Jøtul GF 300 BV Installation And Operation Instructions Manual Download Page 7

7

137945_Rev_F   7.29.10

Stove and Vent Clearance 

Requirements

Minimum Clearances from the Stove  

to Combustibles

 

 See figs. 2-3.

Rear: 

2”  (51 mm) - measured from Draft Hood 

Ceiling: 

32 1/4” (819 mm) - measured from stove top 

Corner: 

3”  (76 mm) - measured from stove top 

Sides:  

3”  (76 mm) - measured from stove top 

 

Minimum Clearances from the Vent Pipe to 

Combustibles

Horizontal Run:

 

Top: 

     Off the top of the pipe    2”  (50 mm)

 

Sides: 

  Off the sides and bottom    2”  (50 mm)

Vertical Run: 

 

All sides: 

 1”  (25 mm)

All vent components must be installed in accordance with 

the manufacturer’s instructions and within the terms of 

their listing. Refer to the manufacturer’s instructions for 

approved clearances from the vent pipe to combustible 

materials.

Minimum Alcove Dimensions 

Maintain clearances to combustibles as noted above.

Width: 

36”  (914 mm)  

Depth: 

24”  (610 mm)  

Height: 

61”  (1550 mm)        

Figure 3. Vent adaptor centerline at minimum clearance 

to corner walls.

Figure 4.  Mantel and Trim specifications -  

Stove installed flush with fireplace face. 

 Stove shown with standard legs.  With Short Legs, subtract 2 1/4” (51 mm) 

from the clearances indicated below.

Figure 4a.  Mantel specifications -  

Stove recessed into fireplace no more than 6 1/2”.

Mantel Clearances -

3” 

(76 mm)

2” 

(51 mm) 

To Rear Wall

Figure 2.  Parallel Installation Clearances.

3” 

(76 mm)

 

 



 

 









 

 



 

Summary of Contents for GF 300 BV

Page 1: ...or future reference QUEFAIRESIVOUSSENTEZUNEODEURDEGAZ Ne pas tenter d allumer l appareil Ne touchez aucum interrupteur Ne pas vous servir des t l phones se trouvant dans le b timent o vous trouvez App...

Page 2: ...stalled and serviced by professionals who are certified in the U S by the National Fireplace Institute NFI as NFI Gas Specialists THIS PRODUCT MUST BE INSTALLED BY A LICENSED MASTER OR JOURNEYMAN PLUM...

Page 3: ...tion 23 Illustrated Parts Breakdown 24 Replacement Parts List 25 Warranty Statement 26 Lighting Instructions 27 J tul GF BV Allagash Natural Vent Gas Stove 300 Manufactured and Distributed by J tul No...

Page 4: ...a Propane 12 0 WC 2 99 kPa 14 9 WC 3 71 kPa Manifold Pressure MIN MAX Natural Gas 1 2 WC 30 kPa 3 8 WC 95 kPa Propane 2 9 WC 722 kPa 11 0 WC 2 74 kPa Piezo Ignitor Standing Pilot 13 330 mm Rear Exit 2...

Page 5: ...thority in determining if a proposed installation is acceptable Any requirement that is requested by the local authority having jurisdiction that is not specifi cally addressed in this manual defaults...

Page 6: ...ation Due to the high operating temperatures this appliance should be located out of traffic and away from furniture draperies etc Maintain proper clearance to combustible mantels and fireplace trim C...

Page 7: ...turer s instructions and within the terms of their listing Refer to the manufacturer s instructions for approved clearances from the vent pipe to combustible materials Minimum Alcove Dimensions Mainta...

Page 8: ...through a roof must have a flashing storm collar thimble and a Type B cap is required See diagrams page 10 Venting on the Allagash CANNOT be less than 4 in diameter or greater than 4 in diameter Any...

Page 9: ...When installing at an altitude above 2000 the mini mum vertical rise becomes 12 from the draft hood Figure 6 GF 300 BV venting through a masonry chimney Listed termi nation cap required Storm collar...

