Jøtul GI 550 DV Installation And Operation Instructions Manual Download Page 15

15

138727_Rev_F   8/9/11

Gas Pressure

Proper gas pressure provides a consistent flow of 

gas to the appliance and is instrumental in checking 

for gas leaks. The gas control valve on the fireplace is 

equipped with pressure test points 

for gauge connections.  The gauge 

connections are located on the 

front of the valve next to the 

On/Off/Pilot knob.  Gauge con-

nections are identified by: 
•  IN / E  for inlet or supply 

pressure (the amount of gas com-

ing to the valve.)

•  OUT / A  for manifold pres-

sure (the amount of gas that is 

coming out of the  valve to the 

burner.)

Soap Solution Leak Test

•  Mix a 50-50 solution of water and dish soap.
•  Light appliance- see lighting instructions on page 

23 of this manual or on the fireplace’s rating plate.

•  Brush or spray all joints and connections with the 

soapy water solution.

•  If bubbles appear at any connection or seam or a 

gas odor is detected, immediately turn gas control 

knob to the OFF position.

Tighten or reconnect the leaking joint and retest 

for any gas leaks.

Figure 11.  Gas supply line fittings.

The appliance must be isolated from the gas sup-

ply line by closing its individual manual gas shut-off 

valve (gas cock) during any pressure testing of the gas 

supply piping system that is equal to or exceeds pres-

sures of 1/2 psig (3.5 kPa).

Inlet Pressure

 

                          MIN  

 

MAX 

    Natural Gas:   5.0 WC  (1.24 kPa)  

      7.0 WC  

(1.74 kPa)

    Propane:       12.0 WC  (2.98 kPa)        16.0 WC  (3.98 

kPa)

Manifold Pressure

 

                          MIN  

 

MAX 

    Natural Gas:   1.2 WC  (0.29 kPa)  

     3.8 WC   

(.95 kPa)

    Propane:          2.9 WC  (0.72 kPa)      11.0 WC  (2.74 kPa)

ALWAYS TEST PRESSURE WITH VALVE CONTROL KNOB 

SET ON HIGH.

  Symptoms of incorrect gas pressure 

include:
Insufficient gas pressure:  
•  Small pilot flame which can result in insufficient 

millivolts.  

•  Little variation in flame picture between HI and LO 

settings.

•  Insufficient gas to support more than one appli-

ance causing nuisance outages or gas surges.

Excessive gas pressure:
•  Permanent damage to valve causing complete ap-

pliance shut down.

•  Too large a pilot flame resulting in overheating of 

the power generator and consequent shut down.

•  Sooting due to impingement and/or incorrect fuel 

to air mix.

High Altitude Adjustment

Installations located at altitudes from 2000 - 4250 ft. 

(610 M - 1370 M)  require adjustment for differences 

in pressure.  Use Jøtul High Altitude Adjustment Kit 

156451 for propane or 156452 for natural gas adjust-

ment.

 

 









Figure 12. Pressure test points located on the front of 

the valve.

E

A

Summary of Contents for GI 550 DV

Page 1: ...ce QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer l appareil Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trou vant dans le b timent o vous trouvez Appelez imm...

Page 2: ...mpletion of the installation Suggested Tools for Installation and Service External regulator for Propane only Piping which complies with local code Manual shut off valve T Handle required in Massachus...

Page 3: ...engage it from the Glass Frame Latch Release Tool Left Latch Release Unpacking the Fireplace A Miscellaneous Hardware Kit is packed within the right side compartment of the firebox It contains Install...

Page 4: ...onversion Kit LP to NG 156447 High Altitude Adjustment Kit LP 156451 High Altitude Adjustment Kit NG 156452 Wall Thermostat 750003 Remote Control 129706 Cast Iron Surrounds 40 Wide x 30 High 32 w plin...

Page 5: ...vir de cet appareil s il a ete plonge dans l eau completement ou en partie Appeler un technicien qualifie pour inspecter l appareil et rem placer toute partie du syste me de controle et toute commande...

Page 6: ...for use with 3 Type B vent pipe components or a Listed Flexible gas liner See the Appendix on page 28 for a complete list of vent pipe manufacturers whose prod ucts are approved for use with this appl...

Page 7: ...he height appropriate to your installation require ments Figure 2 Firebox dimensions Figure 3 Minimum fireplace dimensions GI 550 DV A Opening Width 34 1 2 876 mm with leveling brackets 36 914 mm B Op...

Page 8: ...least 16 forward of the firebox glass panel with the following exception Cast Iron surrounds without Plinth the hearth pro tection must extend 36 x 18 See fig 4 Table 1 Fireplace Facing Options J tul...

Page 9: ...nry or zero clearance flue CANNOT be used to vent any other appliance Flexible liner components may not be exposed in any living space Installation of any components not manufactured or approved by J...

Page 10: ...the unit and will carry the exhaust gases to the outside of the house This exhaust liner must be directly connected to the unit and run the full length of the chimney See fig 6 The other 3 liner will...

Page 11: ...uld be cut or pried off 2 Remove the damper assembly This includes the damper blade handle and any linkage Two 3 liners must be able to pass through the damper area 3 Remove any fire screen or door as...

Page 12: ...ebox where it will be readily seen should the insert be removed Cutting of any sheet metal parts on a solid fuel fireplace is prohibited If the factory built fireplace has no gas access hole s provide...

Page 13: ...st not block or seal any venti lation openings on the prefabricated fireplace Vent Connection The Vent Collar Plate located on top of the cabinet is removable to ease connection of the vent liners in...

Page 14: ...Turn on gas supply and test for gas leaks using a 50 50 soapy water solution or a gas detector Never use an open flame to check for leaks A T HANDLE GAS SHUT OFF VALVE IS RE QUIRED IN MASSACHUSETTS I...

Page 15: ...ing its individual manual gas shut off valve gas cock during any pressure testing of the gas supply piping system that is equal to or exceeds pres sures of 1 2 psig 3 5 kPa Inlet Pressure MIN MAX Natu...

Page 16: ...ng a 4 mm hex key unscrew the pilot orifice counterclockwise Replace with the orifice from the kit Tighten new orifice securely into the base of the pilot assembly Replace Pilot Hood by pushing it int...

Page 17: ...rubber gasket Thoroughly tighten new regulator to valve body 8 Apply the Conversion Labels Apply LABEL A to the cabinet floor so that it may be seen by anyone servicing the fireplace Apply LABEL B to...

Page 18: ...lugged directly into a properly grounded three prong receptacle DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THE PLUG ALWAYS DISCONNECT THE POWER SUPPLY BEFORE SERVICING THE BLOWER Wall Thermostat In...

Page 19: ...ent the rear panel to align with the brick courses on the Side Panels as shown in fig 20 Place the panel against the back wall of the firebox resting on the log shelf as in fig 21 4 Install the Side P...

Page 20: ...skirt against the back of the firebox as shown in fig 24 2 Set the Lower Left and Right logs in place on the burner plate pegs as shown in fig 25 3 Set the three upper logs on the appropriate pegs as...

Page 21: ...s described in the lighting instructions located on the fireplace s rating plate and back cover of this manual 2 PILOT FLAME The pilot flame should be steady not lifting or floating The flame should b...

Page 22: ...anger brackets that engage with the hanger tabs on the firebox Hanger Brackets Surround Assembly Each of the surround assemblies and front facings is completely assembled at the factory No further as...

Page 23: ...ways follow the Lighting Instructions located on the inside Back Cover of this manual and also on the Rating Plate located in the burner controls compartment 2 For the first several hours of operation...

Page 24: ...tube Glass Care Clean the glass as necessary Wipe the surface with a clean dampened soft cloth Follow with a dry soft towel Take care not to scratch the glass surface Scan 70i Sliding Glass Panel Car...

Page 25: ...es using a blanket or towel 3 The glass panel is held in place by four retainer clips Use a screwdriver to carefully pry these up off the edge of the glass retaining walls See fig 35 4 Remove the old...

Page 26: ...26 138727_Rev_F 8 9 11 Universal GI 550 Illustrated Part Breakdown DV Figure 37 Part Identification...

Page 27: ...0 Cabinet Top 221737 41 Gasket Vent Adaptor 222281 42 Vent Connector Assembly 222259 43 Gasket 3 Adaptor 129677 44 Heat Shield Top Firebox 222415 45 Relief Door 222432 46 Burner Top Plate 221749 47 Bu...

Page 28: ...ch cap Place the switch in the OFF position 5 Run the receiver wires out the back of the switch box and connect the leads to the TH and TH TP terminals on the valve DO NOT DISCONNECT ANY WIRES FROM TH...

Page 29: ...associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enameled s...

Page 30: ...erformed ____________________________ _________________________________________ _________________________________________ Your fireplace insert has a unique serial number stamped on the rating plate w...

Page 31: ...trol which has been under water 3 Access the lower controls 4 Depress gas control knob slightly and turn clockwise to OFF Do not force 8 Push in control knob all the way and hold in Im mediately light...

Page 32: ...nning the installation it is important that the these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in specif...

Reviews: