VMA1615/1626/1628/1630 VAV Controllers

Installation Guide

Applications

The VMA1615/1626/1628/1630 programmable digital

controllers are designed for Variable Air Volume

(VAV) applications that communicate through the

BACnet

®

 MS/TP or N2 protocol. These Variable

Air Volume Modular Assembly (VMA) controllers

feature combinations of an integral digital pressure

sensor (DPT), a damper actuator, and a 32-bit

microprocessor. The VMA1626 has an actuator

but does not contain a DPT. The VMA1628 model

has a DPT but does not contain an actuator. The

controllers' small package size facilitates quick

field installation and efficient use of space without

compromising high-tech control performance. These

VMA controllers connect easily to the wired and

wireless network sensors for zone and discharge air

temperature sensing.

Switchable Communications
protocols

The 

Metasys

®

 system Field Equipment Controller

(FEC) family controllers and network sensors

communicate using the standard BACnet

®

 protocol,

based on the ANSI/ASHRAE 135-2008. The BACnet

protocol is a standard for ANSI, ASHRAE, and the

International Standards Organization (ISO) for

building controls.
VMA16, VMA18 controllers are BTL-listed as BACnet

Application Specific Controllers (B-ASCs).
The Controller Configuration Tool (CCT) can be used

to switch the Field Bus communications protocol in

supported FEC, FAC, and VMA controllers to be either

the standard BACnet MS/TP or the N2 protocol. All

new controllers use either BACnet MS/TP as the

default communications protocol, or BACnet/IP.

Switchable communications protocols in the MS/

TP models provide a cost-effective upgrade and

modernization path for customers with existing N2

controllers.
The N2-capable FEC Family Controllers can be used

as functional replacements for legacy N2 controllers.

The N2-capable FEC Family Controllers:
• have the input and output (I/O) quantities and

characteristics of the FEC Family Controllers

• must be programmed with CCT, which has similar,

but not identical programming capabilities as

HVACPro, GX9100, GPL, and other legacy tools

• support SA Bus devices
• support WRZ wireless sensors from the controller

using the WRZ-7860 receiver (most models)

• are available in Buy American versions (most

models)

The N2-capable FEC family controllers:
• do not support Zone Bus (for example, TMZ

sensors and M100 actuators) or XT-Bus (System

91) devices (for example, XT, XTM, and XP

modules)

• do not support a wireless connection to the N2

bus

• do not support NxE passthrough

North American Emissions
Compliance

United States

This equipment has been tested and found to comply with the

limits for a Class A digital device pursuant to Part 15 of the FCC

Rules. These limits are designed to provide reasonable protection

against harmful interference when this equipment is operated

in a commercial environment. This equipment generates, uses,

and can radiate radio frequency energy and, if not installed

and used in accordance with the instruction manual, may cause

harmful interference to radio communications. Operation

of this equipment in a residential area may cause harmful

interference, in which case the users will be required to correct

the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements of the

Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte toutes les

exigences du Règlement sur le matériel brouilleur du Canada.

*2410143217K*

Part No.  24-10143-217 Rev. K

2019-10-18

(

barcode f

or factory use only)

MS-VMA1615,MS-VMA1626,MS-VMA

1628,MS-VMA1630

Summary of Contents for VMA1615

Page 1: ...controllers The N2 capable FEC Family Controllers can be used as functional replacements for legacy N2 controllers The N2 capable FEC Family Controllers have the input and output I O quantities and c...

Page 2: ...rminals for input and output wiring and crimping tool for spade mounted terminal blocks Small straight blade screwdriver for securing wires in the terminal blocks 8 mm 5 16 in wrench or 10 mm 3 8 in 1...

Page 3: ...g for information on using the controller coupler 8 Coupler Bolt see Mounting for information on setting the coupler bolt Table 1 VMA1615 1626 1628 1630 Feature Callout Numbers and Descriptions Physic...

Page 4: ...closure mount applications observe these additional guidelines Do not install the controller in an airtight enclosure Mount the controller so that the enclosure walls do not obstruct cover removal or...

Page 5: ...led on VAV boxes The models have either a round shaft up to 13 mm in diameter or a 10 mm square shaft Tighten the square coupler bolt to the shaft using an 8 mm 5 16 in wrench or 10 mm 3 8 in 12 point...

Page 6: ...Communications Bus Technical Bulletin LIT 12011034 VMA terminals and bus ports See for input and output terminal and bus port locations on the controllers Observe the following guidelines when wiring...

Page 7: ...e Table for more information Figure 6 24 VAC supply power terminal block wiring Important Exercise caution while rewiring the power plug when replacing a VMA1610 or VMA1620 controller with a VMA1615 o...

Page 8: ...ice address See Also activate the EOL switch if necessary 5 Connect the controller to 24 VAC Class 2 power Note If you are using the VMA1615 1626 1628 1630 controller with the Wireless Field Bus Syste...

Page 9: ...ive Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 3 INn Binary Input Dry Contact Maintained Mode 1 secon...

Page 10: ...pper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire 183 m 600 ft twisted wire A 0...

Page 11: ...ngs Requirements Recommended cable type 1 1 FC Bus Communications COM Signal Reference Common for bus communications FC BUS 2 2 SHLD Isolated terminal optional shield drain connection 0 6 mm 22 AWG st...

Page 12: ...er commons The 1 models only isolate this terminal from the FC bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 See Table 3 to determine wire size and cable lengths for cables other than the recommen...

Page 13: ...ures in this section for the applicable termination diagrams Table 5 Termination details Type of field device Type of Input Output Termination diagrams Voltage Input External Source UI Voltage Input I...

Page 14: ...ternal Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low External Source CO Note Applies to CO4 and CO5 Analog Output V...

Page 15: ...maging the controller Setting the device address Metasys field controllers are master devices on BACnet MSTP SA or FC Buses Before operating field controllers on a bus you must set a valid and unique...

Page 16: ...R182x Pro Series Wireless Field Bus System Technical Bulletin LIT 12012356 or the ZFR1800 Series Wireless Field Bus System Technical Bulletin LIT 12011295 for more information on device addresses in w...

Page 17: ...connect the 24 VAC supply to the controller 6 Using an SA bus connection download the firmware and controller application file The download process asks to confirm switching the communication protocol...

Page 18: ...C power supply causing protective devices such as breakers or fuses to trip make sure that the power connections on the VMA are not reversed The most common cause of this problem is when the 24 VAC po...

Page 19: ...t connected Correction Connect OCOM terminal of the configurable output to the common of the connected end device Verification 1 Measure the output and verify that it matches the command 2 Disconnect...

Page 20: ...imary to 24 VAC Secondary 40 VA Foot Mount Y65AS 20 32 cm 8 in Primary Leads and 76 2 cm 30 in Secondary Leads Class 2 Y65T42 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 40 VA Hub Mount...

Page 21: ...3 and 128 255 are reserved and not valid field controller addresses Controller Addressing for N2 DIP switch set valid field controller device addresses 1 254 Communications Bus RS 485 selectable betw...

Page 22: ...ing Laboratories BTL Protocol Revision 12 Listed BACnet Advanced Application Controller B AAC The performance specifications are nominal and conform to acceptable industry standard For application at...