Page 10: ...ion cap required NOTE Installation at altitude greater than 2000 re quires minimum 12 ft vertical rise from Draft Hood NOTE Installation at altitude greater than 2000 re quires minimum 12 ft vertical...

Page 11: ...TH THE REQUIREMENTS OF THE PRO VINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CAN1 B149 1 AND 2 INSTALLATION CODE AVERTISEMENT CET EQUIPEMENT DE CONVERSION SERA...

Page 12: ...e rear of the firebox When correctly positioned there will be 1 2 13 mm clearance be tween the burner plate and the front of the firebox See fig 15 11 CHANGE THE PILOT ORIFICE From within the firebox...

Page 13: ...Install the identification labels to the stove so that they can be seen by any person that may be ser vicing the stove Label A apply to back of stove Label B apply to stove s rating plate Small valve...

Page 14: ...2 0 14 9 The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing on that system at test pressures in excess of 1 2 psig 3 5 kP...

Page 15: ...Left Log Figure 23 Install Middle Log Figure 24 Position embers loosely and maintain 1 4 clearance from the burner skirt edges 1 4 6 mm 1 4 6 mm Pilot Assembly KEEP CARRY OVER PORTS CLEAR PN 220727 P...

Page 16: ...ssory wiring diagram Flame Appearance Air Shutter Adjustment The GF 300 BV gas stove is shipped from the factory equipped to burn Natural gas If the stove has been converted for use with propane the A...

Page 17: ...ated in the center of the valve face Fire intensity can be adjusted up to 50 between the LOW and HIGH settings See fig 29 NO SMOKE OR SOOT SHOULD BE PRESENT CHECK LOG PLACEMENT IF ANY SOOT OR SMOKE IS...

Page 18: ...ure the stove is cold and there are NO hot embers 5 This appliance has a continuous burning pilot flame Exercise caution when using products having combus tible vapors Always shut off gas supply while...

Page 19: ...e Compartment Convection Airways and optional Blower to BE CERTAIN THAT THE FLOW OF COMBUSTION AND VENTILATION AIR IS UNOBSTRUCTED The firebox should be vacuumed annually to remove any surface build u...

Page 20: ...using the two M6 hex nuts and a 10 mm wrench See fig 34 3 Attach the Blower to the stove with the screen open ing to the rear using the two M6 flange head hex bolts as shown in fig 35 4 Attach either...

Page 21: ...on is not desired place the blower control switch in the MANUAL position M6 x 20 mm Hex Bolts Male Quickconnector Female Figure 35 Attach Blower to the stove bottom and connect wires to Snapstat and f...

Page 22: ...ck wall resting on the burner skirt Fig 40 5 Install a Side Panel Tilt the panel bottom edge first into position against the side wall The panel will stand on its own against the wall fitting snugly b...

Page 23: ...equipe ment L installation n est pas propre et complete jusqu a l operation de l appareil converti est cheque suivant les criteres etablis dans les instructions de proprietaire provi sionnees avec l...

Page 24: ...10 Figure 44 GF 300 BV Allagash Illustrated Parts Breakdown NOTE Models beginning at Serial No 30000 are configured with a front mounted gas control valve ONLY USE REPLACEMENT PARTS PROVIDED BY AN AUT...

Page 25: ...960 64 Glass Frame 22076292 65 Glass Gasket Tadpole 129124 Replacement Glass Kit 155599 66 Firebox Heat Exchanger 221192 67 Screw 8 x 1 2 Blk 117917 68 Nut M6 Flange 2 117968 69 Exhaust Baffle 220763...

Page 26: ...osts associated with the repair of gas controls plumbing burners log set or sheet metal firebox beyond the warranty period 5 Damage caused by unauthorized modification use or repair 6 Damage to enamel...

Page 27: ...knob Never use tools If the knob will not push in or turn by hand do not try to repair it Call a qualified technician Force or attempted repair may result in a fire or explosion D Do not use this appl...

Page 28: ...ginning the installation it is important that the these instructions be carefully read and understood J tul maintains a policy of continual product development Consequently products may differ in spec...

Reviews: