background image

TFP700

Page 2 of 4

Cautions must be understood by all dis-

ciplines (for example, sprinkler fitters, 

designers, authorities having jurisdic-

tion, and material handlers) involved 

with the installation of automatic sprin-

klers. Care must be exercised during 

installation, and the following guide-

lines must be followed to ensure that 

the sprinkler will operate properly:
•  Store sprinklers properly and shield 

them from extreme heat. Do not 

store sprinklers in direct sunlight or 

in areas of vehicles that are subject. 

to extreme temperatures. Over-

heating will damage the sprinkler 

by weakening the thermal sens-

ing element resulting in premature 

activation.

•  Sprinkler cartons are specially 

designed to protect the sprinkler 

during transit. Do not empty sprin-

klers from their cartons into bags or 

buckets prior to installation, since 

damage to the sprinklers may result. 

Install the sprinklers directly from 

their cartons.

•  Unless otherwise modified by 

NATIONAL FIRE PROTECTION 

STANDARDS (NFPA) such as 

NFPA 13 “Installation of Sprin-

kler Systems”, sprinkler temper-

ature ratings shall be as follows: 

Maximum 

Ceiling 

Temperature, 

°F (°C)

Sprinkler 

Temperature 

Rating, 

°F (°C)

100 (38)

135-170 (57-77)

150 (66)

175-250 (79-107)

225 (107)

250-300 (121-149)

300 (149)

325-375 (163-191)

375 (191)

400-475 (204-246)

475 (246)

500-575 (260-302)

625 (329)

650 (343)

TABLE A 

TEMPERATURE 

RATINGS

Over-heating will damage the sprin-

kler by weakening the thermal sens-

ing element resulting in premature 

activation.

•  Do not install any sprinkler that 

shows signs of damage. Immediately 

replace all sprinklers that are dam-

aged during installation.

•  Inspect glass bulb sprinklers at the 

time of installation to make sure that 

the bulb contains fluid. Inspection of 

the glass bulb is to be made with the 

sprinkler strap in place by looking 

through the openings of the sprin-

kler strap.
Any glass bulb that shows evidence 

of leakage or that does not have 

any fluid must be discarded. Do not 

install any bulb type sprinkler if the 

bulb is cracked or there is a loss of 

liquid from the bulb. With the sprin-

kler held horizontally, a small air bub-

ble should be present. The diameter 

of the air bubble is approximately 

1/16 inch (1,6 mm) for the 135°F 

(57°C) to 3/32 inch (2,4 mm) for the 

360°F (182°C) temperature ratings. 

Loss of liquid from a bulb can cause 

the sprinkler to fail to activate in a 

fire. Install sprinklers in fittings with 

the pipe ‘in place’. Sliding piping 

through structural members with the 

sprinklers in place can severely dam-

age sprinklers.

•  Do not apply any thread roughen-

ing process to the sprinkler thread. 

Application of this effect can cause 

distortion of the frame, which may 

result in leakage or damage to the 

actuation mechanism.

•  When starting the thread of a  sprin-

kler, do not over-tighten by hand. 

Excessive tightening by hand can 

cause damage to the thermal sens-

ing element without knowledge to the 

installer.

•  Always wrench tighten the sprinklers 

with the sprinkler wrench specified 

for use with the specific sprinkler 

being installed. Using the wrong 

wrench can damage the sprinkler.

•  Apply sprinkler wrenches to the 

proper sprinkler wrench boss/flats 

only. Do not allow the sprinkler 

wrench to slip during the wrench 

tightening procedure. Wrenching 

the sprinkler frame arms, deflector, 

or thermal sensing element, and/or 

wrench slippage, will severely dam-

age the sprinkler.

•  Do not over-tighten (maximum torque 

is as follows: 1/2” NPT/14 ft.-lbs.; 3/4” 

NPT/20 ft.-lbs.; 1” NPT/30 ft.-lbs.). 

Over-tightening can distort the sprin-

kler inlet causing leakage or inability 

of the sprinkler to operate properly.

•  Do not attempt to make-up for insuf-

ficient adjustment in the escutcheon 

plate by under- or over-tightening the 

sprinkler. Over-tightening can distort 

the sprinkler inlet causing leakage or 

inability of the sprinkler to operate 

properly. Under-tightening can result 

in pipe thread leakage. Relocate the 

position of the sprinkler, as neces-

sary, to facilitate the adjustment pro-

vided by the escutcheon.

•  Do not remove protective devices (for 

example, sprinkler straps or protec-

tive caps for concealed type sprin-

klers) until the water supply, either 

temporary or permanent, is made 

available to the sprinklers for pur-

poses of fire protection. Failure to 

maintain the protective devices 

where provided may allow damage to 

occur to the thermal sensing element 

with increasing risk of the sprinkler 

failing to activate in a fire or causing 

the sprinkler to activate prematurely.

Note

: For upright sprinklers and sprin-

klers installed more than 10 ft. (3,1 m) 

above the floor, protective devices (for 

example, sprinkler straps or  protec-

tive caps for concealed type sprin-

klers) are permitted to be removed 

from the sprinklers immediately fol-

lowing their installation. (Where instal-

lation of mechanical services or other 

construction work is expected to take 

place following the installation of sprin-

klers, consideration should be given to 

leaving protective devices in place until 

such time as the water supply is made 

available to the sprinklers for purposes 

of fire protection.)
•  After a protective device (for exam-

ple, sprinkler straps or protective 

caps for concealed type sprinklers) 

is removed, inspect glass bulb sprin-

klers to make sure that the bulbs 

contain fluid, and inspect fusible sol-

der type sprinklers for damage to the 

fusible element and associated link 

assembly parts.
Any sprinkler having a glass bulb 

that shows evidence of leakage or 

that does not have any fluid must 

be replaced, and any sprinkler that 

shows evidence of damage to the 

fusible element and associated link 

assembly parts must be replaced.

•  Sprinklers cannot operate properly 

with protective devices in place (for 

example, sprinkler straps or protec-

tive caps for concealed type sprin-

klers). As applicable, refer to the 

“Sprinkler Strap Instructions” pro-

vided in this data sheet.

•  Sprinklers that are found to be leak-

ing or exhibiting visible signs of cor-

rosion must be replaced. Leakage 

and/or corrosion may cause the 

sprinkler to fail to activate in a fire, 

and corrosion may cause the sprin-

kler to activate prematurely.

•  Automatic sprinklers (including cover 

plates of concealed type sprin-

klers) must never be painted, plated, 

coated or otherwise altered after 

leaving the factory. Painted, coated, 

or otherwise altered sprinklers may 

interfere with the sprinkler’s ability to 

operate in a fire. Modified sprinklers 

must be replaced.

•  After a fire, bulb type sprinklers that 

have been exposed to corrosive 

products of combustion, but have 

not operated, should be replaced if 

they cannot be completely cleaned 

by wiping the sprinkler with a cloth 

or by brushing it with a soft bristle 

brush.

Reviews: