Page 6 of 8

Installation

The TYCO Model WS Specific Appli-

cation Window Sprinklers must be 

installed in accordance with this 

section.

General Instructions

Do not install any bulb-type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in. (1,6 

mm).
A leak-tight 1/2 in. NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum  torque of 7 to 14 

ft-lb (9,5 to 19,0 N

m). Higher levels of 

torque may distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.

Step 1.

 Install the pendent vertical 

sidewall sprinkler only in the pendent 

position with the center-line of the 

sprinkler parallel to the glass surface. 

Orient the sprinkler so that the direc-

tion of flow indicated on the sprinkler 

deflector is facing the window.

Step 2.

 Install the horizontal sidewall 

sprinkler only in the horizontal position 

with the center-line of the sprinkler per-

pendicular to the glass surface. Orient 

the sprinkler so that the word “Top” 

indicated on the sprinkler deflector is 

facing the top of window frame.

Step 3.

 With pipe-thread sealant 

applied to the pipe threads, hand-

tighten the sprinkler into the sprinkler 

fitting.

Step 4.

 With reference to Figures 1 or 

2, apply End A of W-Type 20 Sprinkler 

Wrench only (Figure 4) to the sprinkler 

wrench flats and tighten the sprinkler 

into the sprinkler fitting.

INSTALLATION NOTE:

STRUCTURE

BUILDING

MODEL WS SPRINKLER

GLAZING FOR CLARITY

SHOWN ON ONE SIDE OF

2" (50,8 mm)

± 1" (25,4 mm)

NO MAXIMUM

DISTANCE

FOR GLASS TYPES

OTHER THAN FIRELITE

PLUS WS CERAMIC GLASS

BY TGP, ALL COMBUSTIBLE

MATERIALS SHALL BE

KEPT 2" (50,8 mm) MINIMUM

FROM SPRINKLERED FACE

OF GLAZING. THIS MAY BE

DONE THROUGH USE OF

MINIMUM 3'-0" (0,9 m)

PONY WALL

NON-OPERABLE
GLASS WINDOW

TO GLAZING

1/2" (12,7 mm)

TO 4" (101,6 mm)

ALIGNED VERTICALLY

DEFLECTOR FACING

AND PARALLEL

AND MARKED SIDE OF

WITH FRAME ARMS

POSITION SPRINKLER

MAXIMUM

NO

HEIGHT

(3,96 m)

GLAZING

MAXIMUM

EXPOSED

HEIGHT

13'-0"

FRAME

WINDOW

SPRINKLER DEFLECTOR

INDICATED ON

"TOP"

FIGURE 3C 

MODEL WS HORIZONTAL SIDEWALL SPRINKLER 

TYPICAL INSTALLATION

Summary of Contents for tyco WS

Page 1: ...nklers is based on their fast response thermal sensitivity and on their specially designed deflectors that ensure that the spray pattern wets the entire surface of the window Based on successful testing the Model WS Window Sprinklers can be used as interior protection of windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Mat...

Page 2: ...ulb allowing the sprinkler to activate and water to flow Temperature 1 5 8 DIA 41 3 mm NPT WATERWAY OF SPRINKLER CENTERLINE NOMINAL MAKE IN 7 16 11 1 mm Screw Deflector 6 THREAD 1 2 RELIEF Components Button Sealing Compression Frame Assembly 1 5 4 2 3 Bulb 54 0 mm FLATS WRENCH 2 1 8 WINDOW 20 6 mm 13 16 TOWARDS DEFLECTOR ORIENT INDICATED TOP DEFLECTOR OF SPRINKLER SPRINKLER FRAME ARMS 1 2 3 4 5 6 ...

Page 3: ...parated by a baffle or mullion of sufficient depth to act as a baffle A mullion will act as a baffle when in the case of the Pendent Vertical Side wall the mullion extends to the back of the sprinkler deflector and in the case of the Horizontal Sidewall the mullion extends to the sprinkler wrench flat Refer to Figures 3B 1 and 3B 2 Minimum Distance from Standard Sprinklers 6 ft 1 83 m unless separ...

Page 4: ...or sprinkler spacing less than 6 ft 1 83 m Maximum Pressure per Sprinkler Horizontal Sidewall 70 psi 4 83 bar The 70 psi is only for cold solder purposes If there is a baffle or a mullion of sufficient depth to act as a baffle separating the sprinklers the maximum pressure is 175 psi 12 07 bar Vertical Sidewall 175 psi 12 07 bar When acceptable to the Authority Having Jurisdiction the Model WS Spe...

Page 5: ...indow Sprinklers is 6 0 baffle by a baffle or mullion of MULLION MINIMUM SPRINKLER MODEL WS OR VERTICAL HORIZONTAL 0 4 101 6 mm MINIMUM 4 0 1 22 m MAXIMUM 8 0 2 44 m MAXIMUM when intermediate horizontal Window Sprinklers are NOT listed to protect windows mullions are present MULLION WS SPRINKLER VERTICAL MODEL INTERMEDIATE MULLION HORIZONTAL OR FIGURE 3B B 1 TO B 3 WINDOW MULLIONS AND BUTT JOINTS ...

Page 6: ...sition with the center line of the sprinkler per pendicular to the glass surface Orient the sprinkler so that the word Top indicated on the sprinkler deflector is facing the top of window frame Step 3 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 4 With reference to Figures 1 or 2 apply End A of W Type 20 Sprinkler Wrench only Figur...

Page 7: ...m its bulb Refer to the Instal lation section for additional information The owner is responsible for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards recognized by the Approval agency e g NFPA 25 in addition to the stan dards of any authorities having jurisdic tion Contact the installing co...

Page 8: ...fy Model WS Specific Application Window Sprinkler TY3488 Pendent Vertical Sidewall with specify tem perature rating specify finish and P N specify 155 F 68 C Natural Brass 50 304 1 155 Signal White RAL9003 Polyester 50 304 4 155 Jet Black RAL9005 Polyester 50 304 5 155 Chrome Plated 50 304 9 155 200 F 93 C Natural Brass 50 304 1 200 Signal White RAL9003 Polyester 50 304 4 200 Jet Black RAL9005 Pol...