Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and Part Number 

(P/N).

Model WS HSW Window Sprinkler 

with NPT Thread

Specify: Model WS Specific Appli-

cation Window Sprinkler TY3388, 

Horizontal Sidewall, with (specify) tem-

perature rating, (specify) finish, and 

P/N (specify):

155 °F (68 °C)

Natural Brass  . . . . . . . . . . . . . . . .  50-305-1-155

Signal White (RAL9003)

Polyester . . . . . . . . . . . . . . . . . . . . 50-305-4-155

Jet Black (RAL9005)

Polyester . . . . . . . . . . . . . . . . . . . . 50-305-5-155

Chrome Plated  . . . . . . . . . . . . . . . 50-305-9-155

200 °F (93 °C)

Natural Brass  . . . . . . . . . . . . . . . . 50-305-1-200

Signal White (RAL9003)

Polyester . . . . . . . . . . . . . . . . . . . . 50-305-4-200

Jet Black (RAL9005)

Polyester . . . . . . . . . . . . . . . . . . . . 50-305-5-200

Chrome Plated  . . . . . . . . . . . . . . . 50-305-9-200

Model WS Pendent Vertical 

Sidewall Window Sprinkler 

with NPT Thread

Specify: Model WS Specific Application 

Window Sprinkler TY3488, Pendent 

Vertical Sidewall, with (specify) tem-

perature rating, (specify) finish, and 

P/N (specify):

155 °F (68 °C)

Natural Brass  . . . . . . . . . . . . . . . .  50-304-1-155

Signal White (RAL9003)

Polyester . . . . . . . . . . . . . . . . . . . . 50-304-4-155

Jet Black (RAL9005)

Polyester . . . . . . . . . . . . . . . . . . . . 50-304-5-155

Chrome Plated  . . . . . . . . . . . . . . . 50-304-9-155

200 °F (93 °C)

Natural Brass  . . . . . . . . . . . . . . . . 50-304-1-200

Signal White (RAL9003)

Polyester . . . . . . . . . . . . . . . . . . . . 50-304-4-200

Jet Black (RAL9005)

Polyester . . . . . . . . . . . . . . . . . . . . 50-304-5-200

Chrome Plated  . . . . . . . . . . . . . . . 50-304-9-200

Sprinkler Wrench

Specify: W-Type 20 Sprinkler Wrench, 

P/N 56-000-1-106

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

INSTALLATION NOTE:

SHOWN ON ONE SIDE OF

GLASS WINDOW

GLAZING FOR CLARITY

INSTALL VERTICAL AND

DO NOT PLACE BLINDS,

WINDOW COVERINGS

NONOPERABLE

AND GLAZING

BETWEEN SPRINKLER

TYPICAL

COVERING

WINDOW

CEILING SPACES.

CURTAINS OR OTHER

WS SPRINKLERS

INTO RECESSED

HORIZONTAL MODEL

MODEL WS SPRINKLER

WINDOW

FRAME

SPACE

CEILING

RECESSED

BUILDING

STRUCTURE

FOR GLASS TYPES

OTHER THAN FIRELITE

PLUS WS CERAMIC GLASS

BY TGP, ALL COMBUSTIBLE

MATERIALS SHALL BE

KEPT 2" (50,8 mm) MINIMUM

FROM SPRINKLERED FACE

OF GLAZING. THIS MAY BE

DONE THROUGH USE OF

MINIMUM 3'-0" (0,9 m)

PONY WALL

WRENCH RECESS
(USE END "A" FOR

MODEL WS)

FIGURE 3E 

MODEL WS PENDENT VERTICAL SIDEWALL SPRINKLER 

RECESSED CEILING TYPICAL INSTALLATION

FIGURE 4 

W-TYPE 20 SPRINKLER 

WRENCH

Summary of Contents for tyco WS

Page 1: ...nklers is based on their fast response thermal sensitivity and on their specially designed deflectors that ensure that the spray pattern wets the entire surface of the window Based on successful testing the Model WS Window Sprinklers can be used as interior protection of windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Mat...

Page 2: ...ulb allowing the sprinkler to activate and water to flow Temperature 1 5 8 DIA 41 3 mm NPT WATERWAY OF SPRINKLER CENTERLINE NOMINAL MAKE IN 7 16 11 1 mm Screw Deflector 6 THREAD 1 2 RELIEF Components Button Sealing Compression Frame Assembly 1 5 4 2 3 Bulb 54 0 mm FLATS WRENCH 2 1 8 WINDOW 20 6 mm 13 16 TOWARDS DEFLECTOR ORIENT INDICATED TOP DEFLECTOR OF SPRINKLER SPRINKLER FRAME ARMS 1 2 3 4 5 6 ...

Page 3: ...parated by a baffle or mullion of sufficient depth to act as a baffle A mullion will act as a baffle when in the case of the Pendent Vertical Side wall the mullion extends to the back of the sprinkler deflector and in the case of the Horizontal Sidewall the mullion extends to the sprinkler wrench flat Refer to Figures 3B 1 and 3B 2 Minimum Distance from Standard Sprinklers 6 ft 1 83 m unless separ...

Page 4: ...or sprinkler spacing less than 6 ft 1 83 m Maximum Pressure per Sprinkler Horizontal Sidewall 70 psi 4 83 bar The 70 psi is only for cold solder purposes If there is a baffle or a mullion of sufficient depth to act as a baffle separating the sprinklers the maximum pressure is 175 psi 12 07 bar Vertical Sidewall 175 psi 12 07 bar When acceptable to the Authority Having Jurisdiction the Model WS Spe...

Page 5: ...indow Sprinklers is 6 0 baffle by a baffle or mullion of MULLION MINIMUM SPRINKLER MODEL WS OR VERTICAL HORIZONTAL 0 4 101 6 mm MINIMUM 4 0 1 22 m MAXIMUM 8 0 2 44 m MAXIMUM when intermediate horizontal Window Sprinklers are NOT listed to protect windows mullions are present MULLION WS SPRINKLER VERTICAL MODEL INTERMEDIATE MULLION HORIZONTAL OR FIGURE 3B B 1 TO B 3 WINDOW MULLIONS AND BUTT JOINTS ...

Page 6: ...sition with the center line of the sprinkler per pendicular to the glass surface Orient the sprinkler so that the word Top indicated on the sprinkler deflector is facing the top of window frame Step 3 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 With reference to Figures 1 or 2 apply End A of W Type 20 Sprinkler Wrench only Figur...

Page 7: ...m its bulb Refer to the Instal lation section for additional information The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards recognized by the Approval agency e g NFPA 25 in addition to the stan dards of any authorities having jurisdic tion Contact the installing co...

Page 8: ...fy Model WS Specific Application Window Sprinkler TY3488 Pendent Vertical Sidewall with specify tem perature rating specify finish and P N specify 155 F 68 C Natural Brass 50 304 1 155 Signal White RAL9003 Polyester 50 304 4 155 Jet Black RAL9005 Polyester 50 304 5 155 Chrome Plated 50 304 9 155 200 F 93 C Natural Brass 50 304 1 200 Signal White RAL9003 Polyester 50 304 4 200 Jet Black RAL9005 Pol...

Reviews: