Code 02; alarm “Tc sensor damage”

This alarm is reported when a temperature on exhaust gas 

sensor exceeds 1115°C. It indicates that a measurement range of 

both sensor and regulator is exceeded

Code 03; alarm “Tc connection error”

This alarm will be reported when the exhaust gases temperature 

sensor (thermocouples) is connected incorrectly. The alarm will 

occur when exhaust gases temperature during burning in the 

fireplace reaches approximately 100°C. Change the polarization 

of exhaust gases sensor cables connection.

Code 04; alarm “Caution !!! Attempt of deactivating the 

regulator at high temperature”

This message will be displayed in situation when the user will try 

to switch the regulator off in spite of the fact that temperature 

of the jacket (on 

Tc

 sensor) is higher than 

Toperation

 set value. 

Select 

Yes

 in order to switch the regulator off and completely 

close the intake air throttle (in spite of setting a different value 

of 

Throt.off/put down

). It is not recommended to switch the 

regulator off at high temperatures.

Code 05; alarm “Fuel shortage”

Message indicating shortage of fuel in the fireplace furnace. 

It indicates that the regulator detected fuel shortage in the 

fireplace furnace. This message can be displayed only in 

automatic operation mode; if it is reported too often and in 

inappropriate moments, it means that the function of fuel 

shortage detection requires calibration. Detailed description of 

parameters of fuel shortage detection function is described in 

chapter “

Fuel shortage detection”

. Fuel shortage detection can 

be disabled. In such case, message will not be displayed.

12.0 Options menu

Icons displayed in 

“Options”

 provide access to particular 

settings connected with burning process and operation of 

regulator outputs. Detailed description of particular positions 

is included in sections below.

12.1  Burning options

Burning settings of the regulator are made in this menu. Below, 

there is a detailed description of parameters.

Tset min -

 Minimum preset temperature of exhaust gases in the 

fireplace. According to the value of this parameter, the regulator 

will  calculate  temperature  steps.  Value  of  this  parameter  is 

assigned to position 1 of temperature presetting steps.

Tset max

 - Maximum preset temperature of exhaust gases in 

the fireplace. According to the range spread between 

Tmax

 

and 

Tmin

, the regulator will calculate thresholds of a preset 

temperature  values.    Value  of  this  parameter  is  assigned  to 

position 

11

 of temperature presetting steps.

Twork

 – – casual operation temperature of a fireplace. When 

the temperature of exhaust gas in the smoke pipe reaches the 

set values, the flame controller activates the flames animation 

in the main display. If the temperature of exhaust gas is higher 

than Twork parameter, the flame controller, after switching 

on, starts running in automatic operation mode 

phase I

. When 

the fireplace is cooling down and the temperature of exhaust 

gas decreases below 

Twork –Hysteresis 1

, the flame controller 

switches into automatic operation 

phase II

Throt. safe mode

 – the throttle position during power supply 

failure.

In the areas with chronic power supply disruptions, the fireplace 

can still be used. In order to operate the fireplace, the user has 

to set the throttle parameter on a different value than 0 and 

operate the fireplace manually by means of a manual throttle.  

The manual throttle is connected in-line to the throttle which is 

operated through the fireplace.

 

When the flame controller is on (standard operation) the 

additional manual throttle is to be fully open. Any other position 

of the manual throttle results in the faulty operation of the flame 

controller. 

Attention! In case of power supply loss, the throttle closure is 

determined by the default setting at 50%.

Auto off 

– if the temperature drops below 

Toperation-Histeresis 1

 

and value 

YES

 is set on the screen, the flame controller shuts 

the throttle and starts the scavenging process (blow-bys). If the 

temperature does not increase in the fireplace above 

Toperation

 

value after several failed scavenging cycles (blow-bys), the 

flame controller switches off. If this option is not deactivated 

by setting 

NO

, the flame controller shuts the throttle once an 

extinguishing extension period is over and switches into 

STOP

 

operation mode.

Attention! To restore the default settings see „Restoring default 

parameters”.

Summary of Contents for ERS 01

Page 1: ...GB Before use please read General use and maintenance manual carefully The manuals which are enclosed with the product must be kept throughout the product s entireservice life Electronic Flame Control...

Page 2: ...Closing the casing step one 7 Fig 11 Closing the casing step two 7 Fig 12 User log in screent 7 Fig 13 Wrong password message 7 Fig 14 Controller and welcome screen 10 Fig 15 Main screen 10 Fig 16 Op...

Page 3: ...ded to get acquainted with a local system of utilization of electric and electronic products It is recommended to act accordingly to local regulations and not to throw used products to containers toge...

Page 4: ...damaged In no circumstances can the design of the regulator be modified Keep the regulator out of reach of children Do not assemble the device when it is energized Operating the device which is defec...

Page 5: ...ing of the cable and bushing tip should be within the range of 8 10 mm Cable is inserted into a terminal by pushing a button on this terminal with a flat screwdriver inserting the cable tip with a col...

Page 6: ...ure is exceeded The throttle should be calibrated together with the regulator Calibration process is described in chapter 12 4 Calibration process can be performed outside the fireplace by connecting...

Page 7: ...parameters may result in the malfunction of the fireplace or damage Description of parameters Tmin Parameter limiting the possibility of presetting minimum temperature of exhaustion gases Tzadmin val...

Page 8: ...oller s throttle in phase I of lighting process Td lighting I differentiation time of PID algorithm for controlling the flame controller s throttle in phase I of lighting process T lighting I optimum...

Page 9: ...ount of fuel The intake air throttle is opened at 60 100 and exhaust gases temperature is decreasing Fuel amount which is supplied to the fireplace furnace is insufficient to maintain temperature of f...

Page 10: ...adout The regulator can be operated with the use of provided or adapted remote control Adaptation procedure is described in chapter Handling Remote control menu Press the switch in order to enable dis...

Page 11: ...ade by a menu system Activating MENU is also performed by pushing or turning the knob in the main window so as to select the MENU icon Push the knob according to the following diagram Fig 19 Activatin...

Page 12: ...of a fireplace the user can select another temperature out of 11 set temperature options by increasing or reducing the temperature s value Attention It is not recommended to use low temperature range...

Page 13: ...rature of the automatic mode of operation the flame controller switches into the second stage of lighting process 10 1 2 Lighting phase II In the second phase of lighting flame controller slowly shuts...

Page 14: ...nabling to open the throttle and enable edition by pushing the knob In edition mode blinking value turn the knob in order to change position of the air throttle there is no need to confirm the value F...

Page 15: ...the regulator will calculate temperature steps Value of this parameter is assigned to position 1 of temperature presetting steps Tset max Maximum preset temperature of exhaust gases in the fireplace...

Page 16: ...o II automatic mode stage II activated the throttle positions on the fireplace temperature fall to the value of Toperation dT auto II automatic mode stage II activated the difference of temperature in...

Page 17: ...ation manual If no access code is provided 0000 value will be left the regulator will show the read only parameter values included in the menu Important Parameters should be modified only by persons w...

Page 18: ...tion is used in dark compartments The encoder s backlight pulsing is maintained after switching the regulator off 13 2 Handling Screen menu This menu provides access to set screen options Turning the...

Page 19: ...ff screen When disabling function is confirmed by selecting YES the intake air throttle will be set to Throt off put down parameter value thisparameterisdescribedinchapter Burningoptions However if th...

Page 20: ...roducts supplied may therefore differ in specification colour and type of accessories from those illustrated and described in the brochure J tul Polska Sp z o o Polska 80 871 Gda sk ul Twarda 12 A www...

Reviews: