Section 6: Programming
201 – 231 Zone Follower Zones 1-248
01 – True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
02 – Timed Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
09-16 – Zone Terminals 1-8
ON: zones associated with terminals 1-8 are enabled for zone follower operation.
OFF: zones are not enabled for zone follower operation.
[011] PGM Configuration Options
This section is used to configure PGM types that offer multiple options.
[001]-[324] Select PGM
The following options may be selected for each PGM:
Zone Follow PGM By Zone
This option is used to specify the zone that PGM type 200 follows. Enter 001-248 to select zone 1-248.
Proximity Tag Used
This option is used to define which proximity tag will activate PGM outputs programmed as [165] Prox Used. Enter 000 to enable this
PGM attribute for all user proximity tags, or enter user number 0002-1000 to have this attribute activated by a specific user proximity
tag.
Command Output 1-4
This option is used to assign a schedule, programmed in section [601]-[604], for PGM Types 166 and 121-128 to follow. Program
001-004 to for schedules 1-4. Program 000 to activate the PGM when a proximity tag is presented.
[012] System Lockout
Keypad Lockout – Number of Invalid Local Attempts
This option controls the number of invalid access code entries allowed before the keypad is locked.
When keypad lockout occurs, the system is inaccessible by keypad for the programmed duration. If the number of invalid attempts is
not reached within one hour, or if a valid access code is entered, the counter is reset to 0. Valid entries are 000 to 255 minutes.
Entering 000 disables the feature. Presenting an invalid tag counts toward keypad lockout.
Note:
For EN 50131 certified installations, maximum number of attempts is 10.
Keypad Lockout Duration
This programming option determines the length of time the keypad is locked out for. If the system cold starts while in keypad lockout,
the lockout is removed. Valid entries are 000 to 255 minutes. Entering 000 disables keypad lockout.
EN
Note:
For EN 50131 certified installations, minimum of duration is 90 s.
Remote Lockout DLS
This programming option determines the number of invalid access code entries allowed via SMS or DLS before remote access is
locked out for the programmed duration (see below). If the number of invalid attempts is not reached within one hour, or if a valid
access code is entered through SMS or DLS, the counter is reset to 0. The valid entries are 003 to 255 attempts. Default is 6 attempts.
The number of invalid attempts is fixed at 5 when using System Administrator Software and the lockout duration is 1 hour.
EN
Note:
DLS tries to connect using the programmed DLS Access code first and, if unsuccessful, using the default DLS access code.
Two failed attempts are counted if both codes are incorrect.
Remote Lockout Duration
This programming option determines how long the remote lockout lasts. If the system cold starts while in remote lockout, the lockout
restarts for the programmed duration. Valid entries are 001 to 255 minutes. Entering 000 disables remote lockout.