background image

TFP700

Page 4 of 4

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association

1400 Pennbrook Parkway, Lansdale, PA 19446 | Tel1-215-362-0700

© 2021 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

•  Any time copper piping is used in 

any part of a fire sprinkler system, 

the copper piping must be installed 

in conformance with all applica-

ble standards and requirements 

for copper piping, including: NFPA 

13, 13D, 13R and 25, ASTM B813, 

ASTM B828, and Copper Develop-

ment Association (CDA). Any solder-

ing in any part of a sprinkler system, 

either internally or externally, must 

be done with use of only an ASTM B 

813 approved flux. Residual flux must 

be thoroughly REMOVED from both 

the interior and exterior surfaces of 

the piping before installing the sprin-

kler heads. The use of improper flux, 

or the failure to thoroughly remove 

proper flux, may result in corrosion of 

the sprinkler head or stress cracking, 

which in turn may cause the sprin-

klers heads to develop leaks, oper-

ate unexpectedly, or not operate 

properly.

•  Do not allow solvent cement from 

CPVC piping installation to get into 

the bore of the sprinkler. Dried sol-

vent cement can negatively affect the 

operation of the sprinkler by prevent-

ing the flow of water, increasing the 

activation pressure of the sprinkler, 

and causing deterioration of the seal 

from solvent and chlorine attack.

•  Use di-electric unions when installing 

sprinklers in systems that utilize both 

copper and steel piping as galvanic 

reactions can occur due to dissimilar 

nature of the metals causing leakage 

and performance concerns with the 

metallic components installed into 

the system.

•  Dry Type Sprinklers must be installed 

in the appropriately sized outlet 

or run of malleable or ductile iron 

threaded tee fittings that meet the 

dimensional requirements of ANSI 

B16.3 or cast iron threaded tee fit-

tings that meet the dimensional 

requirements of ANSI B16.4 with 

the end sprinkler fitting on a branch 

line to be plugged. Failure to use the 

appropriate fitting may result in: fail-

ure of the sprinkler to properly oper-

ate due to formation of ice over the 

inlet Plug or binding of the inlet Plug; 

or, insufficient engagement of the 

inlet pipe threads with consequent 

leakage.

•  Branch, cross, and feedmain piping 

connected to Dry Type Sprinklers 

and subject to freezing tempera-

tures must be pitched for drainage 

in accordance with the minimum 

requirements of the National Fire 

Protection Association for dry pipe 

sprinkler systems. Failure to appro-

priately pitch the system piping for 

drainage can result in ice formation 

at the Dry Type Sprinkler Inlet that 

may cause the sprinkler to fail to acti-

vate in a fire or cause the sprinkler to 

activate prematurely.

•  When Dry Type Sprinklers are to be 

used in wet pipe sprinkler systems 

protecting areas subject to freezing 

temperatures (e.g., sprinkler drops 

into freezers), consideration must 

be given to the appropriate length of 

the sprinkler that will prevent freezing 

of the water in the connecting pipes 

due to conduction. When the tem-

perature surrounding the wet pipe 

sprinkler system is maintained at a 

minimum temperature of 40°F (4°C), 

the following are the minimum rec-

ommended lengths between the face 

of the sprinkler fitting and the out-

side surface of the protected area 

(that is, lengths exposed to a min-

imum ambient temperature of 40°F 

(4°C): 12 inches (300 mm) when the 

temperature within the protected 

area is -20°F (-29°C); 18 inches (450 

mm) when the temperature within the 

protected area is -40°F (-40°C); and 

24 inches (600 mm) when the tem-

perature within the protected area 

is -60°F (-51°C). For protected area 

temperatures between those given 

above, the minimum recommended 

length from the face of the fitting to 

the outside of the protected area 

may be determined by interpolating 

between the indicated values. Fail-

ure to provide sufficient length may 

cause the sprinkler to fail to activate 

in a fire or cause the sprinkler to acti-

vate prematurely.

•  When Dry Type Sprinklers penetrate 

a ceiling or wall into an area sub-

ject to freezing, the clearance space 

around the Sprinkler Casing must be 

completely sealed in order to pre-

vent the leakage of moist air into the 

freezing area which might result in 

the formation of condensate around 

the Frame, Deflector, Bulb Seat, or 

Bulb. Failure to prevent the forma-

tion of condensate could result in 

the build-up of ice around the releas-

ing components. This could result in 

inadvertent operation of the sprinkler 

or impaired operation due to reduced 

thermal sensitivity.

•  For additional information on the use 

of sprinklers, refer to the “Product 

Packaging Sheet’ that is enclosed 

separately.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Reviews: