, JSPR INSTALLATION, OPERATION AND MAINTENANCE MANUAL

tnbpowersolutions.com/joslynsurge

 

CAUTION: The JSP Series unit’s performance will be limited 

severely if the conductors are (a) too long, (b) are of too small a wire 

gauge, (c) have too many bends or (d) have sharp bends. For optimum 

performance never exceed 10' conductor lengths.

The factors listed above should be addressed during the design of an 
installation to reserve a suitable place for the JSP Series unit next to its 
point of connection to the electrical system . The selected mounting location 
should allow for the shortest possible conductor runs and a direct route with 
a minimum of bends . If bends are required, they should be 

sweeping

 bends . 

Do not make sharp 90° bends for appearance purposes because they will 
severely decrease the effectiveness of JSP Series unit .

Binding or twisting conductors together using tie-wraps or electrical tape 
increases the protection performance of the device .

The conductor length should be as short as possible to ensure the maximum 
level of protection . Wires are marked with (Phase A, B, C, Line 1, Line 2, 
Neutral or Ground) depending on the model . 

Conductor Sizing & Routing

Note: High-Leg Orange must be B Phase

A

  30–200 AMP, 3-POLE 

1

CIRCUIT BREAKER

A B

B

C

C

N

N
G

N

G

JSP SERIES

  CONDUCTORS 

2

FURNISHED WITH

JSP SERIES

A

C

B

G

N

EARTH

GROUND

Xo BOND

1  All JSP Series units can be connected without an 

upstream breaker/fuse.

2  JSP 60 through 100kA and all JSPR units are furnished 

with #10AWG leads.  

Figure 5

3-Phase High-Leg Delta, 4-Wire

Summary of Contents for JSP series

Page 1: ...Surge Protective Devices Installation Operation and Maintenance Manual PN 750 0100 001 C00 JSP JSPR S U R G E P R O T E C T I O N S U R G E P R O T E C T I O N Joslyn TM TM ...

Page 2: ...ice Configurations 5 Conductor Sizing and Routing 6 Upstream Overcurrent Protection Device 7 Mounting 8 Indoor vs Outdoor Installation 8 Conduit Openings 8 Electrical Connections 10 Connecting Form C Dry Contacts 11 Remote Monitoring 11 Verification and Power Up 12 Troubleshooting 13 Installation Assistance 13 Standards and Listings 13 Return and Warranty Procedures 13 Warranty Statement 14 ...

Page 3: ...elta or Split Phase JSP Series device See NEC Article 250 If the transformer is not accessible check the main service disconnect panel for the NG bond Lack of a proper bond will damage JSP Series and void the warranty W A R N I N G Do not HIPOT the JSP Series units or the electrical system to which the JSP Series unit is connected without disconnecting the JSP Series units conductors including pha...

Page 4: ...hase 2 Wire Ground JSP R xxx 1P2401 240 216 264 N A 1 Phase 2 Wire Ground JSP R xxx 1S2401 120 240 108 132 216 204 Split Phase 3 Wire Ground JSP R xxx 3Y2081 120 208 108 132 187 229 3 Phase 4 Wire Ground JSP R xxx 3Y3801 220 380 198 242 342 418 3 Phase 4 Wire Ground JSP R xxx 3Y4151 240 415 216 264 374 457 3 Phase 4 Wire Ground JSP R xxx 3Y4801 277 480 249 305 432 528 3 Phase 4 Wire Ground JSP R x...

Page 5: ...2 Wire Figure 4 3 Phase Delta 3 Wire Figure 3 3 Phase Wye 4 Wire 30 200 AMP 3 POLE 1 CIRCUIT BREAKER JSP SERIES EARTH GROUND Xo BOND B N C A N G N G CONDUCTORS 2 FURNISHED WITH JSP SERIES A B C G N A B C 30 200 AMP 3 POLE 1 CIRCUIT BREAKER B C A N G JSP SERIES CONDUCTORS 2 FURNISHED WITH JSP SERIES A B C G A B C G EARTH GROUND Service Configurations Figures 1 5 show the electrical relationship bet...

Page 6: ...s are required they should be sweeping bends Do not make sharp 90 bends for appearance purposes because they will severely decrease the effectiveness of JSP Series unit Binding or twisting conductors together using tie wraps or electrical tape increases the protection performance of the device The conductor length should be as short as possible to ensure the maximum level of protection Wires are m...

Page 7: ...switch or connected directly to the bus of the panelboard or switchboard it is protecting If direct bus connection is used Joslyn recommends installing the JSP Series unit behind a disconnect switch or other disconnecting means for ease of serviceability If the SPD is connected to a dedicated OCPD a 60A breaker is recommended 30A minimum 200A maximum JSP Models Conductor size JSP 120 6AWG JSP 160 ...

Page 8: ...adjacent studs After the drywall has been installed install Flush Mounting Plate FMP by first removing the JSPR enclosure lid Place the FMP over enclosed body Attached the FMP to the wall using the enclosed hardware kit Screw the lid back on to the enclosure body JSPR 120 160 Weight 30 lbs 13 6 kg NEMA 4 enclosures are suitable for indoor or outdoor use NEMA 4X stainless steel enclosures are suita...

Page 9: ...gs continued Figure 6A Conduit Openings and Enclosure Mounting Dimensions JSP Dim JSP 60 80 100 JSP 120 160 JSP 200 240 300 400 H1 6 00 152 4 10 00 254 0 14 00 355 6 H2 6 75 171 5 10 75 273 1 14 75 374 7 H3 7 50 190 5 11 50 292 1 15 50 393 7 W1 6 00 152 4 8 00 203 2 12 00 304 8 W2 4 00 101 6 6 00 152 4 10 00 254 0 D 6 20 157 5 6 20 157 5 D1 4 16 105 7 D2 2 00 50 8 All measurements in inches mm W1 ...

Page 10: ...ors Each phase conductor is labeled Phase A B or C Ensure that the conductor lengths are kept as short and straight as possible On all high leg delta systems the high leg 208V LN must be connected to the Phase B of the SPD Color coded orange according to NEC The 3 Wire Ground Delta JSP Series units do not have a neutral conductor All measurements in inches mm and pounds kg Figure 6B Enclosure Moun...

Page 11: ...ition Models JSP120kA to JSP400kA For these models the Form C contacts must be wired by the installer See Figure 8 for the Form C contact configuration and terminal location on the monitor board The annotations on the diagram match the markings on the terminal block The installer must route the monitoring conductors to the terminal blocks on the door mounted main monitoring board Route the wires t...

Page 12: ...on For Standard JSP units 120 160 200 240 300 and 400 or M 60 80 and 100kA and JSPR Units Verify that all Protection Available indicating lights are illuminated The Protection Available lights extinguish only upon failure of one or more phases indicating an alarm condition Audible alarm should not operate under normal conditions The audible alarm can be muted by pressing the ALARM SILENCE button w...

Page 13: ...of Failure Service Required indicating light illuminated Desired Action from Joslyn Replace tnbpowersolutions com joslynsurge UL Listed 1449 4th Edition for Type 1 and Type 2 SPD application cUL and UL 1283 Meets Requirements for UL 96A Compliant to IEEE C62 41 1 2002 C62 41 2 2002 and C62 45 2002 NFPA 70 NEC Article 285 RoHS Compliant Standards and Listings The following standards and listings ap...

Page 14: ...uct alteration of the Product including removal of any warning labels accidents or improper installation application operation or repair of the Product THIS WARRANTY REPRESENTS THE ENTIRE WARRANTY OF SELLER ALL OTHER WARRANTIES EXPRESS OR IMPLIED ORAL OR WRITTEN INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED The liability o...

Page 15: ...15 JOSLYN JSP TM JSPR INSTALLATION OPERATION AND MAINTENANCE MANUAL Notes ...

Page 16: ...ation JoslynTM is a trademark of Thomas Betts International Inc Specifications are subject to change without notice Visit our website for latest revisions Thomas Betts Power Solutions 5900 Eastport Blvd Richmond VA 23231 4453 USA Tel 804 236 3300 Toll free 800 238 5000 Fax 804 236 4841 tnbpowersolutions com joslynsurge 750 0100 001 C00 081418 Model Date of Purchase Date Installed Installer ...

Reviews: