Johnson Controls VAV1717 Installation Manual Download Page 6

For 45° and 60° boxes, you must provide hard stops

at both full-closed and full-open damper positions.

When you install the controller at the full-open

position, the controller provides the open stop for

45° and 60° boxes. The closed damper seal pro-

vides the full-closed stop.

Note: 

The integrated actuator has a stroke

time of 60 seconds for 90° of travel. The

stroke time is the amount of time (in seconds)

that it takes the actuator to move from the

fully closed to the fully opened position

or from the fully open to the fully closed

position.

8. Tighten the square coupler bolt to the shaft with an

8 mm (5/16 in.) wrench or 10 mm (3/8 in.) 12-point

socket. Tighten to 10.5 N·m to 11.5 N·m (95 to 105

lb·in).

Note: 

The models have either a round shaft

up to 13 mm in diameter, or a 10-mm square

shaft.

9. Loop the pneumatic tubing that field personnel

supply to include a trap for condensation. Take the

needed length of tubing that field personnel supply

and install, and attach one end to the dual port

fitting on the controller, and attach the other ends

of the tubing to the pressure transducer in the VAV

box application.

Note: 

The controller uses a digital differential

pressure sensor with bidirectional flow

operation. You can connect the high- and low-

pressure DP tubes to either barbed fitting

on the controller. You do not need to make

a specific high- or low-side connection when

you attach the tubing to the barbed fittings

on the controller.

10. Push the 

Manual Override

 button, and turn the

actuator coupling manually to ensure that the

actuator can rotate from full-closed to full-open

positions without binding.

11. Rotate the damper to the full-open position.

 CAUTION

Risk of Property Damage

Rotate the damper to the full-open position
before starting the air handler. Failure to rotate
the damper to the full-open position may result
in damage to the VAV box or ductwork when
the air handler is started.

Wiring

 CAUTION

Risk of Electric Shock

Disconnect the power supply before making electrical

connections to avoid electric shock.

Important: 

Do not connect supply power to the

controller before you finish wiring and before

you check all wiring connections. Short circuits or

improperly connected wires can result in damage to

the controller and void any warranty.

Important: 

Do not exceed the controller electrical

ratings. Exceeding controller electrical ratings can

result in permanent damage to the controller and

void any warranty.

Important: 

Use copper conductors only. Make

all wiring in accordance with local, national, and

regional regulations.

Important: 

Electrostatic discharge can damage

controller components. Use proper electrostatic

discharge precautions during installation, setup, and

servicing to avoid damaging the controller.

For detailed information about configuring and wiring an

FC bus or an SA bus, refer to the 

MS/TP Communications

Bus Technical Bulletin (LIT-12011034)

.

Wiring guidelines

See 

Physical features

 for terminal and bus port locations

on the controller. Observe the following guidelines when

you wire the controller.

Input and output terminals

See 

I/O terminal blocks, ratings and requirements

for information about the functions, ratings, and

requirements for the input and output terminals. See

Cable and wire length guidelines

 for wire sizes and cable

lengths guidelines.
In addition, observe the following guidelines when you

wire inputs and outputs:
• Run all low-voltage wiring and cables separate from

high-voltage wiring.

• Use twisted, insulated, and stranded copper wires for

all input and output cables, regardless of wire size or

the number of wires.

• Shielded cable is not required for input or output

cables. However, it is best practice to use shielded

cables for input and output cables that are exposed to

high electromagnetic or radio frequency noise.

• Cable runs of less than 30 m (100 ft) do not require an

offset in the input and output software setup.

• Cable runs over 30 m (100 ft) may require an offset in

the input and output software setup.

VAV1717 and VAV1732 VAV Controllers Installation Guide

6

Summary of Contents for VAV1717

Page 1: ...ls provide a cost effective upgrade and modernization path for customers with existing N2 controllers For installation and commissioning support and tips for efficient and safe replacement refer to th...

Page 2: ...Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input 0 ohm to 600k ohm qualified sensors 0 ohm to 2k ohm potentiometer RTD 1k Nickel 1k Platinum or A99B Si NTC 10k Type L 10k...

Page 3: ...Callout Description and references 15 SA bus modular port RJ 12 6 pin modular jack see SA bus port 16 LED status indicators see LED states VAV1717 and VAV1732 VAV Controllers Installation Guide 3...

Page 4: ...n see Mounting the controller 7 Controller coupler see Mounting the controller 8 Coupler bolt see Mounting the controller 9 Universal inputs Voltage analog input 0 VDC to 10 VDC Resistive analog input...

Page 5: ...ontroller Mount the controller so that the power transformer and other devices do not radiate excessive heat to the controller To mount the controller complete the following steps 1 Set all the switch...

Page 6: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Important Do not connect supply power to the controller before you finish wiring and b...

Page 7: ...on the SA bus 2 Daisy chained device on the SA bus 3 Cable shield connection 4 Connection to another device on the SA bus TSTAT port The TSTAT port on the face of the controller is an RJ 45 8 position...

Page 8: ...ontroller does not require an earth ground connection However when you need to ground the secondary of the 24 VAC transformer make only one ground connection near the transformer See the following fig...

Page 9: ...n for all Universal IN terminals Note All Universal ICOMn terminals are isolated from all other commons Same as Universal INn OUTn Binary Output 24 VAC Triac Internal Power Sources internal 24 VAC pow...

Page 10: ...BUS SA BUS RJ 12 6 position modular port that provides communications and 15 VDC power for the following devices NS and NSA Series network sensors MAP Gateway 4 2 or later Bluetooth Commissioning Conv...

Page 11: ...tput point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted...

Page 12: ...controller Table 9 Termination diagrams Type of field device Type of input or output Termination diagrams Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered U...

Page 13: ...External Source CO Note Applies to CO4 and CO5 Incremental Control to Actuator Switch Low Externally Sourced CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Swi...

Page 14: ...th Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection Network Stat with Terminals Addressable SA Bus...

Page 15: ...ock at the top of the controller see Physical features Device addresses 4 through 127 are the valid addresses for these controllers on an MS TP FC bus The DIP switch block has eight switches numbered...

Page 16: ...ch to OFF Note When the EOL switch is set to ON the EOL LED on the front of the controller is illuminated Commissioning the controller About this task To commission the controller use the Controller C...

Page 17: ...ries Fan On off heating water valve and variable speed series fan 8 On Off Series Fan Single speed series fan 8 Incr HW Reheat Var Speed Series Fan Incremental heating water valve and variable speed s...

Page 18: ...LED status indicator information for troubleshooting the controllers Note If you experience short circuits in the 24 VAC power supply causing protective devices such as breakers or fuses to trip make...

Page 19: ...nd COM Ensure that no short circuit occurs Note Some installations require the secondary of the transformer to be earth grounded If this is the case verify that the earth ground connection is valid an...

Page 20: ...BCPro Controller Firmware Package Files required for CCT TL MAP1810 0PA Portable MAP Gateway Australia China India Japan Malaysia New Zealand Singapore South Korea Thailand TL MAP1810 0PM Portable MAP...

Page 21: ...er TE730 Analog sensors with occupancy option TSTAT port NSA7000 Network sensors with occupancy option and RH display option NS7000 NS8000 Network sensors with occupancy option CO2 display option and...

Page 22: ...ded between the supervisory controller and the VAV controller SA bus 0 6 mm 22 AWG stranded 4 wire 2 twisted pairs shielded cable recommended from the VAV controller to network sensors and other senso...

Page 23: ...ns consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Repair information If the controller fails to oper...

Page 24: ...anty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license ope...

Reviews: