Installation, Operating and Maintenance  

 

 

7/8 

Instructions for Jola external-mounting limit switches 
RK 1/K/…/Variant ./Ex-..   

 

 

 

21.04.2018

 

 

6. 

Connection 

 

Connect the 

contact of the external-mounting limit switch 

RK 1/K/…/Variant ./Ex-.. 

as shown in the circuit diagram in the supplied product documentation.  

If intrinsically safe contact protection relays are used, connect the external-
mounting limit switch RK 1/K/…/Variant ./Ex-.. in line with the instructions 
contained in the corresponding production description. 

 

Potential equalisation is necessary with: 

 

the external-

mounting limit switch RK 1/K/…/Variant ./Ex-.. 

and 

 

the metal accessories and the accessories made of antistatic electrically 
conductive plastic. 
 
 
 
 

 

 
 
 
 
 
 

Connection to the potential equalisation system is essential for safe operation 
and must never be neglected.

  

 
You must also always ensure that you are connecting to the potential equalisation 
system and not to a potential earth. 
 
 
 
 
 
 

7. 

Start-up 

 

Prior to start-up, you must re-check the mounting position, the mechanical 
fastening and the electrical connection. 

In particular, you must check once again that the unit is also connected to the 
corresponding, admissible intrinsically safe circuit (see point 2). 
 

In addition, you must also check and verify that there is no possibility 
whatsoever of hazardous conditions occurring due to non-adherence to any of 
the relevant instructions, standards or official regulations. 

 
Only then may the unit in question be started up electrically. 
 
 

The entire installation set-up must always comply with the standard  

IEC/EN 60 079-14 resp. the replacing standard. 

Connect the green-yellow conductor or the non-insulated conductor of 

the cable (depending of the type of cable) of  

the external-

mounting limit switch RK 1/K/…/Variant ./Ex-..  

to the potential equalisation system. 

 

The horizontal metallic shaft and all other accessories made of metal or 

made of electrically conductive plastic material have as well to be 

connected to the potential equalisation system. 

Summary of Contents for RK 1/K Variant Ex Series

Page 1: ...These Installation Operating and Maintenance Instructions must always be handed over to the fitter operator service personnel of our products together with all other user documentation and informatio...

Page 2: ...ia IIC T6 Ga or II 2 G Ex ia IIC T6 Gb Tamb 20 C to 60 C INERIS 12ATEX0059 are binary contact devices for use in underground areas in mines as well as in above ground areas of mines which could be at...

Page 3: ...hole situated in the middle of the body of the switch Through this hole the limit switch has to be mounted on a horizontal shaft of the customer s device which permits a rotation of max 180 The rotat...

Page 4: ...or the external mounting limit switches RK 1 K Variant Ex Sensor type Type designation Li Ci Each external mounting limit switch RK 1 K Variant Ex 1 H per meter connecting cable 200 pF per meter conne...

Page 5: ...itch and following all instructions contained therein The qualified specialist personnel must ensure that they are familiar with all valid standards regulations local requirements and specific conditi...

Page 6: ...mits a rotation of max 180 The rotation of the shaft causes the switching In order to prevent an incorrect functioning of the limit switch and a cable break a sufficient cable length must be left Afte...

Page 7: ...em and not to a potential earth 7 Start up Prior to start up you must re check the mounting position the mechanical fastening and the electrical connection In particular you must check once again that...

Page 8: ...witch is installed as a safety element within a system it must always be inspected and checked at intervals to be agreed with the local supervisory authorities Prior to all maintenance work the qualif...

Reviews: