VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions 

9

See Figure 19 and Figure 20 to wire the applicable 
VA9208-Bxx-3 Series model.

      

Using Conduit

All VA9208 Series Actuators accept 3/8 in. (10 mm) 
trade size flexible metal conduit.

1.

Feed the actuator cables through the field supplied 
conduit.

2.

Push the conduit into the holes in the actuator and 
secure it with the supplied 10-32 x 9/16 in. screws, 
as illustrated in Figure 21. The product label marks 
the position of holes for the screws. Drive the 
screws through the product label in the marked 
positions. Drive the screwhead flush with the plate 
to secure the conduit.

Figure 19:  Control Wiring Diagrams

AC 120 V  60 Hz

L1

N

WHT BLK

2

1

AC 230 V  50/60 Hz

L1

N

BLU BRN

2

1

AC 24 V 50/60
DC 24 V

RED

BLK

2

1

+

-

~

F

IG

:S

_

w

ir

in

g

Figure 20:  Optional Auxiliary Switch Wiring

F

IG

A

X

_

S

W

C

T

H

COM NC

NO

COM

NC

NO

IMPORTANT:

Careful workmanship is required to 

secure flexible metal conduit. Cut the conduit end 
perpendicular to its axis. Insert the cut end into the 
bottom of the holes in the actuator and hold the 
conduit in place while securing it with the screws 
provided. Check a completed installation by pulling 
on the conduit to ensure its retention.

Figure 21:  Adding Flexible Metal Conduit

Summary of Contents for VA9208-BAA-3

Page 1: ...Actuator uniquement pour commander des quipements dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du electric actuator risque de provoquer des blessures o...

Page 2: ...1 A B C D E F G 1 1 4 DN32 All 5 5 32 131 1 1 32 26 1 23 32 44 7 5 32 182 3 15 16 100 11 32 9 1 31 32 50 1 1 2 DN40 All 5 5 16 135 1 9 64 29 1 57 64 48 7 3 8 187 4 21 64 110 11 32 9 2 11 64 55 2 DN50...

Page 3: ...cted to the coil See Figure 2 Figure 3 Spring Return VA9208 Actuated VG1241 VG1245 VG1841 and VG1845 Series Ball Valve with Optional M9000 561 Thermal Barrier Installed Dimensions in mm 3 29 32 99 A B...

Page 4: ...ds 212 F 100 C See the Mounting the Thermal Barrier section for more information Note Proceed to Step 7 if the ball valve linkage is on actuator Side B 3 Remove the linkage from Side A Figure 5 4 Inse...

Page 5: ...tor to Spring Return Port A Coil Closed To mount the actuator to spring return port A coil closed 1 Turn the valve stem to the position outlined in Figure 10 2 Mount optional M9000 561 Thermal Barrier...

Page 6: ...2 3 to 2 7 N m 6 Insert fixed pointer and M4x0 7x83 mm long screw into the Side B actuator hub Direct the arrow on the pointer to 0 Figure 14 7 Install the actuator on the ball valve Figure 15 Tighte...

Page 7: ...o the valve when mounting the actuator to the thermal barrier Note Depending on your application you may position the assembly in any of the four 90 increments on the valve Manual Override Use only th...

Page 8: ...ment lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants porteurs de tensions dangereuses...

Page 9: ...the screws through the product label in the marked positions Drive the screwhead flush with the plate to secure the conduit Figure 19 Control Wiring Diagrams AC 120 V 60 Hz L1 N WHT BLK 2 1 AC 230 V...

Page 10: ...ugh Step 3 Repair Information A number of replacement parts are available see Table 3 for more details If an VA9208 Series Electric Spring Return Actuator fails to operate within its specifications re...

Page 11: ...3 lb in 6 N m Load at 40 F 40 C Life Cycles 60 000 Full Stroke Cycles with 70 lb in 8 N m Load Audible Noise Rating Power On Running 47 dBA at 70 lb in 8 N m Load at a Distance of 39 13 32 in 1 m Powe...

Page 12: ...Electrical Controls for Household and Similar Use and CSA C22 2 No 24 93 Temperature Indicating and Regulating Equipment Europe CE Mark Johnson Controls declares that this product is in compliance wi...

Reviews: