21. ANA TEST
View the control level for each of the analog inputs.
The analog voltage level for the 4 analog inputs can be tested and viewed as a
percentage or hexadecimal value. The level displayed is proportional to the 0-10VDC
analog input where 5VDC is 50%.
Press EXECUTE to enter the menu and activate analog test mode.
AI>01=00
Displays the active analog input (AI>01) and the level (00).
AI>04=00
Press MENU (
) to select the desired analog input to test.
AI>04=FL
Displays the analog input level from off (00) to full-on (FL).
Press ESCAPE or RESET to exit the menu.
22. ANA FLTR
Apply a noise filter on the analog inputs of up to 1 Volt.
High frequency noise can sometimes be induced into the analog input lines. The
analog filter is set in 1% increments where each percent (%) represents 0.1 Volts for
a maximum filter level of 1 Volt, or 10%. For example, when the analog filter level is
set at 5% (LEV:05%) all analog input levels at or below 0.5 Volts is ignored or filtered out.
LEV:00%
Displays the filter level (00%) in percent.
LEV:00%<
Press EXECUTE to enter the menu and adjust the analog filter level.
LEV:10%<
Press MENU (
) to select the desired filter level.
Press ESCAPE to exit the menu and save the desired analog filter level.
Press RESET to exit the menu without saving.
The menu will automatically timeout after 2 minutes of inactivity and save.
23. ANA BLOC
Enable or disable the analog inputs when DMX is being received.
When analog blocking (ANA BLOC) is enabled the analog inputs will be ignored when
DMX is online. When analog blocking is disabled the analog inputs will be merged/
combined with the DMX inputs and functions in a highest-takes-precedence (HTP)
mode of operation.
ENABLED
Press EXECUTE to toggle analog blocking from ENABLED to DISABLED.
DISABLED
Press EXECUTE to toggle analog blocking from DISABLED to ENABLED.
Any change in the configuration is automatically saved.
24. STANDBY
Enable or disable the power savings standby mode.
When standby mode is enabled the microcontroller goes to sleep within 5 seconds
of inactivity on the control inputs. The microcontroller wakes up again when a
programming switch is pressed or when control is sensed on the control inputs. Note
that there is a delay of 150 milliseconds for the microcontroller to wake up and restart
normal run mode.
ENABLED
Press EXECUTE to toggle standby mode from ENABLED to DISABLED.
DISABLED
Press EXECUTE to toggle standby mode from DISABLED to ENABLED.
Any change in the configuration is automatically saved.
25. TEST INC
Set the test increment units to percent or hexadecimal.
The levels for the dimmer test (DIM TEST) and analog test (ANA TEST) features can
be displayed as a percentage or hexadecimal value.
PERCENT
Press EXECUTE to toggle test increments from PERCENT to HEX VAL.
HEX VAL
Press EXECUTE to toggle test increments from HEX VAL to PERCENT.
Any change in the configuration is automatically saved.
26. OC MODE
Configure the input trigger parameters for the open collector output.
The on-board open collector output is used to sink up to 100mA of current. It can be
configured to be triggered via a selected DMX channel, analog input 4, or both. The
open collector is triggered on at 55% control input and triggered off again at 45%
control input. When analog and DMX (A+D) is selected to trigger the open collector
the inputs are combine for highest takes precedence (HTP).
Press EXECUTE to enter the menu and configure the open collector output.