![Johnson Controls YVAHP036B21S Engineering Manual Download Page 29](http://html.mh-extra.com/html/johnson-controls/yvahp036b21s/yvahp036b21s_engineering-manual_2023242029.webp)
OUTDOOR UNITS
TC-16001-rev.5
2-11
2.9 Electrical Data
Model
Outdoor Unit
INV Comp.
Hz
Voltage
Max.
Min.
MCA
MOP
Max. Fuse
RLA
LRA
[Hz]
[V]
[V]
[V]
[A]
[A]
[A]
[A]
[A]
(H,Y,C)VAHP036B21S
60
208/230
228/253
188/207
31
40
40
24
30
(H,Y,C)VAHP048B21S
60
208/230
228/253
188/207
31
40
40
24
30
(H,Y,C)VAHP060B21S
60
208/230
228/253
188/207
31
40
40
24
30
Model
Fan Motor
Wiring Size
Conduit Tube
Output
FLA
Power Supply
Wiring
Ground Wiring
Communication
Cable
for Power
Supply Wiring
[kW]
[A]
[AWG]
[AWG]
[AWG]
[in. (mm)]
(H,Y,C)VAHP036B21S
0.058+0.058
0.5+0.5
8
8
18
3/4 (19.05)
(H,Y,C)VAHP048B21S
0.058+0.058
0.5+0.5
8
8
18
3/4 (19.05)
(H,Y,C)VAHP060B21S
0.058+0.058
0.5+0.5
8
8
18
3/4 (19.05)
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
RLA: Rated Load Ampacity (A)
LRA: Locked Rotor Ampacity (A)
FLA: Full Load Ampacity (A)