Johnson Controls VA-77 Series Product Bulletin Download Page 8

8

PB_VA-7700_Electricl Valve Actuators_02 2011

Mounting■instructions

When mounting the actuator on a valve, please follow the 
instructions below:
•  It is recommended that the valves be mounted upright or at 

angles not greater than 90° in an easily accessible location.

•  The actuator must be protected against dripping water, which 

could enter the housing and damage the mechanism or motor.

•  Do not cover with insulating material.
•  Sufficient clearance must be allowed for actuator removal (refer 

to the dimension drawings).

•  The valve must be installed so that the plug seats against the 

flow, as indicated by the arrows on the valve.

WARNING:■These■actuators■are■intended■to■

control■equipment■under■normal■operating■

conditions.■Where■failure■or■malfunction■of■the■

actuator■could■lead■to■an■abnormal■operating■

condition■that■could■cause■personal■injury■or■

damage■to■the■equipment■or■other■property,■

other■devices■(limit■or■safety■controls)■or■

systems■(alarm■or■supervisory■systems)■

intended■to■warn■of■or■protect■against■failure■

or■malfunction■of■the■actuator■must■be■

incorporated■into■and■maintained■as■part■of■the■

control■system.

Wiring■instructions

•  All wiring must be in accordance with local regulations 

and national electrical codes and should be carried out by 
authorised personnel only.

•  Make sure that the line power supply is in accordance with the 

power supply specified on the device. 

•  See also the instructions in paragraph “Application”.

WARNING:■■
Shock■Hazard

• 

Disconnect■the■power■supply■before■wiring■

connections■are■made■to■prevent■personal■

injury.

Equipment■Damage■Hazard

• 

Make■and■check■all■wiring■connections■before■

applying■power■to■the■system.■Short■circuited■

or■improperly■connected■wires■may■result■in■

permanent■damage■to■the■unit.

Summary of Contents for VA-77 Series

Page 1: ...des Enables sequence control Magnetic clutch Provides constant output force for close off of valves and protects motor in stall conditions Control Signal failure stem to pre determined position Actuat...

Page 2: ...ectrical and Mechanical VA 7746 8201 24 VAC Electrical and Mechanical These actuators can be combined with the following valve ranges VG7000 Series Threaded Valves Female and male threaded valves Thes...

Page 3: ...ranges The standard control signals are selected by setting DIP switches 3 and 4 switch see paragraph DIP switch settings It is recommended to set the actuator to the desired control signal and actio...

Page 4: ...um and the maximum control signal values are stored in the memory of the actuator When the auto calibration cycle is completed the LED stop flashing the actuator stem moves to the position that corres...

Page 5: ...VDC 3 0 10 VDC 4 4 3 5 10 VDC 5 4 6 Direct Acting mode 3 Free Range 7 Electrical manual override off 4 8 Signal failure position pre set Up 5 0 20 mA 5 4 20 mA 6 Action 6 DA 6 RA 7 Electrical Manual...

Page 6: ...nd the LED indicate a general alarm code If the problem is cleared however the actuator continues normal function Fault mode If the actuator enters fault mode the LED will flash as shown The indicatio...

Page 7: ...tion The controller 0 10 V output can operate several actuators with built in electronic positioner The number of actuators that can be linked to a single controller depends on the controller s active...

Page 8: ...d lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property other devices limit or safety controls or systems alarm or supervisory systems i...

Page 9: ...g models 230 VAC supply VA 7746 xx01 Proportional models 24 VAC supply WARNING Equipment Damage Hazard On 24 V models with manual override it is not permitted to connect voltages greater than 24 V to...

Page 10: ...ors_02 2011 VA 7700 xx01 Floating models 24 VAC supply VA 7700 xx03 Floating models 230 VAC supply VA 7706 xx01 Proportional models 24 VAC supply Wiring Diagrams Models without mechanical manual overr...

Page 11: ...11 PB_VA 7700_Electricl Valve Actuators_02 2011 Dimensions in mm VA 77xx 82xx 87 90 VA 77xx 10xx A 25 mm VA 770x actuators without manual override A 80 mm VA 774x actuators with manual override...

Page 12: ...250 0 4 20 mA Resolution 0 5 up to 200 steps on 20 mm stroke Feedback ratings max 2mA at 0 10 VDC 5 k Manual contact micro switch max load 2A Resistive 1A Inductive 24 VAC 24 V switch 2A Resistive 1A...

Reviews: