Codes and description
Domestic air conditioner
7.2 Error Codes and Description indoor display
The code indication that is listed above is the main fault
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or else parts damage
may be occurred.
E1: Room temperature sensor failure CN6
E2: Heat-exchange sensor failure CN6
NO
Check the value of the
sensor to see whether the
sensor is damaged or not?
YES
The indoor PCB is broken, replace with new indoor PCB
Sensor is broken,replace it with new sensor
Pull the sensor out of the mainboard
1)
Measure the value of resistance Between its two
jumpers
2)
Measure the temperature at the room temperature
sensing head.
E4 Indoor EEPROM error: Replace the PCB of indoor unit
YSCC/H07/09/12FSAADG
34