Installation

The Series EC-8 Sprinklers must 

be installed in accordance with this 

section.

General Instructions

Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm).
A leak tight 3/4 in. NPT sprinkler joint 

should be obtained with a torque of 10 

to 20 lb-ft (13,4 to 26,8 N

·

m). Higher 

levels of torque may distort the sprin-

kler inlet with consequent leakage or 

impairment of the sprinkler.
Do not attempt to compensate for 

insufficient adjustment of an escutch-

eon plate by under-or over-tightening 

the sprinkler. Re-adjust the position of 

the sprinkler fitting to suit.

Step 1.

 The sprinkler must be installed 

with the deflector parallel to the mount-

ing surface. Pendent sprinklers must 

be installed in the pendent position.

Step 2.

 After installing the Style 30 or 

40 mounting plate (or other escutch-

eon, as applicable) over the sprinkler 

pipe threads, and with pipe thread 

sealant applied to the pipe threads, 

hand tighten the sprinkler into the 

sprinkler fitting.

Step 3.

 Wrench tighten pendent sprin-

klers using only the W-Type 3 (End A) 

Sprinkler Wrench. Wrench tighten the 

recessed pendent sprinklers using only 

the W-Type 23 Sprinkler Wrench. The 

wrench recess of the applicable sprin-

kler wrench (Ref. Figures 4 and 5) is to 

be applied to the sprinkler wrench flats 

(Ref. Figure 1).

Area

Style

135

°

F (57

°

C)

155

°

F (68

°

C)

16 x 16

Pendent

QR

QR

16 x 16

Style 30 Recessed

QR

QR

16 x 16

Style 40 Recessed

QR

QR

18 x 18

Pendent

QR

QR

18 x 18

Style 30 Recessed

QR

SR

18 x 18

Style 40 Recessed

QR

SR

20 x 20

Pendent

QR

SR

20 x 20

Style 30 Recessed

QR

SR

20 x 20

Style 40 Recessed

SR

SR

QR: Quick Response 
SR: Standard Response

Area

Style

135

°

F (57

°

C)

155

°

F (68

°

C)

16 x 16

Pendent

QR

QR

16 x 16

Style 30 Recessed

QR

N/A

16 x 16

Style 40 Recessed

N/A

N/A

18 x 18

Pendent

QR

QR

18 x 18

Style 30 Recessed

QR

N/A

18 x 18

Style 40 Recessed

N/A

N/A

20 x 20

Pendent

QR

QR

20 x 20

Style 30 Recessed

QR

N/A

20 x 20

Style 40 Recessed

N/A

N/A

QR: Quick Response 
SR: Standard Response 
N/A: Not Applicable

Description

Area

GPM

PSI

TY4232 (K=8.0) 

Pendent

16 x 16

26

10.6

18 x 18

33

17.0

20 x 20

40

25.0

1 ft = 0.3048 m 
1 ft

2

 = 0.093 m

1 gpm = 3.785 lpm 
1 psi = 0.06895 bar 
1 gpm/ft

2

 = 40.74 mm/min

TABLE B 

SENSITIVITY RATING FOR UL AND C-UL LISTING 

OF SERIES EC-8 SPRINKLERS

TABLE C 

SENSITIVITY RATING FOR FM APPROVAL 

OF SERIES EC-8 SPRINKLERS

TABLE D 

FLOW CRITERIA FOR UL AND C-UL LISTING 

OF SERIES EC-8 SPRINKLERS

Summary of Contents for tyco EC-8 Series

Page 1: ...ush pendent position whereas the Style 40 provides 3 4 in 19 1 mm of verti cal adjustment from the flush pendent position The adjustment provided by the Recessed Escutcheons reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut Corrosion resistant coatings where applicable are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obt...

Page 2: ...ded Coverage Sprinklers are to be installed in accor dance with the applicable Factory Mutual Loss Prevention Data Sheet Information provided in the FM Loss Prevention Data Sheet relate to but are not limited to hydraulic design ceiling slope and obstructions minimum and maximum allowable spacing and deflector to ceiling distance HAZARD TYPE TEMP BULB LIQUID SPRINKLER FINISH See Note 4 NATURAL BRA...

Page 3: ...hten pendent sprin klers using only the W Type 3 End A Sprinkler Wrench Wrench tighten the recessed pendent sprinklers using only the W Type 23 Sprinkler Wrench The wrench recess of the applicable sprin kler wrench Ref Figures 4 and 5 is to be applied to the sprinkler wrench flats Ref Figure 1 Area Style 135 F 57 C 155 F 68 C 16 x 16 Pendent QR QR 16 x 16 Style 30 Recessed QR QR 16 x 16 Style 40 R...

Page 4: ...ffice however instead of inspecting from the floor level a random sampling of close up visual inspections should be made so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating as it may be affected by the corrosive conditions present The owner is responsible for the inspection testing and maintenance of their fire protection system an...

Page 5: ...kler specify tem perature rating specify finish P N specify 135 F 57 C Natural Brass PSN 50 801 1 135 Signal White RAL9003 Polyester PSN 50 801 4 135 Chrome Plated PSN 50 801 9 135 155 F 68 C Natural Brass PSN 50 801 1 155 Signal White RAL9003 Polyester PSN 50 801 4 155 Chrome Plated PSN 50 801 9 155 Recessed Escutcheon Specify Style 30 or 40 Recessed Escutcheon with specify finish P N specify Ref...

Page 6: ...re Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Reviews: