Read Before Installation

Tools/Materials

Use

Notes

Gauge Manifold

Evacuating,refrigerant charging

5.09MPa on the High-pressure side.

Charging Hose

Evacuating, refrigerant charging

Hose diameter larger than the concentional ones.

Refrigerant Recovery Equipment

Refrigerant recovery

Refrigerant Cylinder

Refrigerant charging

Write down the refrigerant type. Pink in color at the top of the cylinder.

Refrigerant Cylinder Charging Port Refrigerant charging

Hose diameter larger than the conventional ones.

Flare Nut

Connecting the unit to piping

Use Type-2 Flare nuts.

Tools/Materials

Use

Notes

Gas leak detector

Detection of gas leaks

The ones for HFC type refrigerant may be used.

Vacuum Pump

Vacuum drying

May be used if a reverse flow check adaptor is attached.

Refrigerant Recovery Equipment

Recovery of refrigerant

May be used if designed for use with R410A.

Flare Tool

Flare machining of piping

Chages have been made in the flare machining dimension.Refer to the next page.

Tools/Materials

Use

Notes

Vacuum Pump with a Check Valve

Vacuum drying

Bender

Bending pipes

Pipe Cutter

Cutting pipes

Torque Wrench

Tightening flare nuts

Only    12.70 (1/2'') and    15.88(5/8'') have a larger flare machining dimension.

Welder and Nitrogen Cylinder

Welding pipes

Refrigerant Charging Meter

Refrigerant charging

Vacuum Gauze

Checking vacuum degree

Tools/Materials

Use

Notes

Charging Cylinder

Refrigerant Charging

Must not be used with R410-type units.

CAUTION

Items to Be Checked

(1). Verify the type of refrigerant used by the unit to be serviced. Refrigerant Type: R410A
(2). Check the symptom exhibited by the unit to be serviced. Look in this service handbook for symptoms relating to the

      refrigerant  cycle.
(3). Be sure to carefully read the safety precautions at the beginning of this document.
(4). If there is a gas leak or if the remaining refrigerant is exposed to an open flame, a noxious gas hydrofluoric acid may

      form. Keep workplace well ventilated.

Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.

Chloride in some types of refrigerants such as R22 will cause the refrigerating machine oil to deteriorate.

Necessary Tools and Materials

Prepare the following tools and materials necessary for installing and servicing the unit.

Necessary tools for use with R410A(Adaptability of tools that are for use with R22 and R407C).
1. To be used exclusively with R410A ( Not to be used if used with R22  or R407C )

2. Tools and materials that may be used with R410 with some restrictions

3. Tools and materials that are used with R22 or R407C that can also be used with R410A

4. Tool and materials that must not used with R410A

Tools for R410A  must be handled with special care, and keep moisture and dust from entering the cycle.

Summary of Contents for YORK YHUJYH024BAR-A-M

Page 1: ...Read this manual before installation and operation Make sure that it is well kept for later reference L A U N A M N O I T A L L A T S N I Outdoor Inverter R410a 50 60HZ YHUJYH 024 060 BAR S A M ...

Page 2: ...Contents English Safety Precautions Read Before Installation Name of Parts Installation Procedure Troubleshooting 3 7 10 11 18 ...

Page 3: ......

Page 4: ...d be checked for any damages If the damaged base is not repaired the unit may fall down and cause accidents When need maintenance and repairment call dealer to handle it Incorrect maintenance and repairment may cause water leak electrical shock and fire hazard Air conditioner can t be installed in the environment with inflammable gases because the inflammable gases near air conditioner may cause f...

Page 5: ...t to run an abnormal cycle and abnormal cycle and cause the unit to burst In the event of a refrigerant gas leak provide adequate ventilation to the room If leaked refrigerant gas is exposed to a heat source noxious gases may form Do not touch the fins on the heat exchanger with bare hands for they are sharp and dangerous Do not try to defeat the safety features of the devices and do not change th...

Page 6: ...oat flares and flange connections Use liquid refrigerant to charge the system Charge the unit with gas refrigerant will cause the refrigerant in the cylinder to change its composition and will lead to a drop in performance Do not use a charging cylinder The use of charging cylinder will change the composition of the refrigerant and lead to power loss Exercise special care when handling the tools A...

Page 7: ...lling draining pipes follow the instructions in the manual and make sure that they properly drain water so as to avoid dew condensation If not installed properly they may cause water leaks and damage the furnishings Do not spray water on the air conditioners or immerse the air conditioners in water Water on the unit presents a risk of electric shock Periodically check the platform on which is plac...

Page 8: ... Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R410 type units CAUTION Items to Be Checked 1 Verify the type of refrigerant used by the unit to be serviced Refrigerant Type R410A 2 Check the symptom exhibited by the unit to be serviced Look in this service handbook for symptoms relating to the refrige...

Page 9: ...ness If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe protrusion is useful Size mm Radial Thickness mm Size inch Type Type O pipes Type 1 2H or Hpipes Piping Materials Types of Copper Pipes Reference The table shows the standards in Japan Using this table as a ...

Page 10: ...oil from flowing back into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degree of vacuum for the vacuum pump Use a pump which reaches 65Pa or below after 5 minutes of operation In addition be sure to use a vacuum pump that has been properly maintained and oiled using the spec...

Page 11: ...inlet Compressor Inside of unit Air inlet Air outlet Compressor Inside of unit Air outlet Air inlet Air outlet Inside of unit Compressor 24K 36K 28K 48K 3 phase 48K 1 phase 60K Air inlet Air outlet Compressor Inside of unit ...

Page 12: ... winter time Place where obstacles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a strong wind Place surrounded at four sides are not suitable for installation A 1m or more of overhead space is needed for the unit Avoid mounting guide louvers to the place where short circuit is a possibility When installing several units secure sufficient suction s...

Page 13: ... Procedure 3 Installation dimension Unit mm 12 580 Installation of Outdoor Unit 447 410 648 180 180 25 948 840 25 1250 948 380 340 25 830 1008 340 580 380 730 630 308 335 860 24K 36K 28K 48K 3 phase 48K 1 phase 60K ...

Page 14: ... Forced fastening without centering may damage the threads and cause a gas leakage Model One way piping length Vertical height difference between indoor and outdoor Install the removed flare nuts to the pipes to be connected then flare the pipes Gas pipe 15 88x1 0mm Liquid pipe Gas pipe 9 52x0 8mm 19 05x1 0mm Liquid pipe 9 52x0 8mm Piping Connection 90 0 5 Pipe diameter Fastening torque N m Liquid...

Page 15: ...e M g additional refrigerant per meter That is Refrigerant charging amount L 5m x 45 g m Air Tightness Test When pressurizing for 24 hours a variation of 1 C in the ambient temperature will cause a variation of 0 01MPa 0 1kg cm 2 g in pressure It shall be corrected during test Check if the pressure drops If the pressure does not drop then pass If the pressure drops then please check the leaking po...

Page 16: ... the inspection of gas leakge No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed the step 6 If it does not stop gas leakage discharge whole refrigerants from the service port After flaring work again and vacuumize fill up prescribed refrigerant from the gas cylinder Detach the charge hose from the service port open liquid stop valve and gas stop va...

Page 17: ... wiring method should be in line with the local wiring standard The power cable and connecting cable should be self provided All the cables shall have got the European authentication certificate During installation when the connecting cables break off it must be assured that the grouding wire is the last one to be broken off The breaker of the air conditioner should be all pole switch and the dist...

Page 18: ...THOUT ON OPERATION WHEN ELECTRIC POWER IS SUPPLIED BE SURE TO EXECUTE OFF OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING This unit has a function of automatic restart system after recovering power stoppage 1 Before starting test run for all Heat pump models Confirm whether the power source breaker main switch of the unit has been turned on for over 12 hrs to energize the crankcase h...

Page 19: ...Troubleshooting 18 ...

Page 20: ...2012 Johnson Controls Inc www johnsoncontrols com AHUJYHAR 130130 Johnson Controls reserve the right to change product features without prior notice ...

Reviews: