FORM 150.66-NM1 (708)
163
JOHNSON CONTROLS
The table below shows the minimum, maximum, and default values.
TABLE 36 – MINIMUM, MAXIMUM AND DEFAULT VALUES
DESCRIPTION
MINIMUM
MAXIMUM
DEFAULT
DE MODIFIER ADDRESS
-1
41943
-1
DE MODIFIER OFFSET
-1
99
-1
P1 BAUD RATE
1200
76800
4800
1200, 4800, 9600, 19200, 38400, 76800, AUTO SELECTABLE
P2 BAUD RATE
1200
57600
1200
1200, 4800, 9600, 19200, 38400, 57600 SELECTABLE
P1, P2 MANUAL MAC ADDRESS
-1
127
-1
P1, P2 PARITY
NONE
IGNORE
NONE
NONE, EVEN, ODD, IGNORE SELECTABLE
P1 PROTOCOL
BACNET
API
BACNET
BACNET, API SELECTABLE
P2 PROTOCOL
TERMINAL
MODBUS CLIENT
API
TERMINAL, MODBUS IO, MODBUS SERVER, API, MODBUS CLIENT SELECTABLE
P1, P2 STOP BITS
1
2
1
RESET REAL TIME ERROR
NO
YES
NO
TABLE 37 – REAL TIME ERROR NUMBERS
ERROR NUMBER (##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED
The table below shows the real time error numbers and a description of each.