background image

JOHNSON CONTROLS

21

SECTION 2 - INSTALLATION

FORM 160.78-N1 

ISSUE DATE: 5/30/2012

2

ing Guide (Form 160.78-EG1) 

for required minimum 

Condenser and Evaporator temperatures. Refer to 

Figure 

8

 for typical water piping schematic.

Stop Valves

Stop valves may be provided (by others) in the evapora-

tor and condenser water piping adjacent to the unit to 

facilitate maintenance. Thermometer wells and pressure 

taps should be provided (by others) in the piping as close 

to the unit as possible to facilitate operating check.

Flow Switches

Thermal type water flow switches are factory mounted 

in the chilled and condensed water nozzles and are fac-

tory wired to the OptiView™ Control Panel. These sol-

id-state flow sensors have a small internal heating ele-

ment and use the cooling effect of the flowing fluid to 

sense when an adequate flow rate has been established.

Waterbox Drain And Vent Valves

Drain and vent valves (by others) should be installed 

in the connections provided in the evaporator and con-

denser liquid heads. These connections may be piped 

to drain if desired.

Checking Piping Circuits And Venting Air

After the water piping is completed, but before any 

water box insulation is applied. Tighten and torque to 

maintain between 30 and 60 ft. lbs. (41 and 81 N·m) 

the nuts on the liquid head flanges. Gasket shrinkage 

and handling during transit cause nuts to loosen. If wa-

ter pressure is applied before tightening is done, the 

gaskets may be damaged and have to be replaced. Fill 

the chilled and condenser water circuits, operate the 

pumps manually and carefully check the evaporator 

and condenser water heads and piping for leaks. Repair 

leaks as necessary.
Before initial operation of the unit both water circuits 

should be thoroughly vented of all air at the high points.

Refrigerant Relief Piping

Each unit is equipped with pressure relief valves lo-

cated on the condenser and on the evaporator for the 

purpose of quickly relieving excess pressure of the re-

frigerant charge to the atmosphere as a safety precau-

tion in case of an emergency, such as fire.
Refrigerant relief vent piping (by others), from the relief 

valves to the outside of the building, is required by code 

in most areas and should be installed on all chillers. The 

vent line should be sized in accordance with the ANSI/

ASHRAE-15, or local code. The vent line must include 

a dirt trap in the vertical leg to intercept and permit clean 

out and to trap any vent stack condensation. The piping 

MUST be arranged to avoid strain on the relief valves, 

using a flexible connection, if necessary.

Unit Piping

Compressor refrigerant piping and system external 

piping are factory installed on all units shipped assem-

bled. On units shipped dismantled, the piping should 

be completed under the supervision of the Johnson 

Controls representative.

Control Wiring

On units shipped disassembled, after installation of the 

control center, control wiring must be completed be-

tween unit components and control center, solid state 

starter, or variable speed drive, when used, using wir-

ing harness furnished. Refer to 

YMC

2

 Field Connec-

tions Manual (Form 160.78-PW1)

Field wiring connections for commonly encountered 

control modifications (by others) if required, are shown 

in the 

YMC

2

 Unit Wiring and Field Control Modifica-

tions Manual (Form 160.78-PW2)

.

No deviations in unit wiring from that 

shown on drawings furnished shall be 

made without prior approval of the John-

son Controls representative.

Power Wiring

DO NOT cut wires to final length or make 

final connections to starter power input 

terminals until approved by the Johnson 

Controls representative.

Supplied Variable Speed Drive.

The factory mounted Variable Speed Drive does not 

require wiring to the compressor motor. The mo-

tor power wiring is factory connected to the Variable 

Speed Drive (refer to the 

YMC

2

 Unit Wiring and Field 

Control Modifications Manual (Form 160.78-PW2))

All wiring to the control panel is completed by the fac-

tory. A control transformer is factory furnished with 

the Variable Speed Drive.

Summary of Contents for YORK YMC2

Page 1: ...LD14000 YMC2 MODEL A WITH OPTIVIEW CONTROL CENTER CENTRIFUGAL LIQUID CHILLERS INSTALLATION Supersedes 160 78 N1 611 Form 160 78 N1 512 R 134a Issue Date May 30 2012...

Page 2: ...s This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in...

Page 3: ...s the technician should verify whether the equipment has been modified and if current litera ture is available from the owner of the equipment prior to performing any work on the chiller CHANGE BARS R...

Page 4: ...Code 4 Heat Exchanger Mod Level Nominal Inside Diameter Inches Nominal Length Feet Marketing Tube Number E A 25 14 271 B R 1 1 F C R COMPRESSOR NOMENCLATURE Gas Path Revision Level Impeller Design Rev...

Page 5: ...rene Isolator Pads 14 Install Optional Spring Isolators 17 Make Connections 19 Piping Connections 19 Refrigerant Relief Piping 21 Unit Piping 21 Control Wiring 21 Power Wiring 21 Supplied Variable Spe...

Page 6: ...Pass Nozzle Arrangements 28 FIGURE 18 Condensers Compact Water Boxes 2 Pass Nozzle Arrangements 28 FIGURE 19 Condensers 150 Psi Compact Water Boxes 29 FIGURE 20 Evaporators Marine Water Boxes 1 Pass...

Page 7: ...cal to enlarge access openings to accommodate the factory assembled unit Chillers that are shipped dismantled MUST be field assembled under the supervision of a Johnson Controls representative but oth...

Page 8: ...1 or 2 below use the YMC2 Unit Re assembly Manual Form 160 78 N2 in conjunction with this installation manual This manual is furnished with all units that are to be field assembled The services of a J...

Page 9: ...y 2 The evaporator condenser shell assembly 3 The Variable Speed Drive VSD 4 Miscellaneous shipped loose items Refrigerant charges are shipped separately Arrangements with the local service office mus...

Page 10: ...parated at the tube sheets and prepared for shipping separately but not skidded All conduit is left on the shells Refrigerant lines between shells are flanged and capped requiring no welding All openi...

Page 11: ...ssembly is mounted with all necessary interconnecting pip ing assembled The complete unit is factory leak tested evacuat ed and shipped charged with R 134A refrigerant The Motor Terminal Box adapter r...

Page 12: ...ion isolation pads or optional spring isolators and brackets Other shipped loose items including piping wa ter temperature controls wiring etc VSD Inhibitor INSPECTION DAMAGE SHORTAGE The unit shipmen...

Page 13: ...s When optional skids are used it may be necessary to remove the skids so riggers skates can be used under the unit end sheets to reduce overall height Each unit has four lifting holes two in each end...

Page 14: ...ping skids are used remove them before lowering the chiller to its mounting position At this point units shipped dismantled should be assembled under the supervi sion of a Johnson Controls representat...

Page 15: ...2 2 UNIT WEIGHT 15 001 29 000 Lbs 6 805 13 154 Kgs LD12641 UNIT WEIGHT UP TO 5 500 Lbs 2 494 Kgs LD12638 UNIT WEIGHT 5 501 8 000 Lbs 2 495 3 628 Kgs LD12639 UNIT WEIGHT 8 001 15 000 Lbs 3 629 6 804 Kg...

Page 16: ...5 30 2012 Section 2 Installation A B C D E D D D LD12642 Figure 4 NEOPRENE ISOLATORS OPERATING UNIT WEIGHT DIM A DIM B DIM C DIM D DIM E 15 001 29 000 Lbs 6 805 13 154 Kgs 62 1575 31 787 31 787 10 254...

Page 17: ...he unit can be lowered onto the floor Level The Unit The longitudinal alignment of the unit should be checked by placing a level on the top center of the evaporator shell under the compressor motor as...

Page 18: ...2012 Section 2 Installation A B C D E F F Figure 6 SPRING ISOLATORS OPERATING UNIT WEIGHT DIM A DIM B DIM C DIM D DIM E DIM F Up to 35 000 Lbs 15 880 Kgs 62 1575 31 787 31 787 6 152 6 7 8 175 5 1 2 1...

Page 19: ...lve should be the type to open on increasing drive coolant temperature fail closed and set for a temperature above dewpoint It can be requested as factory supplied on a chiller order by special quotat...

