TEC2245-4 L
ON
W
ORKS
® Network Thermostat Controller with Single Proportional Output and One-Speed
Fan Control Installation Instructions
8
You cannot send the Neuron ID while in the Installer
Configuration menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
The UI3 input provides changeover of hot/cold water
switching, or supply air temperature monitoring at the
thermostat controller.
Each input can be configured to the Selection Options
included in Table 4.
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation. See
Table 3, and Figure 8 through Figure 11.
Note:
The modes presented to the user are
dependent upon the sequence of operation selected.
For 2-pipe applications using a Change Over Sensor
(COS), choose
0 = Cooling Only
. Changeover occurs
between
Cooling Only
and
Heating Only
.
Table 3: Selection Options for Sequence of Operation
Selection Option
Control Curve
Terminal Numbers Used
(See Table 1 and Figure 6)
0: Cooling Only
10:
Proportional Cooling
1: Heating Only
10:
Proportional Heating
2: Cooling and Reheat
6 and 7:
Reheat
10:
Proportional Cooling
3: Heating and Reheat
6 and 7:
Reheat
10:
Proportional Heating
Figure 8: Cooling Only
Temperature Increase
( Increments of 1F /0.5C )
o
o
Device Closed
Cooling Setpoint
Device Opened
On/Off, Floating,
or Proportional
Output
F
IG
:c
l_
o
n
Figure 9: Heating Only
Temperature Increase
( Increments of 1F /0.5C )
o
o
Device Closed
Heating Setpoint
Device Opened
On/Off, Floating,
or Proportional
Output
FI
G
:ht
_
on
Figure 10: Cooling with Reheat
Temperature Increase
( Increments of 1F /0.5C )
o
o
Heating Setpoint
Device
Closed
Cooling Setpoint
Device
Opened
F
IG
:c
l_
rh
t
Deadband
Reheat
On/Off, Floating,
or Proportional
Outputs
Heating Output
Cooling output
Off
Off
On
On
Figure 11: Heating with Reheat
Temperature Increase
( Increments of 1F /0.5C )
o
o
F
IG
:h
t_r
ht
0%
100%
Reheat
On/Off, Floating,
or Proportional
Output
Off
Off
On
On