background image

30

3.0 Safety precautions

3.1 Fire preventive measures

Any use of the fireplace may represent some danger.

  

Therefore, 

respect the following instructions:

 

•  Ensure that furniture and other flammable materials do not 

get too close to the fireplace. 

•  Let the fire die. Never put it out with water as this may 

damage the product.

•  The fireplace gets warm when used and may cause burns if 

touched.

•  Only remove the ashes when the fireplace is cold.
• 

Ash must be properly disposed of outdoors, or emptied where 
it does not entail a fire hazard.

3.2 Air supply

Warning!

 Please ensure that there is adequate air supply from the 

outdoors to the room in which the fireplace is to be installed.

An inadequate air supply could cause smoke gas to escape into 
the room. This is very dangerous! Symptoms of this include smoky 
smell, drowsiness, nausea and feeling ill.

Ensure that air vents in the room where the fireplace is located 
are not blocked.

Avoid using mechanical fan vents in a room with a fireplace.  
This may cause negative pressure and draw poisonous gasses 
into the room.

4.0 Installation

4.1 Floor

Foundations

Ensure that the floor is strong enough for the fireplace. See 

«2.0 Technical data»

 for weights. Floor,  which is not fixed  to 

the foundation (so-called floating floor) is reccomended to be 
removed before installation.

Wooden floor protection 

Jøtul I 

80

 has a heat shield beneath the bottom to protect the 

floor from radiant heat.
Therefore the product can be mounted directly on a combustible 
floor, if the floor is covered with a plate made of metal or or 
other non-combustible material.  The recommended minimum 
thickness is 0,9 mm. The whole floor inside the surround must 
be covered.  

Any flooring made of combustible material, such as linoleum, 
carpets, etc. must be removed from under the floor plate.

Requirement for protecting combustible 
flooring in front of fireplace (fig. 1)

The front plate must be in accordance with national laws and 
regulations

. Contact your local building authorities regarding 

restrictions and installation requirements

.

4.2 Wall

Distance to combustible walls protected by 
insulation material insulation/firewall - see fig. 1

Requirements for insulation

50 mm rock wool 120 kg/m

3

 foliated on one side with 

aluminium.

Distance from the insert heat shield to the 
insulation on the wall

Minimum 

15 mm

.

Distance from the insert heat shield to the firewall:

The distance must be 

minimum 15 mm

.

 

Firewall requirement

The firewall must be at least 

100 mm

 thick and be made of 

brick, concrete-stone or light concrete. Other materials and 
constructions with satisfactory documentation may also be used.
Contact your local building authorities regarding restrictions and 
installation requirements.

Requirements for the insert surround

The insert surround must be made in an incombustible material.

Note that the entire back panel within the surround must be 
covered by insulation.
If the stove cowling is bricked up to the ceiling and the ceiling is 
made of combustible material, on top of the warming chamber 
and the cowling vents an extra ceiling panel must be installed 
to avoid heating the ceiling.

ENGLISH

Summary of Contents for I 80 Maxi Classic

Page 1: ...nstalaci n 47 IT Manuale di installazione ed uso 56 DE Montage und Bedienungsanleitung 65 NL Installatie en montagehandleiding 74 Figures Pictures 83 Monterings og bruksanvisningen m oppbevares under...

Page 2: ...output 6 0 kW 9 0 kW Smoke gas mass flow 5 4 g s 8 1 g s Rec chimney draught 12 Pa 12 Pa Effiency 83 4 9 kW 80 9 9 kW CO emission 13 O2 0 08 0 06 Flue gas temperature 240 0 C 314 0 C Operating mode I...

Page 3: ...ctly on a combustible floor if the floor is covered with a plate made of metal or or other non combustible material The recommended minimum thickness is 0 9 mm The whole floor inside the surround must...

Page 4: ...have a certain flexibility in order to prevent movement in the installation leading to cracks N B A correct and sealed connection is very important for the proper functioning of the product Warning We...

Page 5: ...e adapted to the insert 3 The flue pipe bend should be assembled directly onto the insert and should be able to rotate 360o Pipe 150 mm is assembled on the inside of the smoke outlet and the 175 mm is...

Page 6: ...are the correct size The size of the logs should be Kindling Length Approx 35 40 cm Diameter 3 5 cm Amount per fire 8 10 pieces Firewood split logs Mini Maxi Recommended length 35 cm 35 kg Diameter A...

Page 7: ...mwaterandaddsomeashfrom theburnchamber Rubit over the glass and then clean the glass with clean water Dry well If it is necessary to clean the glass more thoroughly we recommend using a glass cleaner...

Page 8: ...ection 2 Pull the air chamber forward while at the same time lifting it up at the edge Edge it down and remove it through the opening in the door Be aware that the part is heavy 3 Before replacing the...

Page 9: ...ooting Poor draught Check the length of the chimney and that it complies with national laws and regulations Make sure that the minimum cross section on the chimney is large enough See also 2 0 Technic...

Page 10: ...high 340995 2 units of 103x573 1 Remove the front see relevant section on 7 0 Service 2 Attach the panels A with countersunk head screws through the 2 slits at the sides of the combustion chamber Make...

Page 11: ...83...

Page 12: ...84 B C A D A B C A G F E D B A C H A B Fig 5 750 cm 2 500 cm 2 600 cm 2 C 350 cm 2 Fig 4 Fig 2 Fig 6 Fig 3 A D B C Fig 7 A Fig 8 E C D B A Fig 9 Mini Maxi...

Page 13: ...85 A B B A A B B A Fig 11 g 10 E D C B A Fig 13 C E A B D ig 12 C B A B C D A Fig 15 ig 14...

Page 14: ...86...

Page 15: ...87...

Page 16: ...n bedriftens historie startet i 1853 Qualit t J tul AS hat ein Qualit tssicherungssystem das sich bei Entwicklung Produktion undVerkauf von fen und Kaminen nach NS EN ISO 9001 richtet Diese Qualit tsp...

Reviews: