated, 
the pump (R1) is only switched on if the adjustable 
collector minimum temperature is exceeded. The minimum 
temperature prevents the pump from being switched on too 
often at low collector temperatures. A fixed hysteresis of 
5 K [10 °Ra] is set for this function
If the collector minimum limitation is active,   (flashing) is 
shown on the display.

Antifreeze option
OCF: 
Antifreeze function 
Adjustment range: OFF / ON 
Factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the store when the temperature falls below 
the adjusted antifreeze temperature. This will protect the 
fluid against freezing or coagulating. If the adjusted antifreeze 
temperature is exceeded by 1 K [2 °Ra], the loading circuit 
will be deactivated.
When the antifreeze function is activated,   is shown on 
the display. If the antifreeze function is active, 

 

and 

 

(flashing) are shown on the display.

Note: 
Since this function uses the limited heat quantity 
of the store, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.
The antifreeze function will be suppressed if the 
store temperature falls below 5 °C [40 °F] in 
order to protect the store from frost damage.

CFR:
Antifreeze temperature 
Adjustment range: 
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
4.0 °C [40.0 °F]

Store cooling function

When the store cooling function is activated, the controller 
aims to cool down the store during the night in order to 
prepare it for solar loading on the following day.
If the adjusted maximum store temperature S MX is 
exceeded and the collector temperature falls below the 
store temperature, the system will be reactivated in order 
to cool down the store. Cooling will continue until the store 
temperature has fallen below the adjusted maximum store 
temperature S MX again. A fixed hysteresis of 2 K [4 °Ra] 
is set for this function.
Reference threshold temperature differences for the store 
cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period of 
time, the additional holiday cooling option OHOL can be 
activated in order to extend the store cooling function. The 
adjustable temperature THOL then replaces the maximum 
store temperature S MX as a switch-off temperature for the 
store cooling function.
When the holiday cooling function is activated

,

 

 and   

(flashing) are shown on the display. 
While the holiday cooling function is active, 

,

 

 and   

(flashing) are shown on the display.

OSTC:
Store cooling option 

 

Adjustment range: OFF / ON 
Factory setting: OFF

THOL:
Holiday cooling temperature 
Adjustment range: 
20 ... 80 °C [70 ... 175 °F]
in steps of 1 K [1 °Ra]
Factory setting: 
40 °C [110 °F]

OHOL:
Holiday cooling option 
Adjustment range: OFF / ON 
Factory setting: OFF

Note: 
If OSTC or OCF is active, the collector minimum 
function will be overridden. In that case, the 
collector temperature may fall below CMN.

 

and

DeltaSol

®

 

BS/4

© RESOL_12089_deltasol_bs4_v2.monen.ind

d

23 |

CMN:
Collector minimum temp. 
Adjustment range: 
10 ... 90 °C [50 ... 190 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
10 °C [50 °F]

Collector minimum limitation option
OCN:  
Collector minimum limitation 
Adjustment range: OFF / ON 
Factory setting: OFF

If the collector minimum limitation option is activated, 
the pump (R1) is only switched on if the adjustable 
collector minimum temperature is exceeded. The minimum 
temperature prevents the pump from being switched on too 
often at low collector temperatures. A fixed hysteresis of 
5 K [10 °Ra] is set for this function
If the collector minimum limitation is active,   (flashing) is 
shown on the display.

Antifreeze option
OCF: 
Antifreeze function 
Adjustment range: OFF / ON 
Factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the store when the temperature falls below 
the adjusted antifreeze temperature. This will protect the 
fluid against freezing or coagulating. If the adjusted antifreeze 
temperature is exceeded by 1 K [2 °Ra], the loading circuit 
will be deactivated.
When the antifreeze function is activated,   is shown on 
the display. If the antifreeze function is active, 

 

and 

 

(flashing) are shown on the display.

Note: 
Since this function uses the limited heat quantity 
of the store, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.
The antifreeze function will be suppressed if the 
store temperature falls below 5 °C [40 °F] in 
order to protect the store from frost damage.

CFR:
Antifreeze temperature 
Adjustment range: 
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps o

f 0.5 K [1 °Ra]

Factory setting: 
4.0 °C [40.0 °F]

Store cooling function

When the store cooling function is activated, the controller 
aims to cool down the store during the night in order to 
prepare it for solar loading on the following day.
If the adjusted maximum store temperature S MX is 
exceeded and the collector temperature falls below the 
store temperature, the system will be reactivated in order 
to cool down the store. Cooling will continue until the store 
temperature has fallen below the adjusted maximum store 
temperature S MX again. A fixed hysteresis of 2 K [4 °Ra] 
is set for this function.
Reference threshold temperature differences for the store 
cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period of 
time, the additional holiday cooling option OHOL can be 
activated in order to extend the store cooling function. The 
adjustable temperature THOL then replaces the maximum 
store temperature S MX as a switch-off temperature for the 
store cooling function.
When the holiday cooling function is activated

,

 

 and   

(flashing) are shown on the display. 
While the holiday cooling function is active, 

,

 

 and   

(flashing) are shown on the display.

OSTC:
Store cooling option 

 

Adjustment range: OFF / ON 
Factory setting: OFF

THOL:
Holiday cooling temperature 
Adjustment range: 
20 ... 80 °C [70 ... 175 °F]
in steps of 1 K [1 °Ra]
Factory setting: 
40 °C [110 °F]

OHOL:
Holiday cooling option 
Adjustment range: OFF / ON 
Factory setting: OFF

Note: 
If OSTC or OCF is active, the collector minimum 
function will be overridden. In that case, the 
collector temperature may fall below CMN.

 (flashing) are shown on the display.

Summary of Contents for ACAPELLA

Page 1: ...1 SOLAR SYSTEMS manual and maintenance JOULE SOLAR SYSTEMS operation and maintenance home owner manual ...

Page 2: ......

Page 3: ...al and maintenance Table of Contents 04 Joule Solar Hot Water Systems 05 Solar Controller Wiring Diagram 06 Panel Types 07 How Your Solar System Works 10 Troubleshooting 13 What Maintenance Is Required 14 Maintenance Sheet ...

Page 4: ...tes in conjunction with our commissioning certificate and leaflets for the solar pump station and controller that we provided on installation controller supplied will vary dependent on solar collectors installed and installation type These documents should be retained for future reference a copy of our commissioning certificate lodged inside the solar pump station housing providing all the details...

Page 5: ... switch on temperature difference DT O the solar pump will be operated by relay 1 and the store will be loaded until the switch off temperature difference DT F or the maximum store temperature S MX is reached R1 Arr 1 S3 Display Channels Channel Description Terminal Page INIT x ODB initialisation active 18 FLL x ODB filling time active 18 STAB x ODB stabilisation in progress 18 COL x Temperature c...

Page 6: ...ed with your system The solar system installed in your home features either the Joule Navitas on roof or in roof solar panels Joule VisSolis in roof solar panels or Joule Acapella high efficiency vacuum tube solar panels Joule Navitas On roof Joule Acapella Joule Navitas In roof Joule VisSolis In roof ...

Page 7: ... solar heats the hot water cylinder Phase 2 When hot water is used hot water level rises and is replaced by cold water The level of hot water rises in the cylinder thus reducing the amount of hot water in the cylinder The cold water enters the cylinder from the base replenishing the used hot water Phase 3 When there is a solar gain it heats cold water at the bottom of the cylinder thus reducing th...

Page 8: ...r over heats and risks very hot water coming out of your taps Your solar controller is programmed to shut down the solar system when you re hot water cylinder reaches a tem perature of 60 C at the bottom of the cylinder This temperature is chosen because it is a safe temperature to store hot water both by not being too hot and protecting people from scalding and also not too cold to reduce the ris...

Page 9: ...ng OFF and tion If the collector minimum limitation option is activated the pump R1 is only switched on if the adjustable When the store cooling function is activated the controller aims to cool down the store during the night in order to prepare it for solar loading on the following day If the adjusted maximum store temperature S MX is exceeded and the collector temperature falls below the store ...

Page 10: ...ohmmeter In the following table the resistance values with the corresponding temperatures are shown Operating control lamp off Check the power supply Is it disconnected no The fuse of the controller could be blown It can be replaced after the front cover has been removed spare fuse is enclosed in the accessory bag yes Check the supply line and reconnect it C F Ω C F Ω 10 14 961 55 131 1213 5 23 98...

Page 11: ... Decalcify it no Heat exchanger blocked yes no Clean it Heat exchanger too small yes Replace with correctly sized one no Plausibility control of the option tube collec tor special function Change Ton and Toff correspondingly Switch on temperature difference Ton to large no yes Non ideal position of the coll ector sensor e g flatscrew sensor instead of sensor in sensor wells no Pump is overheated b...

Page 12: ...d yes no Does the pump start up in manual operation yes There is no current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a value which makes more sense no Is the pump current enabled by the control ler yes Is the pump stuck Turn the pump shaft using a screwdriver now pas sable Pump is defective re place it Are the contr...

Page 13: ...should not be switched off for any prolonged period of time Notify plumber if system pressure is 0 The controller should be on at all times and not turned off except for maintainence Warranty Definition All Joule products come with a manufacturers guarantee Your solar system comes with a 10 year guarantee on the collector and 2 year guarantee on the solar com ponents This guarantee covers all manu...

Page 14: ...14 Date of Service Service Engineer Name Engineer Number Issues Noted Maintenance Sheet ...

Page 15: ...15 SOLAR SYSTEMS manual and maintenance ...

Page 16: ...ower Road Plantation Bus Pk Bromborough Wirral CH62 3RN 44 0 1513 551 094 44 0 1513 568 336 info jouleuk co uk www jouleuk co uk 23 200 Kraśnik ul Towarowa 34 48 0 128811171 48 0 814709046 biuro joule pl pl www joule pl pl JOULE IE JOULE UK JOULE PL mail tel fax eml web mail tel fax eml web mail tel fax eml web ...