background image

15

139467_03   GF 370 DV II     June 2015   

Figure 19. Gas supply valve types and fittings.

 

 









Soap Solution Leak Test

•  Mix a 50-50 solution of water and dish soap.
•  Light appliance - see lighting instructions on the 

back cover of this manual or on the rating plate.

•  Brush or spray all joints and connections with the 

soapy water solution.

•  If bubbles appear at any connection or seam or a 

gas odor is detected, immediately turn gas control 

knob to the OFF position.  

Tighten or reconnect the leaking joint and retest 

for any gas leaks.

The line must be disconnected from the gas 

supply line by closing the main supply manual gas 

shut-off valve (gas cock) during any pressure testing 

of the gas supply piping system that is equal to or 

exceeds pressures of 1/2 psig (3.5 kPa).

4. Testing Gas Pressure

Proper gas pressure provides a consistent flow of gas 

to the appliance and is instrumental in checking for 

gas leaks. There are two pressure test points on the 

front of the stove control valve where test gauge con-

nections are made. See Fig. 20.  Gauge connections 

are identified by:
•  E  for inlet or supply pressure ( the amount of gas 

coming to the valve.)

•  A  for manifold pressure (the amount of gas that is 

coming out of the valve to the burner.)

WARNING

DO NOT ALLOW THE INLET GAS PRESSURE TO 

EXCEED 

14.0

” WC (OR 1/2 PSIG) AS SERIOUS 

DAMAGE TO THE VALVE MAY RESULT.

NEVER USE AN OPEN FLAME TO CHECK FOR GAS 

LEAKS.
ALWAYS REFER TO THE LIGHTING INSTRUCTIONS 

ON THE INSIDE BACK COVER OF THIS MANUAL 

WHEN LIGHTING THE STOVE.

Figure 20.  Pressure test points located on the front 

of the valve.

Manifold

Inlet 

Pilot Adjustment

E

A

Inlet Pressure

 

                          MIN    MAX 

    Natural Gas:   5.0 WC  (1.24 kPa)        7.0 WC  (1.74 kPa)

    Propane:       12.0 WC  (2.99 kPa)      14.0 WC (3.48 kPa)

Manifold Pressure

 

                          MIN    MAX 

    Natural Gas:   1.6 WC  (0.398 kPa)       3.5 WC  (.87 kPa)

    Propane:         6.4 WC  (1.59 kPa)     10.0 WC  (2.48 kPa)

ALWAYS TEST PRESSURES WITH VALVE REGULATOR 

CONTROL AT THE HIGHEST SETTING. 

Symptoms of incorrect gas pressure include:
Insufficient gas pressure:  

•  Small pilot flame which can result in insufficient 

millivolts.  

•  Little variation in flame picture between HI and LO 

regulator settings.

•  Insufficient gas to support more than one appli-

ance causing nuisance outages or gas surges.

Excessive gas pressure:

•  Permanent damage to valve causing complete ap-

pliance shut down.

•  Too large a pilot flame resulting in overheating of 

the power generator and consequent shut down.

•  Sooting due to impingement and/or incorrect fuel 

to air mix.

Summary of Contents for GF 370 DV

Page 1: ...tion and service must be performed by a qualified installer service agency or the gas supplier In the Commonwealth of Massachusetts a carbon monoxide CO detector shall be installed in the same room as the appliance WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Thisappliancemaybeinstall...

Page 2: ...duct approved air intake must be used Installation shall be in strict compliance with the manufacturer s instructions A copy of the installation instructions must remain with the appliance or equipment at the completion of the installation Suggested Tools for Installation and Service External regulator for Propane only Piping which complies with local code Manual shut off valve T Handle required i...

Page 3: ...ing the installation inspect the stove for shipping damage and immediately report any evidence of damage to your dealer 2 Confirm stove contents The Jøtul GF 370 DV II includes the following loose items shipped in the Miscellaneous Hardware bag 4 mm hex key used to remove the front glass panel for access to the firebox Remote Control Transmitter Remote Control Wall Mount Bracket AA Batteries 4 Pro...

Page 4: ...ries 3 AAA 1 5v RemoteControlReceiverbatteries 4 AA FanControlModule 120V 60Hz Jøtul GF 370 DV II Direct Vent Gas Stove Manufactured and Distributed by Jøtul North America Gorham Maine USA Jøtul AS Fredrikstad Norway Test Standards This appliance complies with National Safety standards and is tested and listed by Intertek Testing Services of Middleton Wisconsin In addition the Jøtul GF 370 DV II h...

Page 5: ...g air passageways of the appliance be kept clean 3 This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type s of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used 4 The installation must con...

Page 6: ...s Maintain proper clearance to combustible mantels and fireplace trim Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ignition Young children should be supervised while they are in the same room as the appliance Toddlers young children and others may be susceptible to accidental contact burns A physical barrier such ...

Page 7: ...aterial is anything that can burn i e sheet rock wall paper wood fabrics etc These surfaces are not limited to those that are visible and also include materials that may be located behind non combustible materials If you are not sure of the combustible nature of a material consult your local fire officials Fire resistant materials are considered to be combustible They may be difficult to ignite bu...

Page 8: ...nation Whenever possible use 45 elbows instead of 90 elbows as they offer less restriction to the flow of flue gases and intake air A listed firestop is required at any floor penetration The opening should be framed in according to the manufacturer s instructions Always maintain a minimum 1 clearance from all sides of the vertical vent system to any combustible material Minimum vertical terminatio...

Page 9: ...onry chimney a fireclay liner or listed steel liner must be contained within the entire length of the chimney 3 Overall venting should not exceed 35 ft 10 67 m 4 The liner must have an inside dimension of 6 round or greater 5 Prefabricated chimneys must be UL 103 or ULC S 629 listed and have a minimum INSIDE diam eter of 6 inches 150 mm Prefabricated chimneys must be listed for the specific manufa...

Page 10: ...nation cap with any type of insulation Wall Cut out A minimum 10 X 10 square hole is adequate for proper pipe clearance through a wall provided the vent is positioned to maintain 2 minimum clearance at the top A 1 minimum clearance must be maintained to combustible material around the other sides See fig 11 Any horizontal run of vent must have a 1 4 rise for every foot of run toward the terminatio...

Page 11: ...ft 91 cm within a height 15 ft above the meter regulator assembly I Clearance to service regulator vent outlet 3 ft 91 cm J Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 12 in 30 cm 9 in 23 cm K Clearance to a mechanical air supply inlet 6 ft 1 83 m 3 ft 91 cm above if within 10 ft 3 m horizontally L Clearance above paved sidewalk or pav...

Page 12: ...II features adjustment controls for both intake air and exhaust to accommodate a variety of conditions that result from variables inherent in the vent configuration and environment Both controls can be accessed from outside the firebox to allow the burner to be dialed in under operation See figures 14 and 16 Use the Vent Termination Diagram fig 17 to determine which zone your vent termination fall...

Page 13: ...ximum of two 90 or four 45 elbows may be used Whenever possible use 45 elbows instead of 90 elbows as these offer less restriction to the flow of flue gases and intake air Use of elbows may adversely affect IPI functionality In such cases CPI mode should be used Reduce the overall horizontal run by 5 feet for each additional 45 and 90 elbow When two or more elbows are used in a horizontal run a le...

Page 14: ...ne within 6 feet of the appliance This allows for the disconnection of the stove for servicing and maintenance See Fig 19 A T HANDLE GAS SHUT OFF VALVE IS RE QUIRED IN MASSACHUSETTS IN COMPLIANCE WITH CODE 248CMR THIS PRODUCT MUST BE INSTALLED BY A LICENSED MASTER OR JOURNEYMAN PLUMBER OR GAS FITTER WHEN INSTALLED IN THE COMMONWEALTH OF MASSACHUSETTS The stove and gas control valve must be discon ...

Page 15: ...g to the valve A for manifold pressure the amount of gas that is coming out of the valve to the burner WARNING DO NOT ALLOW THE INLET GAS PRESSURE TO EXCEED 14 0 WC OR 1 2 PSIG AS SERIOUS DAMAGE TO THE VALVE MAY RESULT NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS ALWAYS REFER TO THE LIGHTING INSTRUCTIONS ON THE INSIDE BACK COVER OF THIS MANUAL WHEN LIGHTING THE STOVE Figure 20 Pressure test poin...

Page 16: ...lessure personnelle de vie L agence qualifiée do service est esponsable de l installation propre de cet équipe metn L installation n est pas propre et complète jusqu à l operation de l appareil converi est chéque suivant les critères établis dans les instruction de propriétaire provi sion nées avel l équipement Fuel Conversion Procedure 1 Turn off gas supply to the stove and disconnect from electr...

