TFP1253

Page 2 of 8

NITROGEN/AIR 

SUPPLY LINES

AIR 

COMPRESSOR

1, 2

DRY/PREACTION 

SPRINKLER RISERS

AIR VENT, 

DRY

NITROGEN 

GENERATOR

TABLE B 

MODEL NG-1 1150, NG-1 1500, NG-1 2000, AND NG-1 3000 STAND-ALONE NITROGEN GENERATOR 

OPERATING PERFORMANCE

Notes:

1.  The Americas compressor vertical tank arrangement is shown. The EMEA and APAC compressor tank is a horizontal arrangement.
2.  See Table C for compressor dimensions for your region.

Model 

Number

Min. Supply Air 

SCFM (L/min)

Total System Capacity 

Gal. (L)

Single System  

Capacity

a

 

at 40 psig (2,8 bar) 

Gal. (L)

Single System  

Capacity

a

 

at 20 psig (1,4 bar) 

Gal. (L)

NG-1 1150

14.3 (405)

6500 (24605)

1150 (4353)

2300 (8706)

NG-1 1500

24.3 (688)

11000 (41640)

1440 (5451)

2880 (10902)

NG-1 2000

24 (688)

18500 (70030)

2025 (7666)

4050 (15331)

NG-1 3000

35 (992)

22500 (85172)

2900 (10978)

5800 (21955)

Notes:

a.  Capacity based on NFPA 13 30-minute fill requirement of largest single system

Model 

Number

Cabinet Without Bypass

Cabinet With Bypass

Weight 

Lbs 

(kg)

Width 

Inches 

(mm)

Height 

Inches 

(mm)

Depth 

Inches 

(mm)

Width 

Inches 

(mm)

Height 

Inches 

(mm)

Depth 

Inches 

(mm)

NG-1 1150 

NG-1 1500

24.5 

(622)

52.5 

(1334)

8.5 

(216)

32.5 

(826)

52.5 

(1334)

8.5 

(216)

152 

(69)

NG-1 2000 

NG-1 3000

24.5 

(622)

76 

(1930)

12.5 

(318)

32 

(813)

76 

(1930)

12.5 

(318)

300 

(136)

FIGURE 1 

MODEL NG-1 1150, NG-1 1500, NG-1 2000, AND NG-1 3000 STAND-ALONE NITROGEN GENERATOR 

INSTALLATION SCHEMATIC

TABLE A 

MODEL NG-1 1150, NG-1 1500, NG-1 2000, AND NG-1 3000 STAND-ALONE  NITROGEN GENERATOR 

DIMENSIONS AND WEIGHT

Summary of Contents for tyco NG-1 1150

Page 1: ...on on TYCO Dry Air Vent TAV D and to TFP1263 for more information on TYCO SMART Air Vent TSV D System Assembly The TYCO Nitrogen Generator unit includes the following components Steel enclosure cabinet with mem brane type nitrogen generator no nitrogen gas storage and manual bypass Power supply 120 VAC Single phase 60Hz 230 VAC Single phase 50Hz Single point nitrogen air discharge 1 2 in NPT Hour ...

Page 2: ...4605 1150 4353 2300 8706 NG 1 1500 24 3 688 11000 41640 1440 5451 2880 10902 NG 1 2000 24 688 18500 70030 2025 7666 4050 15331 NG 1 3000 35 992 22500 85172 2900 10978 5800 21955 Notes a Capacity based on NFPA 13 30 minute fill requirement of largest single system Model Number Cabinet Without Bypass Cabinet With Bypass Weight Lbs kg Width Inches mm Height Inches mm Depth Inches mm Width Inches mm H...

Page 3: ... N2 Purity at Discharge 98 or greater maximum of 2 0 oxygen N2 Pressure at Discharge Minimum of 15 psig 1 bar Max of feed air pressure minus 15 psig 1 bar N2 Water Dew Point Typically less than 70 F 57 C Note When connecting a TYCO Stand Alone Nitrogen Generator to an existing dry pipe preaction fire sprinkler system the existing fire sprinkler system s must be limited to a maximum leak rate of le...

Page 4: ... The nitrogen air discharge plumb ing from the nitrogen generator is to be connected directly to the sprinkler system valve trim using a minimum of 1 2 in to 1 in black steel galva nized steel or copper piping The size of the nitrogen air supply line is to be based on the length of pipe between the nitrogen generator and the fire sprinkler systems along with the total volume of the fire sprinkler ...

Page 5: ...GENERATOR RUNNING OUTPUT BYPASS MODE ALARM OUTPUT LEAK MONITORING OUTPUT POWER ON OFF OUTPUT NITROGEN SUPPLY LINE PRESSURE OUTPUT L1 N G PRESSURE SWITCH INCOMING POWER FUSE BOX BUILDING MANAGEMENT SYSTEM MONITORING POINTS POWER SUPPLY POWER DISTRIBUTION L1 G N N N G FIGURE 2A MODEL NG 1 1150 NG 1 1500 NG 1 2000 AND NG 1 3000 STAND ALONE NITROGEN GENERATOR AMERICAS SYSTEM SIGNAL MONITOR AND POWER S...

Page 6: ... drain connection be plumbed to a floor drain or building exterior When plumbing to a drain is not feasible an evaporative collection chamber can be used Note Ensure that the receiver tank auto drain is connected to an un switched power source 120 VAC for Americas 230 VAC for EMEA and APAC Note The Low Oil Level Sensor on the air compressor automatically shuts down air compressor until the proper ...

Page 7: ...rnal inlet piping by slowly opening the Depressurization Ball Valve in the cabinet to the left of the filter housing Step 4 Remove the filter housing by pulling down on the blue housing lock and turning the filter housing count er clock wise Step 5 Once the filter housing has been removed the filter cartridge inside is removed by first unscrewing the black retaining disc at the base of the cartrid...

Page 8: ...he Bypass Ball Valve Step 13 Open the Inlet and Outlet Ball Valves Compressors Maintenance of the Compressor For compressor maintenance please refer to the manufacturer s recom mended maintenance plan in the owner s manual for the compressor Limited Warranty For warranty terms and conditions visit www tyco fire com Ordering Procedure TYCO will supply a list of required part numbers to order throug...

Reviews: