Jøtul GF 3 CF 2 Installation And Operation Instructions Manual Download Page 16

16

Problems With the Flame Pattern

Tall, narrow, yellow flames

These flames can soot the vent system and may be the
result of insufficient oxygen supply. Check for correct air
volume by measuring the opening (fig.

19) 

at the air

shutter.

Correct opening dimensions are normally:

For Propane -  Open 12.6 mm  (fully open)

For Natural Gas - Open 9.6 mm

Warning! To avoid burns, do not adjust the air opening

until the burner has cooled down.  Blocked orifice: Make
sure the main orifice (fig.26) is dirt-free and that the
orifice has the appropriate size. See technical data.

Poor draught in the vent system may be due to

improper installation or because the vent has no climb
towards the chimney.

Tall, blue flames

The cause may be too much oxygen. Check for correct air
volume by measuring the opening (fig. 19) at the air
shutter.  The cause may also be that the gas pressure is
too high. Check the gas pressure as described in the
section about gas pressure on page 10.

When There is No Gas Supply to the
Burner.

This is the trouble-shooting procedure for the electrical
components:

1. Make sure the control knob on the valve is set to “ON”.

Check the position on the “ON/OFF/Thermostat” switch
at the back of the appliance. It should be set to the ON
position.

2. Make sure the wire from the valve to the “ON/OFF/

STAT” switch is connected correctly.

This is the trouble-shooting procedure for the thermopile

(fig. 25):

1. Make sure the gas pressure is correct (see section

about gas pressure, page 10).

2. Make sure the pilot burner has 3 flames.

3. Make sure the flame is centred on the thermocouple.

4. Make sure the thermocouple is enveloped by the flame

up to at least 10mm (3/8") from the tip (fig 19).

5. Check the wires to the thermopile for cracks or damage.

6. Dismantle the wires from the vent.

7. Dismantle optional equipment, such as thermostat or

remote control.

8. Check the voltage generated by the thermopile (see fig

25). Connect the multimeter with plus to one cable clip
(D). Connect minus to the other cable clip. Light the pilot
and make sure the control knob remains on “PILOT” (fig.
21-B). At this point the multimeter should show 500-
700mV.

9. Reconnect the wires to the valve and make sure only

the ON/OFF/STAT switch is connected.

10.Turn the control knob on the valve to “ON” and turn the

ON/OFF/STAT switch to “ON”. At this point the multim-
eter should show more than 300 mV.

11. If a thermostat or remote control is to be connected, it

can be done now. At this point the multimeter should
show more than 175 mV.

Figure 24.
Thermocouple system
check.

Figure 25.
Thermopile system
check.

Summary of Contents for GF 3 CF 2

Page 1: ...flammable vapors and liquids in the vicinity of this or any other appliance WHATTO DO IF YOU SMELL GAS Donottrytolightanyappliance Do not touch any electrical switch do not use any phone in your buil...

Page 2: ...ompany Date Service details Annual service year 5 Sign Company Date Service details Annual service year 6 Sign Company Date Service details Annual service year 7 Sign Company Date Service details Annu...

Page 3: ...Installer Information 6 5 User Information 12 6 Troubleshooting 14 THIS OWNER S MANUAL PROVIDES INFORMATIONTOENSURESAFEINSTALLATION AND EFFICIENT DEPENDABLE OPERATION OF YOUR STOVE PLEASE READTHESE IN...

Page 4: ...Appliance Category II2H3P Gas Types NG LPG G20 1 G31 2 State of Adjustment I2H I3P Supply Pressure mbar 20 37 NominalHeatInput Nett kW 6 3 6 8 Maximum Gas Consumption at Full Rate m3 h at 15 C 1013 25...

Page 5: ...intended for use on a gas installation with a governed gas supply SafetyPrecautions This appliance must be installed in accordance with the rules in force Consult instructions before installation and...

Page 6: ...staller When the TTB is exchanged only original manufacturer s parts shall be used Installation Guide for Qualified Personnel Important The appliance is factory pre set for Natural Gas G20 If Propane...

Page 7: ...arent reason especially during windy or stormy conditions and will not relight it is possible that the flue system safety switch has operated Allow the appliance to cool down and relight Any obstructi...

Page 8: ...pliance will not work correctly and may cut out repeatedly if the sealing of the appliance and flue is not correct Remember if the closure plate extends beyond the sides or top of the stove a non comb...

Page 9: ...tically simulate glowing coals when the burner is operating These should be spread evenly over the burner plate and around the logs 1 Engage the holes in the underside 0f the rear log with the two peg...

Page 10: ...raught diverter hood on the rear of the appli ance accessible through a cutout in the rear heatshield The smoke should be drawn into the flue and no smoke should spill into the room If the smoke does...

Page 11: ...call for service Annual Service Annual service of the appliance includes the following check points Lighting the pilot flame Cleaning the glass The gasket around the glass must be inspected annually...

Page 12: ...778 to provide extra protection Operating Instructions Lighting Note Odors when using the stove When used for the first time the appliance may emit an irritating gas that may smell a little The gas is...

Page 13: ...off of paint and lubrication used in the production process See section Odors when using the stove for the first time Adjusting the Heat Setting Heat and flame size can be adjusted by turning the reg...

Page 14: ...when the valve is being replaced Troubleshooting When No Spark is Generated at the Pilot Head It is uncommon for the Piezo spark ignitor fig 23 A to fail unless it has mechanical damage If the spark...

Page 15: ...valve even if the pressure is OK at outlet E You should therefore always check for leakage Thermocouple Fig 24 and Thermopile Fig 25 A thermocouple is in principle a thermal generator and consists of...

Page 16: ...at the back of the appliance It should be set to the ON position 2 Make sure the wire from the valve to the ON OFF STAT switch is connected correctly This is the trouble shooting procedure for the the...

Page 17: ...17 Figure 26 Check main burner orifice for debris blockage Burner pan is removed Burner Orifice...

Page 18: ...44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 4 7 61 62 63 5 64 65 1 66 67 68 69 70 71 72 73 74 75 76 77 78 79 6 81 82 83 84 85 86 30 89 88 80 90 35 34 24 87 91 92 93 94 ONLY USE REPLACEMENT PART...

Page 19: ...117917 68 Nut M6 Flange 2 117968 69 Exhaust Baffle 220763 70 Inner Draft Hood 220914 71 Screw 8 x 1 2 Blk 4 117917 72 Upper Draft Hood 222519 73 Draft Hood Cover Plate 222520 74 Starter Collar 5 dia...

Page 20: ...rmance with local and national building regulations Before beginning the installation it is important that the these instructions be carefully read and understood J tul maintains a policy of continual...

Reviews: