Johnson Controls Ducted Systems
9
Units may be moved or lifted with a forklift. Slotted openings in
the base rails are provided for this purpose.
THE LENGTH OF THE FORKS MUST BE A MINIMUM OF 60
INCHES.
Figure 5: Unit 4 point load weight
Figure 6: Unit 6 point load weight
Figure 7: Center of gravity
If a unit is installed on a roof curb other than a Ducted
Systems roof curb, you must apply gasketing to all
surfaces that come in contact with the unit underside.
Before lifting the unit, make sure that the unit weight is
distributed equally on the rigging cables so that it lifts
evenly.
All panels must be secured in place when the unit is
lifted.
The condenser coils must be protected from rigging
cable damage with plywood or other suitable material.
D
A
C
B
LEFT
FRONT
D
A
C
B
E
F
LEFT
FRONT
X
Y
LEFT
FRONT
Table 3:ZS-06 through -12 weights and dimensions
Size
(tons)
Model
Weight (lbs.)
Center of gravity
4 point load location (lbs.)
6 point load location (lbs.)
Shipping Operating
X
Y
A
B
C
D
A
B
C
D
E
F
-06
(6.5)
ZS
868
863
47.25
24.00
165
186
272
240
108
117
127
185
170
157
-07
(7.5)
ZS
865
860
48.25
25.34
169
200
266
225
110
122
137
182
163
146
-08
(8.5)
ZS
999
994
47.25
24.75
196
221
306
271
128
139
151
209
192
177
-10
(10)
ZS
1051
1046
45.00
25.50
224
229
300
294
148
151
153
201
198
195
-12
(12.5)
ZS
1258
1253
49.75
24.50
229
291
410
323
147
171
202
284
241
207