SELECTION DATA
4-2
TC-16002-rev.1
TC: Total Capacity
Refer to Outdoor Unit Capacity Tables as the actual performance data affected by indoor and outdoor unit
combinations.
Indoor Air Temp
(
o
F DB)
63
66
68
70
74
77
Outdoor Air
Temp (
o
F WB)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
TC
(MBH)
21
14.1
14.1
14.2
14.2
14.0
13.9
25
14.9
14.9
14.9
14.9
14.7
14.5
29
15.6
15.6
15.6
15.6
15.3
15.1
33
16.3
16.3
16.3
16.3
15.9
15.6
37
17.0
17.0
17.0
17.0
16.5
16.2
41
17.7
17.7
17.7
17.7
17.2
16.8
43
18.1
18.0
18.0
18.0
17.5
17.1
47
18.8
18.7
18.7
18.7
18.0
17.1
51
19.5
19.4
19.4
19.2
18.0
17.1
55
20.4
20.2
19.7
19.2
18.0
17.1
59
20.4
20.2
19.7
19.2
18.0
17.1
21
18.9
18.9
18.9
18.9
18.7
18.5
25
19.8
19.8
19.8
19.8
19.5
19.3
29
20.8
20.7
20.8
20.8
20.4
20.1
33
21.7
21.7
21.7
21.7
21.2
20.8
37
22.7
22.6
22.6
22.6
22.0
21.6
41
23.6
23.6
23.5
23.5
22.9
22.4
43
24.1
24.0
24.0
24.0
23.3
22.8
47
25.0
25.0
24.9
24.9
24.0
22.8
51
26.0
25.9
25.9
25.6
24.0
22.8
55
27.2
26.9
26.3
25.6
24.0
22.8
59
27.2
26.9
26.3
25.6
24.0
22.8
Indoor
Unit
Model
018
024
4.2.2 Heating Capacity
■ 2-Way Cassette: (H,Y,C)IC2018B21S and (H,Y,C)IC2024B21S