Page 20: ...s to protect the chiller as well as the pumps tower spray noz zles chilled water coils and controls etc The strainer must be installed in the entering chilled water and con denser liquid line directly...

Page 21: ...rpose of quickly relieving excess pressure of the re frigerant charge to the atmosphere as a safety precau tion in case of an emergency such as fire Refrigerant relief vent piping by others from the r...

Page 22: ...Installation Figure 9 FAA UNIT INSULATION LD03827a Bold lines and shaded components represent insulation HOT GAS LINE SIGHT GLASS CONDENSER EVAPORATOR EVAPORATOR CONDENSER LIQUID LINE HOT GAS CONNECTI...

Page 23: ...5 30 2012 2 Figure 10 FAB UNIT INSULATION LD03827b Bold lines and shaded components represent insulation HOT GAS LINE SIGHT GLASS CONDENSER EVAPORATOR EVAPORATOR CONDENSER LIQUID LINE HOT GAS CONNECTI...

Page 24: ...r the tube maintenance Units are furnished factory anti sweat insulated on or der at additional cost This includes all low tempera ture surfaces except the two 2 cooler liquid heads INSTALLATION CHECK...

Page 25: ...oximate Certified dimensions are available on request 2 Standard water nozzles are Schedule 40 pipe size furnished as welding stub outs with ANSI AWWA C 606 grooves allowing the option of welding flan...

Page 26: ...5 432 2 3 686 0 5 127 NOTE Dimensions are shown in Inches mm 1 Pass Evaporator Nozzle Arrangements In Out Left End Right End Right End Left End Figure 12 EVAPORATORS COMPACT WATER BOXES 1 PASS NOZZLE...

Page 27: ...ts are not furnished 3 One Two and Three pass nozzle arrangements are available only in pairs shown and for all shell codes Any pair of evaporator nozzles may be used in combination with any pair of c...

Page 28: ...841 NOTE Dimensions are shown in Inches mm LD14008 LD14011 LD14010 LD14009 CONDENSER NOZZLE ARRANGEMENTS 150 PSI COMPACT WATER BOXES 1 Pass Condenser Nozzle Arrangements In Out Left End Right End Rig...

Page 29: ...langed nozzles are optional add 13mm to nozzle length Companion flanges nuts bolts and gaskets are not furnished 3 One Two and Three pass nozzle arrangements are available only in pairs shown and for...

Page 30: ...Inches mm Figure 20 EVAPORATORS MARINE WATER BOXES 1 PASS NOZZLE ARRANGEMENTS LD14012 LD14015 LD14014 Figure 22 EVAPORATORS MARINE WATER BOXES 3 PASS NOZZLE ARRANGEMENTS Figure 21 EVAPORATORS MARINE W...

Page 31: ...nal add 13 mm to nozzle length Companion flanges nuts bolts and gaskets are not furnished 4 One two and three pass nozzle arrangements are available only in pairs shown and for all shell codes Any pai...

Page 32: ...1 2 3 AA5 AA5 BB5 EE AA5 BB5 EE CA21 10 254 6 152 6 152 1 3 1 2 394 3 10 1 2 1181 1 5 1 2 445 3 10 1 2 1181 1 4 1 2 419 1 5 1 2 445 3 10 1 2 1181 1 4 1 2 419 CA25 12 305 8 203 6 152 1 3 1 2 394 4 0 1...

Page 33: ...of welding flanges or use of ANSI AWWA C 606 couplings Factory installed class 150 ANSI B16 5 round slip on forged carbon steel with 1 6 mm raised face water flanged nozzles are optional add 13 mm to...

Page 34: ...hipping weight based on Form 1 shipment Refer to product drawings for detailed weight information Table 3 EVAPORATOR MARINE WATER BOX WEIGHTS TO BE ADDED TO STANDARD UNIT WEIGHTS SHOWN ON TABLE 2 EVAP...

Page 35: ...Celsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 5 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons Refrigerant Eff...

Page 36: ...ania USA 17405 1592 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2012 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 78 N1 512 Issue Date May 30 201...

Reviews: