TECHNICAL GUIDE

SPLIT-SYSTEM 
AIR CONDITIONERS

13 SEER – R-410A – 3 PHASE

MODELS:
TCGD30 THRU 60
(2.5 THRU 5 NOMINAL TONS)

Due to continuous product improvement, specifications 
are subject to change without notice.

Visit us on the web at www.york.com

Additional rating information can be found at 

www.ahridirectory.org

LISTED

ISO 9001

Certified Quality

Management System

 

TECHNICAL
GUIDE 

TECHNICAL
GUIDE 

415571-UTG-C-0309

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

The 13 SEER Series condensing unit is the outdoor part of a
versatile system of air conditioning. It is designed to be custom-
matched with one of UPG’s complete line of evaporator sec-
tions, with each serving a specific function. Matching Air Han-
dlers are available for upflow, downflow, or horizontal
applications to provide a complete system. Electric Heaters are
available, if required. Add-on coils are available for use with
upflow, downflow, or horizontal furnaces and air handlers.

WARRANTY

1-year limited parts warranty.

5-

year limited compressor warranty.

FEATURES

QUALITY CONDENSER COILS -

 The coil is constructed of

aluminum microchannel tubing and enhanced aluminum fins
for increased efficiency and corrosion protection.

PROTECTED COMPRESSOR -

 The compressor is inter-

nally protected against high pressure, temperature, and
externally by a factory installed high pressure switch. This is
accomplished by the simultaneous operation of high pres-
sure relief valve and a temperature sensor which protects the
compressor if undesirable operating conditions occur. A liq-
uid line filter-drier further protects the compressor.

DURABLE FINISH -

 The cabinet is made of pre-painted

steel. The pre-treated galvanized steel provides a better
paint to steel bond, which resists corrosion and rust creep.
Special primer formulas and matted-textured finish insure
less fading when exposed to sunlight.

LOWER INSTALLED COST -

 Installation time and costs are

reduced by easy power and control wiring connections.
Available in sweat connect models only. The unit contains
enough refrigerant for matching indoor coils and 15 feet of
interconnecting piping. The small base dimension means
less space is required on the ground or roof.

TOP DISCHARGE -

 The warm air from the top mounted fan

is blown up away from the structure and any landscaping.
This allows compact location on multi-unit applications.

LOW OPERATING SOUND LEVEL -

 The upward air flow

carries the normal operating noise away from the living area.
The rigid top panel effectively isolates any motor sound. Iso-
lator mounted compressor and the rippled fins of the con-
denser coil muffle the normal fan motor and compressor
operating sounds.

LOW MAINTENANCE -

 Long life permanently lubricated

motor-bearings need no annual servicing.

EASY SERVICE ACCESS -

 Fully exposed refrigerant con-

nections, and a single panel covering the electrical controls
make for easy servicing of the unit.

SECURED SERVICE VALVES -

 Secured re-usable service

valves are provided on both the liquid and vapor sweat con-
nections for ease of evacuating and charging.

U.L. and C.U.L. listed -

 approved for outdoor application.

Agency Listed

 

-

 U.L. and C.U.L. listed - approved for out-

door application. The unit is certified in accordance with the
Unitary Small Equipment certification program, which is
based on ARI Standard 210/240.

Summary of Contents for TCGD30

Page 1: ...liq uid line filter drier further protects the compressor DURABLE FINISH The cabinet is made of pre painted steel The pre treated galvanized steel provides a better paint to steel bond which resists corrosion and rust creep Special primer formulas and matted textured finish insure less fading when exposed to sunlight LOWER INSTALLED COST Installation time and costs are reduced by easy power and co...

Page 2: ...2950 2950 3600 2050 3200 2950 2950 3600 Coil Face Area Sq Ft 9 6 13 07 14 16 14 16 18 68 9 6 13 07 14 16 14 16 18 68 Rows Deep 1 1 1 1 1 1 1 1 1 1 Fin Inches 23 23 23 23 23 23 23 23 23 23 Liquid Line Set OD Field Installed 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 3 8 Vapor Line Set OD Field Installed 3 4 3 4 7 8 7 8 7 8 3 4 3 4 7 8 7 8 7 8 Unit Charge Lbs Oz 4 3 14 4 9 4 5 4 9 5 6 3 14 4 9 4 5 4 9 5 6 ...

Page 3: ...Charge for Various Matched Systems Outdoor Unit TCGD30S4 3 4 S1 TCGD36S4 3 4 S1 TCGD42S4 3 4 S1 TCGD48S4 3 4 S1 TCGD60S4 3 4 S1 Required Orifice or TXV 1 2 0 061 4F1 0 065 4G1 0 075 4G1 0 073 4H1 0 087 4J1 Factory Charge lbs oz 3 14 4 9 4 5 4 9 5 6 Indoor Coil3 4 Additional Charge oz AHP30 0 AHP36 2 0 AHP42 0 0 AHP SHP60 0 0 AHX30 0 AHX36 2 0 AHX42 8 2 AHX48 0 AHX60 4 F4FP024 F4FP036 F4FP040 0 F5F...

Page 4: ... 21 1255 35 0 24 8 13 00 11 00 AHX36 21 1225 35 2 25 0 13 50 11 50 AHX42 21 1190 35 4 25 2 14 00 11 80 F5FP048 24 1235 35 0 24 8 13 00 11 00 F6FP042 21 1290 35 8 25 8 13 50 11 50 TCGD42S4 3 4 S1 AHP42 21 1485 41 0 29 2 13 00 11 00 AHX42 21 1395 42 0 29 9 14 50 12 00 F5FP048 24 1455 41 0 29 2 13 00 11 00 F6FP042 21 1455 42 0 30 1 14 00 11 75 F6FP048 24 1380 41 5 29 4 13 50 11 70 TCGD48S4 3 4 S1 AHP...

Page 5: ...1200 35 0 24 8 13 00 11 00 1000 1400 21 24 UC48 1200 35 0 24 8 13 00 11 00 TCGD42S4 3 4 S1 1200 1600 17 21 FC MC PC43 1400 42 0 29 2 13 00 11 00 1200 1600 21 24 FC MC PC48 1400 42 0 29 2 13 00 11 00 1200 1600 21 HC42 1400 42 0 29 2 13 00 11 00 1200 1600 21 24 UC48 1400 42 0 29 2 13 00 11 00 TCGD48S4 3 4 S1 1400 1800 21 24 FC MC PC48 1600 48 0 34 4 13 00 11 00 1400 1800 21 24 FC MC PC60 1600 48 0 3...

Page 6: ... MC PC43C 21 1260 35 4 25 4 13 45 11 40 T 9X C20 FC MC PC43C 21 1185 35 0 24 6 13 55 11 40 T 8 L X C16 FC MC PC48C 21 1185 35 6 25 2 14 00 11 50 T 8 L X C20 FC MC PC48C 21 1270 35 8 25 8 14 00 11 50 T 9X C16 FC MC PC48C 21 1280 35 8 25 8 13 70 11 50 T 9X C20 FC MC PC48C 21 1205 35 4 25 0 13 70 11 50 T 9X D20 FC MC PC48D 24 1240 35 4 25 0 13 70 11 50 T 8 L X C16 UC48C 21 1185 34 2 24 8 13 50 11 50 ...

Page 7: ...D 21 1690 57 0 37 8 13 50 11 00 T 9X C16 FC PC60C 21 1575 56 0 37 8 13 30 11 00 T 9X C20 FC PC60C 21 1560 56 0 37 8 13 30 11 00 T 9X D20 FC MC PC60D 24 1630 56 5 37 8 13 30 11 00 T 9X C20 FC MC PC60D 21 1645 56 5 37 8 13 30 11 00 T 8 L X C20 FC MC62D 21 1665 57 0 37 8 13 50 11 00 T 8 L X C16 UC60C 21 1640 56 0 37 2 13 00 11 00 T 8 L X C20 UC60D 21 1735 56 5 38 5 13 00 11 00 T 9X C16 FC PC60C 21 15...

Page 8: ...tandards TYPICAL INSTALLATION TYPICAL FIELD WIRING UNIT MODEL dBA 230V 460V 30 76 76 36 76 76 42 77 76 48 77 77 60 78 78 THERMOSTAT SEAL OPENING S WITH PERMAGUM OR EQUIVALENT TO INDOOR COIL TO FURNACE OR AIR HANDLER TERMINAL BLOCK NEC CLASS 2 WIRING NEC CLASS 1 WIRING ALL OUTDOOR WIRING MUST BE WEATHERPROOF CONTROL ACCESS PANEL WEATHERPROOF DISCONNECT SWITCH MINIMUM 18 SERVICE ACCESS CLEARANCE ON ...

