TFP213

Page 3 of 4

FM Approved ceiling-level Storage 

Sprinklers for storage occupancy 

hazards and other similar high heat 

release type fires. When compared 

with other FM Approved Storage Sprin-

klers, the Model EC-25 Upright Sprin-

kler provides low hydraulic demand, 

the spacing advantages of extended 

coverage, and the FM Global obstruc-

tion benefits of an upright sprinkler.
Model EC-25 Upright Sprinklers should 

be used in conformance with applica-

ble FM Global Property Loss Preven-

tion Data Sheets.

Hydraulic Design

To determine the hydraulic design for 

the Model EC-25 Upright Sprinkler refer 

to the applicable FM Global Property 

Loss Prevention Data Sheet.

System Type

Wet pipe systems only

Sprinkler Spacing

The maximum coverage area per 

sprinkler is 196 ft² (18,2 m²). The 

minimum coverage area per sprinkler is 

100 ft² (9,3 m²). The maximum distance 

between sprinklers is 14 ft (4,3 m). The 

minimum distance between sprinklers 

is 10 ft (3,05 m).

Note: When a wall or obstruction 

makes a minimum spacing of 10 ft  

(3,05 m) impossible, consult FM Global 

Property Loss Prevention Data Sheet 

2.0 for applicable guidelines.

Sprinkler Location

Locate sprinklers with respect to 

the ceiling/roof in accordance with 

FM Global Property Loss Prevention 

Data Sheet 2.0.

Obstructions

Follow the obstruction requirements 

as detailed in FM Global Property Loss 

Prevention Data Sheet 2.0.

Other Details

All other design details should be in 

accordance with FM Global Property 

Loss Prevention Data Sheet 2.0 as well 

as any other applicable FM Global Data 

Sheet.

NFPA 13 – Alternative System 
Design (CMSA) Criteria

The TYCO Model EC-25 Extended Cov-

erage Upright Sprinklers (TY9128) have 

successfully undergone large-scale 

fire tests at FM Global to comply with 

the current edition of NFPA 13. As such, 

NFPA 13 may be utilized for design 

options with the Model EC-25 Upright 

Sprinklers for providing ceiling-only 

protection. 
This allows for the protection of Pallet-

ized, Single, Double, and Multiple Row 

Open Racks. Protection is up to 30 ft  

(9,1 m) of Cartoned, Unexpanded 

Group A Plastic Commodities in a 

maximum 35 ft (11 m) ceiling con-

dition with extended spacing up to  

196 ft² (18,2 m²). This protection is 

delivered while maintaining very rea-

sonable flow and pressure require-

ments. Pipe sizes as well as water 

supply requirements can now be kept 

to a minimum when compared to other 

design methods for high piled storage 

challenges.

Storage Type

NFPA

FM Global

Sprinkler Type

CMDA

CMDA/CMSA

Response Type

SR

QR

System Type

Wet/Dry/ Preaction

Wet

Temperature Rating ˚F (˚C)

165˚F (74˚C)  

212˚F (100˚C)

165˚F (74˚C)  

212˚F (100˚C)

Open Frame (i.e., no solid shelves), Single, Double, Multiple-

Row, or Portable Rack Storage of Class I-IV and Group A or 

B Plastics

Refer to NFPA 13

Refer to FM 2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and Group A or 

B Plastics

Refer to NFPA 13

Refer to FM 2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13

Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13

Refer to FM 2-0 and 8-3

Roll Paper Storage 

(Refer to the Standard)

Refer to NFPA 13

Refer to FM 8-21

Flammable/Ignitable Liquid Storage 

(Refer to the Standard)

Refer to NFPA 30

Refer to FM 7-29

Aerosol Storage 

(Refer to the Standard)

Refer to NFPA 30B

Refer to FM 7-31

Automotive Components in Portable Racks 

(Control mode only; refer to the Standard)

Refer to NFPA 13

N/A

N/A – Not Applicable

TABLE B 

MODEL EC-25 UPRIGHT SPRINKLER

 

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW