SELECTION DATA
TC-16001-rev.5
4-3
(5) Given Condition (Example)
● Estimated Load
Item
Room (1)
Room (2)
Room (3)
Estimated
Cooling Load
Btu/h
11,000
11,000
13,000
(kW)
(3.5)
(3.5)
(4.4)
Estimated
Heating Load
Btu/h
11,400
11,400
13,700
(kW)
(3.3)
(3.3)
(4.2)
(6) Selecting Matching Indoor Units and Nominal Capacity
Equivalent Piping Length between Indoor Units and Outdoor Unit: 200 ft (61m)
Piping Lift: 25 ft (8m)
Power Supply: 60Hz
Select Ducted Medium Type Indoor Units (Example)
Item
Room (1)
Room (2)
Room (3)
Total
Selected Model
HIDM015B21S
HIDM015B21S
HIDM018B21S
(1) ~ (3)
Nominal
Cooling Capacity
Btu/h
15,000
15,000
18,000
48,000
(kW)
(4.4)
(4.4)
(5.3)
(14.1)
Nominal
Heating Capacity
Btu/h
17,000
17,000
20,000
54,000
(kW)
(5.0)
(5.0)
(5.9)
(15.8)
Item
Outdoor Unit
Selected Model
HVAHP240B31S
Nominal
Cooling Capacity
Btu/h
48,000
(kW)
(14.1)
Nominal
Heating Capacity
Btu/h
54,000
(kW)
(15.8)
● Temperature Condition
Cooling
Heating
Outdoor Coil Air Inlet
Outdoor Coil Air Inlet
Dry Bulb:
100
o
F (38
o
C)
Dry Bulb:
37
o
F (2.8
o
C)
Indoor Coil Air Inlet
Wet Bulb:
35
o
F (1.7
o
C)
Dry Bulb:
75
o
F (24
o
C)
Indoor Coil Air Inlet
Wet Bulb:
63
o
F (17
o
C)
Dry Bulb:
68
o
F (20
o
C)
● Altitude Condition: 1000 ft (305m)
Connected Indoor Unit Capacity Ratio = 100%