Page 9: ... 2 1 2 1 2 2 2 3 2 2 2 2 2 2 2 2 2 3 2 2 2 2 2 2 2 2 2 3 105 T C 20 5 21 8 20 4 23 7 26 3 22 0 23 1 21 3 24 3 26 4 23 6 24 5 22 1 24 8 26 4 S C 21 0 20 7 17 1 17 4 13 2 22 6 22 7 19 1 19 7 14 3 24 3 24 7 21 0 22 0 15 4 KW 2 3 2 3 2 3 2 4 2 4 2 4 2 4 2 3 2 4 2 5 2 4 2 4 2 3 2 4 2 5 115 T C 18 6 19 8 17 9 20 9 23 5 19 9 21 0 18 8 21 4 23 5 21 2 22 2 19 6 21 8 23 6 S C 19 1 18 9 15 9 16 4 12 3 20 5 2...

Page 10: ... 2 7 2 5 2 6 2 6 2 6 2 6 105 T C 27 9 28 8 27 2 29 8 32 5 27 0 27 8 26 6 29 4 32 2 26 0 26 9 25 9 29 0 31 9 S C 28 7 28 9 25 0 25 0 18 4 27 3 27 2 23 2 23 2 17 3 25 8 25 6 21 5 21 4 16 2 KW 2 8 2 8 2 8 2 8 2 9 2 8 2 8 2 8 2 8 2 9 2 7 2 8 2 7 2 8 2 9 115 T C 24 6 26 0 24 2 26 8 30 1 23 9 25 1 23 4 26 3 29 8 23 3 24 1 22 6 25 9 29 5 S C 26 3 26 3 22 8 24 1 17 8 24 9 24 8 21 3 22 2 16 6 23 5 23 3 19 ...

Page 11: ...3 2 3 3 3 4 3 3 3 3 3 3 3 3 3 4 3 3 3 3 3 3 3 4 3 4 105 T C 35 3 34 7 32 8 37 4 38 7 37 5 36 7 34 2 38 6 39 8 39 8 38 8 35 6 39 8 40 9 S C 32 3 32 1 26 5 26 4 19 6 34 5 34 5 28 8 28 4 20 4 36 7 37 0 31 1 30 5 21 2 KW 3 5 3 5 3 5 3 6 3 7 3 5 3 5 3 5 3 6 3 7 3 6 3 6 3 5 3 6 3 7 115 T C 32 4 31 7 29 2 33 4 34 8 34 5 33 6 30 5 34 6 35 7 36 5 35 5 31 8 35 7 36 7 S C 29 7 30 0 25 0 24 9 18 2 31 6 31 9 2...

Page 12: ...45 4 37 1 37 0 26 3 KW 3 5 3 5 3 5 3 6 3 7 3 6 3 6 3 5 3 7 3 8 3 6 3 6 3 6 3 7 3 8 105 T C 39 8 39 4 37 3 42 4 43 6 41 6 41 1 38 4 43 4 44 0 43 5 42 9 39 5 44 4 44 5 S C 37 1 37 0 30 9 30 9 22 9 38 9 39 3 32 9 33 0 23 9 40 8 41 5 34 9 35 1 25 0 KW 3 8 3 8 3 8 3 9 4 0 3 9 3 9 3 8 3 9 4 1 3 9 3 9 3 8 4 0 4 1 115 T C 36 5 35 9 32 7 38 0 39 3 38 1 37 5 33 9 38 9 39 8 39 7 39 1 35 1 39 8 40 2 S C 33 9 ...

Page 13: ... 37 9 32 3 50 7 50 9 41 4 38 8 30 8 49 0 53 6 43 9 42 3 29 4 KW 4 3 4 3 4 3 4 4 4 5 4 3 4 3 4 3 4 4 4 4 4 3 4 3 4 3 4 4 4 4 105 T C 56 4 52 2 48 8 54 0 60 1 54 0 54 3 50 5 55 7 59 7 51 6 56 3 52 2 57 4 59 4 S C 49 7 45 9 37 5 36 5 29 7 47 9 48 3 40 0 38 7 29 4 46 2 50 6 42 5 40 9 29 0 KW 4 9 4 9 4 9 4 9 5 0 4 9 4 9 4 9 5 0 5 0 4 9 4 9 4 9 5 0 5 0 115 T C 53 8 48 8 45 2 50 2 54 8 51 2 50 9 46 8 51 ...

Page 14: ... change without notice Printed in U S A 415571 UTG C 0309 Copyright 2009 by Johnson Controls Inc All rights reserved Supersedes 415571 UTG B 0708 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...