TFP213

Page 2 of 4

Design 

Criteria

UL and C-UL Listing Criteria

NFPA 13, Chapters 12 thru 20 –

Density / Area Design

The TYCO Model EC-25 Extended 

Coverage Upright Sprinklers (TY9128) 

are UL and C-UL Listed for installa-

tion in accordance with the extended 

coverage upright spray sprinkler 

requirements of NFPA 13 or other appli-

cable NFPA standards when used in  

conjunction with the following 

guidelines:

•  Protection of extra hazard and high-

piled storage occupancies where 

area/density design criteria are 

provided.

•  Unobstructed or non-combustible 

obstructed construction.

•  Model EC-25 Sprinklers, having 

been specifically tested and Listed 

for non-combustible obstructed 

construction, are suitable for use 

within trusses or bar joists having 

non-combustible web members 

greater than 1 in. (25,4 mm) when 

applying the 4 times obstruction 

criteria rule defined under “Obstruc-

tions to Sprinkler Discharge Pattern 

Devel opment.”

•  Maximum coverage area per 

sprinkler is 196 ft² (18,2 m²).

•  Maximum distance between sprin-

klers is 15 ft (4,6 m) when the 

coverage area does not exceed 

144 ft² (13,4 m²), and the maximum 

distance between sprinklers is 

 

14 ft (4,3 m) when the coverage 

area does not exceed 196 ft² 

 

(18,2 m²).

•  Minimum distance between sprin-

klers is 8 ft (2,44 m).

•  Minimum flow requirement is based 

on the design density applied 

over the actual coverage area per 

sprinkler. 

For example, when:

A sprinkler spacing is 14 ft × 12 ft − 6 in.  

(4,3 m × 3,8 m) or 175 ft² (16,3 m²), 

and the design density is 0.6 gpm/ft²  

(24,4 mm/min), the sprinkler design 

flow rate is 105 gpm (397 Lpm) and 

the required design pressure is  

17.4 psi (1,2 bar).

•  The minimum clearance between 

the deflector and the top of storage 

is 36 in. (0,9 m). For clearances of 

36 in. (0,9 m) up to 48 in. (1,21 m), 

the minimum design pressure is 

22 psi (1,52 bar). For clearances 

of 48 in. (1,21 m) and greater, the 

minimum design pressure is estab-

lished by the minimum flow require-

ment. However, the pressure can 

never be less than 7 psi (0,5 bar).

•  Ordinary and intermediate temper-

ature rated Model EC-25 Upright 

Sprinklers have been investigated 

for use in high-piled storage occu-

pancies at the hydraulic demand 

normally associated with high 

temperature sprinklers. As such, 

the Model EC-25 Upright Sprinklers 

are listed storage sprinklers having 

a K-factor greater than 11.2 (161,4) 

and having ordinary and interme-

diate temperature ratings of 165°F 

or 74°C and 214°F or 101°C. Conse-

quently, the Model EC-25 Sprin-

klers, in accordance with NFPA 13, 

may be used in conjunction with the 

density curves for high temperature 

sprinklers.

•  NFPA obstruction rules for Extended 

Coverage Sprinklers must be utilized.

System Type

Wet pipe, dry pipe, and pre-action 

systems are acceptable.

FM Approval Criteria

FM Loss Prevention Data Sheets 

2-0, 3-26, and 8-9

TYCO Model EC-25 Extended Cover-

age 25.2K Upright Sprinklers (TY9128) 

are FM Approved to be utilized in accor-

dance with the following guidelines.

Application

The Model EC-25 Extended Cov-

erage Upright Sprinklers are 

1-  Frame
2-  Deflector

3-  Compression Screw
4-  Hook
5-  Strut
6-  Link Assembly

7-  Button

8-  Gasketed Spring Plate
9-  Ejection Spring

10-  Deflector Nut

* ISO 7-R1 pipe thread can be 
provided on special request.

Item

Description

Sprinkler Identification Number (SIN)

TY9128

K-factor (gpm/psi) (lpm/bar)

25.2 gpm/psi

½

 (362,9 lpm/bar

½

)

Temperature Rating ˚F (˚C)

165˚F (74˚C)  

212˚F (100˚C)

Thread Size

1 in. NPT or ISO 7-R 1

Sprinkler Orientation

Upright

Maximum Working Pressure, psi (bar)

175 psi (12,1 bar)

*

7

1

1" NPT

8

6

9

5

4

2

WRENCH

FLATS

TEMPERATURE

RATING

9/16"

(14,3 mm)

NOMINAL

MAKE-IN

3-3/4"

(95,3 mm)

3

10

2-9/16" DIA.

(65,0 mm)

FIGURE 1 

MODEL EC-25 UPRIGHT SPRINKLER, 25.2K 

EXTENDED COVERAGE

TABLE A 

MODEL EC-25 UPRIGHT SPRINKLER 

TECHNICAL DATA