5566019-BIM-B-1118
30
Johnson Controls Ducted Systems
-10
(10)
208
15.6
110
24
3.03
9.6
5.5
20
None
-
-
-
60.8
66.3
70
80
E18
13.5
2
37.5
71.4
78.3
80
80
E24
18
2
50
87
93.9
90
100
E36
25.5
2
70.8
113
119.9
125
125
E54
40.6
2
112.7
165.4
172.3
175
175
230
15.6
110
24
3.03
9.6
5.5
20
None
-
-
-
60.8
66.3
70
80
E18
18
2
43.3
78.6
85.5
80
90
E24
24
2
57.7
96.6
103.5
100
110
E36
34
2
81.8
126.8
133.6
150
150
E54
54
2
129.9
154.4
161.3
175
175
460
7.8
52
12
1.6
4.7
2.2
20
None
-
-
-
30.5
32.7
35
40
E18
18
2
21.7
39.3
42
40
45
E24
24
2
28.9
48.3
51
50
60
E36
34
2
40.9
63.3
66
70
70
E54
54
2
65
77.1
79.9
90
90
575
5.8
38.9
9
1.35
3.6
1.8
20
None
-
-
-
23.4
25.2
25
30
E18
18
2
17.3
31.1
33.4
35
35
E24
24
2
23.1
38.4
40.6
40
45
E36
34
2
32.7
50.4
52.6
60
60
E54
54
2
52
61.5
63.8
70
70
-12
(12.5)
208
23.1
160
36
3.03
14
5.5
20
None
-
-
-
88.1
93.6
110
110
E18
13.5
2
37.5
88.1
93.6
110
110
E24
18
2
50
92.5
99.4
110
110
E36
25.5
2
70.8
118.5
125.4
125
150
E54
40.6
2
112.7
170.9
177.8
175
200
230
23.1
160
36
3.03
14
5.5
20
None
-
-
-
88.1
93.6
110
110
E18
18
2
43.3
88.1
93.6
110
110
E24
24
2
57.7
102.1
109
110
110
E36
34
2
81.8
132.3
139.1
150
150
E54
54
2
129.9
159.9
166.8
175
175
460
12.2
87
19
1.6
6.6
2.2
20
None
-
-
-
45.5
47.7
50
50
E18
18
2
21.7
45.5
47.7
50
50
E24
24
2
28.9
50.6
53.4
60
60
E36
34
2
40.9
65.6
68.4
70
70
E54
54
2
65
79.5
82.3
90
90
575
8.7
62
14
1.35
5.2
1.8
20
None
-
-
-
34.2
36
40
40
E18
18
2
17.3
34.2
36
40
40
E24
24
2
23.1
40.4
42.6
45
45
E36
34
2
32.7
52.4
54.6
60
60
E54
54
2
52
63.5
65.8
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZS-06 through -12 high static motor - with powered convenience outlet (continued)
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh (amps)
Max fuse
2
/
breaker
3
size (amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA
LRA
MCC
FLA
FLA
FLA
FLA
Model
kW
Stages Amps