Page 17: ...oned and tighten screws securely Connect the wire lead 12 Applytheidentificationlabelstothestovesothattheycan beseenbyanypersonthatmaybeservicingthestove Label A Applytofrontlipofthevalvecompartment Label B Apply to the Rating Plate Small valve sticker Apply to valve 13 Install the accessory panels and burner media as appropriate See pages 19 21 14 Apply anti seize lubricant to the socket head gla...

Page 18: ...r use at an altitude of___________ Orifice Size __________ Manifold Press _______ Input Btu Hr _________ Fuel Type ___________ Date ___ ___ ___ Converted by _____________ Cet appreeil a été converti au _____ Injecteur_____ Pression à la tubulure d alimentation ___________ Déoit calorifique ___________ 7 Firebox Panel Installation Skamol Panels and optional Reflective Glass Kit 156817 Skamol Panels...

Page 19: ...lot must remain clear for proper pilot ignition See figs 29 and 65 for examples StarFire Glass Embers Do not use more than the four pounds in two 2 lb bags of glass media provided For best results evenly spread the contents of the bag over the entire burner plate and rear skirt mounding a crown toward the center DO NOT COVER THE AREA IMMEDIATELY IN FRONT OF THE PILOT ASSEMBLY The carry overportsdi...

Page 20: ...Log up against the upper right corner of the firebox and engage its toe with the indentation in the Bottom Log Figure 30 Engage the Left Log with the rear burner plate pin Figure 31 Evenly disperse the Ember Stones evenly over the burner plate around the log parts DO NOT ALLOW EMBER STONES TO BLOCK THE PILOT ASSEMBLY AREA The carry over ports directly in front of the pilot must remain clear for pr...

Page 21: ...lot operation or Proflame 2 Remote functionality IPI for intermittent operation 4 Once the pilot is lit burner operation is controlled by the rocker switch located on the front panel See fig 32 ON OFF use for manual control of the burner It remains in the ON position for use with the Proflame 2 remote transmitter T STAT use for optional wall thermostat 5 PILOT FLAME The pilot flame should be stead...

Page 22: ...st setting for 20 30 minutes before making any adjustments Always make adjustments in 1 8 increments and allow the burner to settle in for 10 15 minutes between additional adjustments Figure 38 Proper flame picture Traditional Logs Figure 37 Air Shutter location Operation Notes 1 For the first several hours of operation it is common to detect some odor as the metal and manufacturing materials cure...

Page 23: ...This valve has the ability to be stepped down in six increments between high and low It can be done manually or by setting the remote control to the Smart thermostat modulation mode Automatic modulation means that as the room temperature approaches the limit set for shut down the valve gradually decreases or steps down the fire intensity Conversely as room temperature cools the valve gradually inc...

Page 24: ...range fan speed and flame height MODE Key used to select the component to be controlled CPI IPI Burner Fan and Accent Lamp The Wall Mount Bracket can be used for convenient Transmitter storage Initializing the System 1 Press the Controls Access Door to release the magnetic catch and swing the panel down Switch the Burner to OFF 2 Install three AAA batteries into the Transmitter 3 Press the black o...

Page 25: ...th the system ON and the burner flame level at maximum press the Down Arrow Key once to reduce the flame height by one step Each time the Down Key is pressed the flame will step down until the burner is finally turned off Fig 44 The Up Arrow Key will increase the flame height each tim it is pressed If the U Arrow Key is pressed while the system is on but the flame is off the flame will come on in ...

Page 26: ...unsupervised operation To activate the Lock press the Mode key and UP Key at the same time Fig 56 To de activate the Lock press the Mode Key and UP Key at the same time Low Battery Detection The life span of the batteries depends on various factors battery quality the frequency of ignition calls the frequency of changes to Set Points etc When Transmitter batteries are low the Battery icon will be ...

Page 27: ... Power SIT Proflame 2 IFC Proflame 2 IFC Wiring Diagram CAUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING THE CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION ALWAYS VERIFY PROPER OPERATION AFTER SERVICING THE APPLIANCE ATTENTION AU MOMENT DE L ENTRETIENDES COMMANDES ÉTIQUETEZ TOUS LES FILS AVANT LE DÉBRANCHEMENT DES ERREURS DE CÂBLAGE PEUVENT ENTRAÎUN FONCTIONNEMENT I...

Page 28: ...28 139467_03 GF 370 DV II June 2015 This page is intentionally blank ...

Page 29: ...F THE MAIN GAS SUPPLY AND DISCONNECT THE POWER SUPPLY TO THE APPLIANCE BEFORE REPLACING BATTERIES Glass Panel or Gasket Replacement 1 Use the 4 mm hex key to remove the four socket screws that attach the Glass Frame to the firebox Remove the lower screws first and be sure to adequately support the frame against the firebox while you remove the upper screws 2 Lay the assembly upside down on a flat ...

Page 30: ...ch time you replace the batteries you will need to initialize communication between the Receiver and the Transmitter 1 Place the slider switch in the REMOTE position 2 Insert the end of a paper clip into the hole marked PRG on the Receiver cover The Receiver will beep three 3 times to indicate that it is ready to syn chronize with the Transmitter 3 Install 3 AAA batteries in the Transmitter bay an...

Page 31: ...x Cover GF 370 MB 38 225402 Outer Rod Exhaust Restrictor 39 223224 Skamol Rear Panel 40 223235 Skamol Side Panel 2 not illustrated No Part Number Description 1 9911 Bolt Hex Cap M6x45 DIN 933 Class 8 8 Blk 2 9962 Bolt Hex Cap M6x10 DIN 933 8 8 Ser Flange Blk 3 117917 Screw HWH SMA 8 x 1 2 SL Blk Oxide 4 117967 Screw Pan Head 7 x 3 8 PH SMA Zinc 5 117968 Nut M6 Serrated Flange plain 6 117978 Screw ...

Page 32: ...V II June 2015 Figure 64 GF 37 DVII Spud assembly parts identification For stoves with serial numbers after 10000 BURNER ProFlame 2 Remote OPI IPI ON T STAT OFF PILOT MODE RED YEL GRN ORG YEL WHT BLU BLK GRN 40 41 39 42 43 ...

Page 33: ... 222280 Gasket Drop In Orifice Holder 24 223235 Flex tube w connectors 3 8 OD x 48 25 117922 Nut Hex M4 DIN 934 Plain 26 225562 Battery Heat Shield 27 157265 Replacement IPI Back up Battery Box 4 AA 28 118257 Hook Loop Tape 1 wide self adhesive 29 120517 Rocker Switch SPST Blk Plain 30 223201 Rocker Switch SPDT Center OFF Blk Plain 31 224781 Conrol Face Plate Silkscreened IPI Stoves 32 117917 Scre...

Page 34: ...2998 Bracket Firebox Mount GF 370 19 222999 Bracket Side Support GF 370 20 22320792 Bracket Door Catch GF 370 Matte Black Figure 65 External parts identification No Part Number Description 21 156843 Lower Door Hinge Asy GF 370 MB 22 156835 Replacement Outer Side Glass GF 370 23 22321692 Bracket Blower Mount GF 370 MB 25 223220 Plate Centering GF 370 26 223227 Blower Axial 40 CFM 120 V 27 22323292 ...

Page 35: ... IN A MANUFACTURED MOBILE HOME AND MUST BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS AND THE MANUFACTURED HOME CONSTRUCTION AND SAFETY STANDARD TITLE 24 CFR PART 3280 STANDARD FOR MANUFACTURED HOME INSTALLATION ANSI NCBCS A255 1 OR STANDARD FOR CANADA CSA Z240 4 THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS THAT IS INDICATED ON THE STOVE S RATING PLATE THIS APPLIANCE MAY B...

Page 36: ...tove or Fireplace This paragraph sets forth the sole remedy available under this warranty in the event of any defect in the Jøtul Scan or Atra Gas Stove or Fireplace The warranty period for any replaced component will be the remaining unexpired portion of the warranty period for the original component Please retain your dated sales receipt in your records as proof of purchase EXCLUSIONS AND LIMITA...

Page 37: ...component with substitute components determined by JØTUL to be of substantially equal quality and price The dollar value of JØTUL s liability for breach of this warranty shall be limited exclusively to the cost of furnishing a replacement component JØTUL shall not in any event be liable for the cost of labor expended by others in connection with any defective component Any costs or expenses beyond...

Page 38: ...38 139467_03 GF 370 DV II June 2015 Figure 66 Remove top plate Remove temporary spacers and replace top plate ...

Page 39: ...explosion D Do not use this appliance if any part has been under water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water 1 Set the thermostat to the lowest setting 2 Set the Burner Control Switch to the OFF position TO TURN OFF GAS TO THE APPLIANCE PILOT LIGHT FLAME PATTERN 1 STOP R...

Page 40: ...re beginning the installation it is important that the these instructions be carefully read and understood Jøtul maintains a policy of continual product development Consequently products may differ in specification color or type of accessories from those illustrated or described in various publications Jøtul vise sans cesse a ameliorer ses produits C est pourquoi il se reserve le droit de modifier...

Reviews: