background image

 

CONTROL PANNEL 

1 Mode 

selector 

switch 1 
(operation mode) 

2 Mode 

selector 

switch 2 (setting 
time, program) 

3 LCD 

display 

4 Override 

button 

5 Setting 

the 

minutes 

Setting the hours 

7 RESET 
8 Setting 

the 

days 

9 Programming 

of 

timer (saving 
settings) 

 

PROGRAMMING INSTRUCTIONS 

 

Before you start programming the unit, move the mode selector switch (2) in to position   and shortly press the RESET (7) button to clear 
the existing program. 
 

SETTING THE ACTUAL TIME AND DAY 

After pressing the RESET (7) button, the display will look like this 

All preprogrammed settings will be 

deleted. The unit is now ready to be programmed. 

You can set the actual time by pressing the [h] hours(6) and [m] minutes (5) , 24 hr display! 

You can set the actual day by pressing the [1…7] button(8), (Mon=1, Tue=2, We=3…..). 

 

1

st

 Step 

Move the mode selector switch (2) into position 

The clock has 16 points: 8 x ON (OPEN the valve) and 8 x OFF (CLOSE the valve). 

All odd (1,3,5 etc.) switch points open the valve, all even (2,4,6 etc.) switch points closes the valve. The switch points are numbered from 1 
to 16. When programming the unit, the

   

symbol will display when setting a valve open cycle. 

When the following display appears

 

 

you can enter the first valve open cycle. 

 

2

nd

 Step 

Enter the time you would like the valve to open by means of pressing the (h)hours (6) and 
(m)minute (5) buttons. 
 

3

rd

 Step 

 
Set the day of the week when the valve should OPEN (by pressing [1…7]) (8). 
- set the day (8) 

(Mon=1, Tue=2, We=3…..) 

- Form time blocks  Mon-Fri (1/2/3/4/5) 
  Mon-Sat 

(1/2/3/4/5/6) 

  Mon-Sun 

(1/2/3/4/5/6/7) 

The day must be set otherwise the switching point will not be activated. 
 

4

th

 Step 

By pressing the [

] (9)key, you save the switching point data and go on to the next switching 

point (CLOSE).  

The display will show 

You can now set the time and day for closing the valve. 

By pressing the [

] (9)key, you save the switching point data and go on to the next switching point 

(OPEN). 
 

5

th

 Step 

To set the next OPEN and CLOSE cycle,  please refer to step 3, 4 and 5. 
To go to the next day, you must complete the 16 switching points (leave the unused switching points at 

the value 0:00 by simply pressing the [

] (9)key until the display shows 

 (3)).  

Then select the next day and continue programming as described under step 3, 4 and 5. 
 

6

th

 Step 

After you have finished programming the unit, move the mode selector switch 2 in to position RUN 
And move mode selector switch (1) in to position AUTO. 
The unit will now operate fully automatically. 

 
CHOOSING THE CORRECT WORKING MODE (Mode selector switch 1): 
 

AUTO 

Unit will work by means of its program (also when using the remote switching feature) 

Unit will OPEN valve permanently (i.e. after hours work shift) 

Unit will CLOSE valve permanently (i.e. holiday factory shutdown) 

 

PROGRAM OVERRIDE BUTTON 

[

(4) 

 

By pressing the [

] (4) button you will override the program for this day (meaning the valve will be closed from the time you press the 

[

] (4) button , until  24:00 the same day. When in override mode the  

 

(4) symbol will be displayed, after which the 

 

symbol 

will be displayed indicating the program mode per day.

 

 

Summary of Contents for Air-Saver 1"

Page 1: ...ith types of fluids or gasses as stated in its documentation Usage of this product in conditions not specified in the product documentation or contrary to the instructions hereby provided is considered IMPROPER The manufacturer will not be held liable for any damages resulting from improper use of the product ATTENTION Observe valid and generally accepted safety rules when planning installing and ...

Page 2: ...________________________________________________ Motorised Ballvalves usually operate in any mounting position We recommend however that the valve is mounted according to these drawings ______________________________________________________________________________________________________ Minimum space required around the unit is 100 mm ______________________________________________________________...

Page 3: ... the day 8 Mon 1 Tue 2 We 3 Form time blocks Mon Fri 1 2 3 4 5 Mon Sat 1 2 3 4 5 6 Mon Sun 1 2 3 4 5 6 7 The day must be set otherwise the switching point will not be activated 4th Step By pressing the 9 key you save the switching point data and go on to the next switching point CLOSE The display will show You can now set the time and day for closing the valve By pressing the 9 key you save the sw...

Page 4: ...nd CLOSE will become OPEN Air Saver 1 housing Figure 1 Air Saver 2 housing Figure 2 Note On the 2 version figure 2 you can manually open close the valve by turning the knob on top of the actuator TECHNICAL SPECIFICATIONS Power supply 115VAC or 230VAC see label Power consumption 7W during the opening and closing of valve Opening closing time 30 seconds 90º for the 1 version 105 seconds 90º for the ...

Page 5: ...n the top cover Identify the remote switching cable sides Slide the remote switching cable through the cable gland Connect the RED remote cable with the RED cable of point 3 Slide the RED cable back into its place marked with the number 3 Connect the BLUE remote cable with the BROWN cable of point 5 ...

Page 6: ...ct the BLACK remote cable with the GREY cable of point 4 Slide the BLACK GREY cables back into its place mark with the number 4 Slide the BROWN remote cable onto point 5 A complete look at the cable set up Tighten the 4 screws and the cable gland ...

Page 7: ...k displaying the correct time TROUBLESHOOTING Check whether the valve has been rotated manually This could interfere with the programmed OPEN and CLOSE times i e the OPEN times could become the CLOSE times and visa versa Check supply voltage Check pressure ...