VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions 

11

Auxiliary Switch 
Rating

-xxC Models

Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with Gold 
over Silver Contacts:
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty

Spring Return

Direction is Selectable with Mounting Position of Actuator:
Actuator Face Labeled A is Away from Valve: CCW Spring Return
Actuator Face Labeled B is Away from Valve: CW Spring Return

Rated Torque

Power On
(Running)

70 lb·in. (8 N·m) All Operating Temperatures

Power Off
(Spring Returning)

70 lb·in. (8 N·m) at Standard Operating Temperatures
53 lb·in. (6 N·m) at Extended Operating Temperatures

Rotation Range

Maximum Full Stroke: 95°

Rotation Time for 
90 Degrees of 
Travel

Power On
(Running)

55 to 71 Seconds for 0 to 70 lb·in. (8 N·m) Load, at all Operating Conditions
60 Seconds Nominal at Full Rated Load (0.25 rpm)

Power Off
(Spring Returning)

13 to 26 Seconds for 0 to 70 lb·in. (8 N·m) Load, at Room Temperature
21 Seconds Nominal at Full Rated Load
39 Seconds Maximum with 70 lb·in. (8 N·m) Load, at -4°F (-20°C)
108 Seconds Maximum with 53 lb·in. (6 N·m) Load at -40°F (-40°C)

Life Cycles

60,000 Full Stroke Cycles with 70 lb·in. (8 N·m) Load

Audible Noise 
Rating

Power On
(Running)

<47 dBA at 70 lb·in. (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)

Power On
(Holding)

<20 dBA at a Distance of 39-13/32 in. (1 m)

Power Off
(Spring Returning)

<52 dBA at 70 lb·in. (8 N·m) Load, at a Distance of 39-13/32 in. (1 m)

Electrical 
Connections

Bxx-3 Models

48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG 
(0.85 mm

2

) Conductors and 1/4 in. (6 mm) Ferrule Ends

Auxiliary Switches
(-xxC Models)

48 in. (1.2 m) UL 758 Type AWM Halogen Free Cable with 18 AWG 
(0.85 mm

2

) Conductors and 1/4 in. (6 mm) Ferrule Ends

Conduit Connections

Integral Connectors for 3/8 in. (10 mm) Flexible Metal Conduit

Fluid 
Temperature 
Limits

VG12x1 and VG18x1 
Series

23 to 203°F (-5 to 95°C), Not Rated for Steam Service

VG12x5 and VG18x5 
Series

-22 to 212°F (-30 to 100°C), Not Rated for Steam Service

VG12x5 and VG18x5 
Series with 
M9000-561 Thermal 
Barrier Installed

-22 to 284°F (-30 to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) 
Saturated Steam

Ambient 
Conditions

Standard Operating

-4 to 140°F (-20 to 60°C); 90% RH Maximum, Noncondensing

Extended Operating

-40 to 4°F (-40 to -20°C); 90% RH Maximum, Noncondensing

Storage

-40 to 185°F (-40 to 85°C); 95% RH Maximum, Noncondensing

Enclosure Rating

NEMA 2 (IP54) for all Mounting Directions

VA9208-Bxx-x Series On/Off Electric Spring Return Actuator (Part 2 of 3 )  

Summary of Contents for VA9208-BAA-3

Page 1: ...Actuator uniquement pour commander des quipements dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du electric actuator risque de provoquer des blessures o...

Page 2: ...1 A B C D E F G 1 1 4 DN32 All 5 5 32 131 1 1 32 26 1 23 32 44 7 5 32 182 3 15 16 100 11 32 9 1 31 32 50 1 1 2 DN40 All 5 5 16 135 1 9 64 29 1 57 64 48 7 3 8 187 4 21 64 110 11 32 9 2 11 64 55 2 DN50...

Page 3: ...cted to the coil See Figure 2 Figure 3 Spring Return VA9208 Actuated VG1241 VG1245 VG1841 and VG1845 Series Ball Valve with Optional M9000 561 Thermal Barrier Installed Dimensions in mm 3 29 32 99 A B...

Page 4: ...ds 212 F 100 C See the Mounting the Thermal Barrier section for more information Note Proceed to Step 7 if the ball valve linkage is on actuator Side B 3 Remove the linkage from Side A Figure 5 4 Inse...

Page 5: ...tor to Spring Return Port A Coil Closed To mount the actuator to spring return port A coil closed 1 Turn the valve stem to the position outlined in Figure 10 2 Mount optional M9000 561 Thermal Barrier...

Page 6: ...2 3 to 2 7 N m 6 Insert fixed pointer and M4x0 7x83 mm long screw into the Side B actuator hub Direct the arrow on the pointer to 0 Figure 14 7 Install the actuator on the ball valve Figure 15 Tighte...

Page 7: ...o the valve when mounting the actuator to the thermal barrier Note Depending on your application you may position the assembly in any of the four 90 increments on the valve Manual Override Use only th...

Page 8: ...ment lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants porteurs de tensions dangereuses...

Page 9: ...the screws through the product label in the marked positions Drive the screwhead flush with the plate to secure the conduit Figure 19 Control Wiring Diagrams AC 120 V 60 Hz L1 N WHT BLK 2 1 AC 230 V...

Page 10: ...ugh Step 3 Repair Information A number of replacement parts are available see Table 3 for more details If an VA9208 Series Electric Spring Return Actuator fails to operate within its specifications re...

Page 11: ...3 lb in 6 N m Load at 40 F 40 C Life Cycles 60 000 Full Stroke Cycles with 70 lb in 8 N m Load Audible Noise Rating Power On Running 47 dBA at 70 lb in 8 N m Load at a Distance of 39 13 32 in 1 m Powe...

Page 12: ...Electrical Controls for Household and Similar Use and CSA C22 2 No 24 93 Temperature Indicating and Regulating Equipment Europe CE Mark Johnson Controls declares that this product is in compliance wi...

Reviews: