Section 4: Configuration
If the keypad is inactive for more than 30 seconds, it reverts to its assigned partition.
Global zones
If a zone is added to more than one partition, it becomes a global zone. A global zone is only armed when all assigned partitions are
armed and is disarmed when any assigned partition is disarmed.
Global zones behave as follows:
l
A global Stay/Away type zone is not activated until all partitions the zone is assigned to are armed in the Away mode. Interiors
must be activated on all partitions for the global Stay/Away zone to be active.
l
A shared zone bypassed on one partition is bypassed on all partitions the zone is assigned to.
l
An entry delay started on a global zone sounds an entry delay on all keypads assigned to partitions the global zone is
assigned to.
l
A global Delay type zone follows the longest programmed delay time of the partitions it is assigned to.
Fire and CO zone types
Fire zones only place the partition they are assigned to into alarm. Other partitions retain their current state.
A fire reset only resets partitions they are assigned to.
One or more fire zones may be located on any partition.
On alarm, the fire auto-scroll display appears on all partition keypads and on all global keypads. Fire alarm silence and fire system
reset may be done directly on any partition keypad. To silence a fire or CO alarm from a global keypad requires that the global
keypad be loaned to one of the partitions the zone is assigned to.
Bell/PGM support
PGMs must be assigned to one or more partitions. See section [007] for partition assignment.
Note:
Bell PGM type requires supervision and follows arming squawks by partition.
Communications
Account codes are assigned to all system and partition events.
For SIA communications, a single account code (programmed in section [310][000]) is used for all events. The partition is identified
via Nri1-8. System events use Nri0.
When using CID communication, individual account codes must be programmed for each partition.
Assign zones
Partition zone assignments are completed using sections [201] - [232] for partitions 1 to 32. Subsections [001 - 032] are used to
enable or disable groups of 8 zones on the partition.
Assign users
Access [*][5] using the master code, select the desired user code and enter digit 4 to modify the partitions that can accept the user
code.
Factory defaults
The alarm panel and individual modules can be returned to factory default settings using the following Installer Programming
sections:
l
[991] Default Keypads
l
000 – Default all keypad programming
l
001-032 – Default keypads 1 to 32
l
[993] Default alternate communicator
l
[996] Default wireless receiver
l
[998] Default HSM2955
l
[999] Default system
See
for more information.
Default all labels
Use programming section [000][999]. The following labels are returned to factory default settings: