12
139262 Rev_H
9 / 11 / 2012
4.5
Clearances to Fireplace Mantels
and Surrounding Trim
See the Clearance Chart on page 13 for approved clearances
to combustible materials that may be part of fireplace
construction.
Mantel and Trim clearances may be reduced by 50% with
use of shielding constructed in accordance with NFPA 211
specifications.
Figure 13. Alcove with Unprotected Walls.
Figure 14. Alcove with Wall Protection.
Figure 15. Hearthmount Clearances.
4.4 Alcove Installation
The Jøtul F
50
TL can be installed in an alcove as
diagrammed in figs. 13.-14.
1. The stove must be installed only with double-wall chim-
ney connector.
2. Wall and ceiling protection, if used, must extend over the
entire area.
3. Alcove floor protection must consist of a UL/ULC or WHI
listed hearth pad or a non combustible material.
4. Minimum Alcove Ceiling Height:
Unprotected Surface - 72” (183 cm)
Protected Surface - 59” (150 cm)